Plan Review Notes
Plan Review Notes For Permit 19030266
Permit Number 19030266
Review Stop E
Sequence Number 1
Notes
Date Text
2019-03-28 10:42:46ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1)SECOND FLOOR CO MISSING AT BEDROOMS
  
 R315.1CARBON MONOXIDE PROTECTION.
 EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A
 FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE,
 AN ATTACHED GARAGE, OR OTHER FEATURE, FIXTURE, OR
 ELEMENT THAT EMITS CARBON
 MONOXIDE AS BYPRODUCT OF COMBUSTION SHALL HAVE AN
 OPERATIONAL CARBON MONOXIDE ALARM INSTALLED WITHIN 10
 FEET OF EACH ROOM
 USED FOR SLEEPING PURPOSES.
  
 2) SECOND FLOOR SMOKE ALARMS LOOK TO BE TO CLOSE TO THE
 FANS
  
 R314.3LOCATION.
 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
  
 1.IN EACH SLEEPING ROOM.
 2.OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
 3.ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING
 BASEMENTS AND HABITABLE ATTICS AND NOT INCLUDING CRAWL
 SPACES AND UNINHABITABLE
 ATTICS. IN DWELLINGS OR DWELLING UNITS WITH SPLIT
 LEVELS AND WITHOUT AN INTERVENING DOOR BETWEEN THE
 ADJACENT LEVELS, A SMOKE ALARM INSTALLED
 ON THE UPPER LEVEL SHALL SUFFICE FOR THE ADJACENT LOWER
 LEVEL PROVIDED THAT THE LOWER LEVEL IS LESS THAN ONE
 FULL STORY BELOW THE UPPER LEVEL.
 4.SMOKE ALARMS SHALL BE INSTALLED NOT LESS THAN 3 FEET
 (914 MM) HORIZONTALLY FROM THE DOOR OR OPENING OF A
 BATHROOM THAT CONTAINS A
 BATHTUB OR SHOWER UNLESS THIS WOULD PREVENT PLACEMENT
 OF A SMOKE ALARM REQUIRED BY SECTION R314.3.
  
 3) RISER DIAGRAM AND PANEL SCHEDULE DO NOT HAVE SAME
 WIRE SIZES FOR SUB-PANEL
  
 PANEL SCHEDULE SHOWS #2 RISER SHOW 1/0
  
 PLEASE SPECIFY WIRE TYPE ON RISER (CU. OR AL)
  
 4) PANEL "A" SHOWS 150 AMPERE BUSS WITH A 200 AMPERE
 MAIN
 SPECIFY MAIN SIZE FOR PANEL "A"