Plan Review Notes
Plan Review Notes For Permit 19030266
Permit Number 19030266
Review Stop B
Sequence Number 1
Notes
Date Text
2019-04-05 16:16:34NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1-PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 SEC. R401.3 FBC-RESIDENTIAL (DRAINAGE).
 SEC. 107.2.5 CITY AMENDMENTS (SITE PLAN).
 SEC. 110.9 CITY AMENDMENTS (IMPACT OF CONSTRUCTION).
  
 2- PROVIDE SOIL TEST REPORT (2 COPIES) AS REQUIRED BY
 SEC. R401.4 FBC-RESIDENTIAL
  
 3- PLANS SUBMITTED HAVE A COPY OF THE ARCHITECT'S SEAL
 AND SIGNATURE. PLANS NEED TO HAVE ARCHITECT'S ORIGINAL
 SEAL AND SIGNATURE WHEN SUBMITTING DOCUMENTS FOR PUBLIC
 RECORDS AS REQUIRED BY 61G1-16.003 FAC.
  
 4- IT LOOKS LIKE SECOND FLOOR BEDROOM WINDOWS DON'T
 COMPLY WITH THE EMERGENCY ESCAPE AND RESCUE OPENINGS
 SEC. R310.2.1 FBC-RESIDENTIAL. WINDOW SCHEDULE SPECIFY
 5'-0" HIGH WINDOWS. TYPICALLY, 5-0" HIGH WINDOWS DON'T
 PROVIDE THE 24" CLEAR OPENING HEIGHT. PROVIDE
 MANUFACTURER'S CUT SHEETS SHOWING THAT SPECIFIED WINDOW
 SIZE PROVIDES 24" CLEAR OPENING AND MIN. TOTAL CLEAR
 OPENING OF 5.7S.F.
 NOTE: VISIT THE WEBSITE FOR WINDOWS PRODUCT APPROVAL
 SUBMITTED (CGI WINDOWS AND DOORS) FOR WINDOW SIZES THAT
 COMPLY WITH ALL THE EGRESS REQUIREMENTS AND REVISE
 WINDOW SCHEDULE AS REQUIRED.
  
 5- WINDOWS AND DOORS DESIGN PRESSURES:
 A)DOORS AND WINDOWS DESIGN PRESSURES SHOWN ON SHEET S-2
 DON'T MATCH THE DESIGN PRESSURES SHOWN ON SHEET A-6.
 REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 B) DESIGN PRESSURES SHOWN ON SHEET S-2 SPECIFY THAT
 DESIGN PRESSURES ARE BASED ON A TRIBUTARY AREA OF 20
 S.F.. THERE ARE SOME OPENINGS THAT ARE LESS THAN 20 S.
 F. THE DESIGN PRESSURES NEED TO BE CALCULATED BASED ON
 THE ACTUAL TRIBUTARY AREA (AND MEAN ROOF HEIGHT). IF
 INTERPOLATING , THEN THE DESIGN PRESSURES FOR THE LOWER
 EFFECTIVE AREA SHALL BE USED. SEE FOOTNOTES ON TABLE
 R301.2(2) FBC-RESIDENTIAL AND REVISE AS REQUIRED.
  
 6- SIZE OF WATER CLOSET DOOR IN THE MASTER BATHROOM
 DOESN'T COMPLY WITH SEC. R320 FBC-RESIDENTIAL. NEED
 DOOR THAT PROVIDES 29" CLEAR OPENING. REVISE AS
 REQUIRED.
  
 7- SPECIFY SIZE OF ATTIC ACCESS ABOVE GARAGE AND MASTER
 BEDROOM HALLWAY. AND, SPECIFY LOCATION AND SIZE OF
 ATTIC ACCESS ON THE SECOND FLOOR AS REQUIRED BY SEC.
 R807 FBC-RESIDENTIAL.
  
 8- ROOF SPRAY FOAM INSULATION:
 A) CLARIFY IF HOUSE IS DESIGNED AS HAVING A VENTED OR
 UNVENTED ROOF VENTILATION. SEC. 107.2.1 CITY AMENDMENTS
 AND SEC. R806 FBC-RESIDENTIAL. INSULATION
 SPECIFICATIONS SON SHEET A-2 CALL FOR R20 SPRAY FOAM
 INSULATION, WHILE SPECIFICATIONS ON BUILDING SECTIONS
 ON SHEET A-7 AND A-8 CALL FOR R30 BATT INSULATION.
 REVISE AS REQUIRED TO MATCH. NOTE: IF DESIGNING
 UNVENTED ATTIC, THEN SOFFIT VENTILATION NEEDS TO BE
 REVISED N THE THE WALL SECTIONS AS WELL.
  
 B) IF HOUSE IS DESIGNED WITH UNVENTED ROOF, THEN
 PROVIDE ICC EVALUATION REPORT (2 COPIES) FOR THE
 SPECIFIED SPRAY FOAM TO VERIFY COMPLIANCE WITH SEC.
 R316 FBC-RESIDENTIAL.
 NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 9- SPECIFY CARBON MONOXIDE ALARM WITHIN 10 FEET OF ALL
 SLEEPING ROOMS ON THE SECOND FLOOR AS REQUIRED BY SEC.
 R315.1 FBC-RESIDENTIAL.
  
 10- STAIR SECTION ON SHEET A-7:
 A)PROVIDE DETAIL/SPECIFICATIONS FOR STAIRWAY
 FIREBLOCKING AS REQUIRED BY SEC. R302.11
 FBC-RESIDENTIAL.
  
 B) CLARIFY TREAD SIZE. STAIR CALCULATIONS CALL FOR 10"
 TREAD WHILE STAIR SECTION CALLS FOR 11" TREAD. REVISE
 AS REQUIRED TO MATCH. SEC. R311.7.5.2 FBC-RESIDENTIAL.
  
 11- PROVIDE SPECIFICATIONS FOR CEILING DWELLING-GARAGE
 SEPARATION SHOWING COMPLIANCE WITH TABLE R302.6
 FBC-RESIDENTIAL.
  
 12- PROVIDE COMPLETE DETAILS ANS SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE TRELLIS OUTSIDE THE GREAT ROOM
 AREA. SEC. R301.2.1 FBC-RESIDENTIAL.
  
 13- TYPICAL ROOF NOTE SHOWN ON ALL WALL SECTIONS ON
 SHEET A-7 AND A-8: ARCHITECT IS SPECIFYING TO INSTALL
 ROOF TILES WITH 2-10D NAILS. ROOF TILE NOA 18-0829.05
 SUBMITTED HAVE DIFFERENT MOMENT OF RESISTANCE VALUES.
 ARCHITECT TO SPECIFY THE CALCULATED ROOF TILE MOMENT OF
 RESISTANCE AND CLEARLY IDENTIFY WHICH 10D NAILS FROM
 NOA SUBMITTED ARE REQUIRED TO MEET THE CALCULATED
 MOMENT OF RESISTANCE. SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: SEE RAS 127 FOR PROCEDURE TO DETERMINE THE MOMENT
 OF RESISTANCE.
  
 14- ALL WALL SECTIONS NEED TO SPECIFY 7/8" MIN. STUCCO
 THICKNESS NOT 5/8" THICKNESS AS REQUIRED BY TABLE
 R702.1(1). REVISE SPECIFICATIONS ON ALL WALL SECTIONS
 AS REQUIRED.
  
 15- NEED FOOTINGS PLACED NOT LESS THAN 12 INCHES BELOW
 FINISHED GRADE AS REQUIRED BY SEC. R403.1.4
 FBC-RESIDENTIAL. REVISE ALL WALL SECTIONS AS REQUIRED.
 CLEARLY SPECIFY THE MIN. FOOTING DEPTH.
  
 16- SHEET S-1:
 A)LOWER ROOF FRAMING PLAN: THERE ARE SOME CONNECTORS
 THAT ARE NOT SHOWN ON THE CONNECTOR SCHEDULE ON SHEET
 S-2. CLEARLY IDENTIFY CUSTOM CONNECTORS FOR ALL
 STRUCTURAL FRAMING MEMBERS THAT ARE NOT SHOWN ON THE
 CONNECTOR SCHEDULE. FOR EXAMPLE WHERE IS CONNECTOR "X",
 "XX", ETC. SEC. 107.2.1 CITY AMENDMENTS.
 NOTE: COORDINATE WITH DETAILS SHOWN ON SHEET S-3 AND
 S-4.
  
 B) CLEARLY SPECIFY THE TOP AND BOTTOM CONNECTORS OF ALL
 STEEL AND WOOD COLUMNS. SEC. 107.2.1 CITY AMENDMENTS.
 NOTE: COORDINATE WITH DETAILS SHOWN ON SHEET S-3 AND
 S-4.
  
 C) CLARIFY WHY THE STEEL COLUMNS SHOWN ON THE
 FOUNDATION PLAN ARE CALLED S/C 2 AND ON LOWER ROOF
 FRAMING PLAN ARE CALLED S/C 1?. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 17- SHEET S-2: REVISE THE ROOF TRUSSES TOP CHORD DEAD
 LOAD SPECIFIED UNDER THE ROOF FRAMING NOTES.
 A 5 PSF DEAD LOAD DOESN'T SEEM TO BE CORRECT IF
 INSTALLING CONCRETE ROOF TILES. REVISE AS REQUIRED.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 18-ENERGY CALCULATIONS:
 A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE OWNER'S NAME AND BUILDER'S NAME .
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 B) PROVIDE WINDOWS AND DOORS MANUFACTURER'S
 SPECIFICATIONS SHOWING THE U-FACTOR AND SHGC FACTOR
 SPECIFIED ON THE ENERGY CALCULATIONS ON ITEM #7 ON PAGE
 1 OF 5 AS REQUIRED BY SEC. R405.4.3 FBC-ENERGY
 CONSERVATION. NOTE: COORDINATE WITH PLANS AND PRODUCT
 APPROVALS SUBMITTED TO AVOID CONFLICTS/DELAYS.
  
 C) REVISE INSULATION R-VALUE SPECIFIED ON FLOOR OVER
 OTHER SPACE ON ITEM #8(B) TO MATCH PLANS.
 SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
 D) REVISE NUMBER OF OCCUPANTS SHOWN ON SPACES
 INFORMATION ON PAGE 2 OF 5 IS INCORRECT. WHY THERE ARE
 "0" OCCUPANTS IN A FOUR BEDROOM HOUSE?. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 E) REVISE WINDOWS OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS. FOR EXAMPLE: SLIDING GLASS DOORS DON'T
 HAVE A 5'-0" OVERHANG DEPTH, THERE IS A TRELLIS NOT A
 ROOF ON THE EXTERIOR SIDE OF THESE DOORS. REVISE AS
 REQUIRED. WINDOW #1 ON PAGE 3 OF 5 FACING NORTH DON'T
 HAVE A 15FT OVERHANG DEPTH. NOTE: SEE EXTERIOR
 ELEVATIONS AND CHECK/REVISE OVERHANG DEPTH AND
 SEPARATION OF ALL WINDOWS/DOORS AS REQUIRED TO MATCH
 PLANS. SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 F) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC-ENERGY
 CONSERVATION.
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE SHGC FACTOR
 SPECIFIED IN THE ENERGY CALCULATIONS WILL BE REQUIRED
 FOR INSPECTION.
  
 19- SURVEY SUBMITTED CAN NOT BE USED FOR CONSTRUCTION.
 SEE SURVEY NOTES ON SURVEY SUBMITTED. PROVIDE SURVEY
 SUITABLE FOR CONSTRUCTION. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 20- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 A)PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 B) 6" HARDI-PLANK SIDING AND 4" HARDI-TRIM AS SHOWN ON
 PLANS.
  
 21- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 22- WINDOW MULLIONS NOA 17-1018.07 SUBMITTED: REQUIRED:
 CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY
 COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 23- ENTRY DOORS SHOWN ON FIRST FLOOR PLAN DON'T MATCH
 DOOR SPECIFIED ON THE DOOR SCHEDULE AND DOOR SHOWN ON
 THE EXTERIOR ELEVATION. REVISE AS REQUIRED TO MATCH.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  