Plan Review Notes
Plan Review Notes For Permit 19030266
Permit Number 19030266
Review Stop P
Sequence Number 2
Notes
Date Text
2019-05-23 09:34:251) SUBMIT NEW ENERGY CALCULATIONS. THE CALCULATIONS
 STILL SHOW THE EF RATING OF THE WATER HEATER AS .86.
 WATER HEATERS UP TO 55 GALS. SHALL HAVE AN EF RATING OF
 .95. 2ND REQUEST.
 2) THE WATER CLOSET IN THE POWDER ROOM IS NOT SHOWN ON
 THE SANITARY RISER. WPB AMEND. TO FBC SEC. 107.2.1.
 3) THE TUB AND WATER CLOSET IN THE MASTER BATH ARE NOT
 VENTED. 2017 FBC-RES. SEC. P3101.2, P3101.2.1.
 4) THE SHOWER IN THE MASTER BATH IS NOT SHOWN ON THE
 SANITARY RISER. WPB AMEND. TO FBC SEC. 107.2.1.
 5) CLEANOUTS ARE REQUIRED IN THE BASE OF THE STACKS TO
 THE 2ND FLOOR. 2017 FBC-RES. SEC.P3005.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW