Plan Review Notes
Plan Review Notes For Permit 19030266
Permit Number 19030266
Review Stop P
Sequence Number 1
Notes
Date Text
2019-03-25 08:16:0203/25/2019 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE WATER HEATER ON YOUR FLORIDA ENERGY EFFICIENCY
 FORM R405-2017 IS SHOWING THE E.F AS .92. AS OF APRIL
 16, 2015, ALL RESIDENTIAL WATER HEATERS ARE REQUIRED TO
 BE A MIN .95 E.F UP TO 55 GALLONS. THIS IS DEFINED IN
 THE CODE OF FEDERAL REGULATION (CFR) 75 FR 2012.
 2. PLEASE SHOW TEMPERING DEVICE FOR ROMAN TUB AND
 LOCATION IF DOES NOT HAVE A INTEGRAL ONE, 2017 FBC
 R2713.3 BATHTUB AND WHIRLPOOL BATHTUB VALVES. HOT WATER
 SUPPLIED TO BATHTUBS AND WHIRLPOOL BATHTUBS SHALL BE
 LIMITED TO A TEMPERATURE OF NOT GREATER THAN 120?F
 (49?C) BY A WATER TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3, EXCEPT WHERE SUCH
 PROTECTION IS OTHERWISE PROVIDED BY A COMBINATION
 TUB/SHOWER VALVE IN ACCORDANCE WITH SECTION P2708.4.
 3. PLEASE SHOW BUILDING CLEAN OUT ON ISOMETRIC DIAGRAM
 ON PAGE A-7, WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  