| 2019-03-21 14:11:07 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | JOSEAN A. DUPREY E.I., BN, PX | | | BUILDING PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6716 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 2ND REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | THE ENGINEERES DESIGN PRESSURES WERE PROVIDED. +66.7; | | | -70.3 | | | | | | 1. THE SINGLE HUNG WINDOW NOA #17-1114.07 PROVIDE TWO | | | OPTIONS. ONE OPTION WITH STANDARD FRAME SILL FOR A WIND | | | LOAD OF +60; -80 PSF AND OTHER OPTION WITH HI-RISE | | | FRAME SILL FOR A WIND LOAD OF +/-80. THE BUYERS ORDER | | | INDICATES THE WINDOW WITH +60; -80 PSF THAT IS NOT | | | MEETING THE ENGINEERED WIND LOADS. PLEASE VERIFY. FBC | | | 107 | | | | | | 2. PROVIDE DOORS PRODUCT APPROVAL. FBC 107 | | | | | | 3. PROVIDE MULLION PRODUCT APPROVAL. FBC 107 |
|