| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| | SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC |
| | RE E3606.3 |
| | 2. THE # 6 EQUIPMENT GROUNDING CONDUCTOR SHOULD NOT BE |
| | INCLUDED IN THE CONDUIT FROM THE METER TO THE MAIN |
| | PANEL. PROVIDE CORRECTION. NEC 250.6; FBC RE E3610.4 |
| | 3. RISER DIAGRAM SHOWS THREE 4/0 CONDUCTORS IN A 1 1/2 |
| | INCH CONDUIT. THIS CONDUIT IS UNDERSIZED FOR THE WIRE |
| | SIZE. PROVIDE CORRECTION. NEC CHAPTER 9 TABLES, |
| | INFORMATIVE ANNEX C |
| | 4. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 |
| | 5. RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS SHALL |
| | HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC |
| | 210.8(A)(9); FBC RE E3902.9 |
| | 6. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, |
| | SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN |
| | KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| | PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, |
| | RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND |
| | SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS |
| | INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES. |
| | SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION. |
| | PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902; |
| | FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS APPLICABLE. |
| | 7. PROVIDE WEATHER PROOF GFCI PROTECTED RECEPTACLE |
| | OUTLET FOR EACH BALCONY (DECK) ACCESSIBLE FROM THE |
| | DWELLING UNIT. NEC 210.52(E)(3); FBC RE E3901.7 |
| | 8. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| | 210.8(D); FBC RE E3902.10 |
| | 9. RISER DIAGRAM SHOWS THE ELECTRCAL PANELS AS MAIN |
| | BREAKER PANELS, BUT THE PANEL SHCEDULES SHOW THEM AS |
| | MAIN LUG ONLY PANELS. CORRECT DISCREPANCY. WPB FBC |
| | 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |