| 2019-03-25 08:16:02 | 03/25/2019 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE WATER HEATER ON YOUR FLORIDA ENERGY EFFICIENCY |
| | FORM R405-2017 IS SHOWING THE E.F AS .92. AS OF APRIL |
| | 16, 2015, ALL RESIDENTIAL WATER HEATERS ARE REQUIRED TO |
| | BE A MIN .95 E.F UP TO 55 GALLONS. THIS IS DEFINED IN |
| | THE CODE OF FEDERAL REGULATION (CFR) 75 FR 2012. |
| | 2. PLEASE SHOW TEMPERING DEVICE FOR ROMAN TUB AND |
| | LOCATION IF DOES NOT HAVE A INTEGRAL ONE, 2017 FBC |
| | R2713.3 BATHTUB AND WHIRLPOOL BATHTUB VALVES. HOT WATER |
| | SUPPLIED TO BATHTUBS AND WHIRLPOOL BATHTUBS SHALL BE |
| | LIMITED TO A TEMPERATURE OF NOT GREATER THAN 120?F |
| | (49?C) BY A WATER TEMPERATURE LIMITING DEVICE THAT |
| | CONFORMS TO ASSE 1070 OR CSA B125.3, EXCEPT WHERE SUCH |
| | PROTECTION IS OTHERWISE PROVIDED BY A COMBINATION |
| | TUB/SHOWER VALVE IN ACCORDANCE WITH SECTION P2708.4. |
| | 3. PLEASE SHOW BUILDING CLEAN OUT ON ISOMETRIC DIAGRAM |
| | ON PAGE A-7, WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |