| 2019-03-28 16:09:27 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | 1) PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED |
| | PER CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE |
| | EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC |
| | R314.3, FBC 107.2.1 |
| | |
| | 2) PROVIDE AN OUTLET ON THE REAR OF THE BUILDING |
| | E3901.7 OUTDOOR OUTLETS. |
| | NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY |
| | ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6 |
| | FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE |
| | INSTALLED OUTDOORS AT THE FRONT AND |
| | BACK OF EACH DWELLING UNIT HAVING DIRECT ACCESS TO |
| | GRADE LEVEL. BALCONIES, DECKS, AND PORCHES THAT ARE |
| | ACCESSIBLE FROM INSIDE OF THE DWELLING UNIT SHALL HAVE |
| | AT LEAST ONE RECEPTACLE OUTLET |
| | INSTALLED WITHIN THE PERIMETER OF THE BALCONY, DECK, OR |
| | PORCH. THE RECEPTACLE SHALL BE LOCATED NOT MORE THAN 6 |
| | FEET, 6 INCHES (1981 MM) ABOVE THE BALCONY, DECK, OR |
| | PORCH SURFACE. [210.52(E)] |
| | |
| | 3) OUTLETS IN LAUNDRY TO BE GFCI PROTECTRD |
| | E3902.9 LAUNDRY AREAS. |
| | 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES |
| | INSTALLED IN LAUNDRY AREAS SHALL HAVE GROUND-FAULT |
| | CIRCUIT INTERRUPTER PROTECTION FOR PERSONNEL. |
| | [210.8(A)(9)] |
| | |
| | 4) OUTLETS IN THE LAUNDRY TO BE AFCI PROTECTED. |
| | E3902.16 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION. |
| | BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- |
| | AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY |
| | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| | DENS, BEDROOMS, SUN-ROOMS, |
| | RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND |
| | SIMILAR ROOMS OR AREAS SHALL BE PROTECTED BY ANY OF THE |
| | FOLLOWING: [210.12(A)] |