Plan Review Notes
Plan Review Notes For Permit 19030248
Permit Number 19030248
Review Stop P
Sequence Number 2
Notes
Date Text
2019-04-16 14:33:08PLUMBING 2ND REIVEW**DENIED**
  
 1) PROVIDE CLEAR FLOOR AND TURNING SPACE IN FRONT OF
 BREAK ROOM SINK. FBC-A 606.1
  
 2) SHT A-0.1 LIST THE PLUMBING CODE AS 2012
 INTENATIONAL. THE CURRENT CODE IN EFFECT AS OF
 12/31/2017 IS THE 2017 FLORIDA PLUMBING CODE 6TH ED.
 PLEASE REVISE SHEET. FBC 107.1
  
 3) SHT A0.2 SHOWS TITLE PAGE AS ( 2010 ADA
 ACCESSIBILITY DETAILS) AND ALSO TOP RIGHT OF PAGE NOTES
 SHOW THE INTENTION OF THIS SHEET IS TO SHOW THE
 REQUIREMENTS OF THE 2010 ADA?. PLEASE CLARIFY AS THE
 2010 IS 2 CODE CYCLE OLD. THIS BUILDING SHELL (PERMIT #
 18101337) AND YOUR CURRENTLY PERMIT APPLICATION FALLS
 UNDER THE 2017 6TH ED FLORIDA ACCESSIBILITY CODE
  
 4) PROVIDE DIGITALLY SIGNED PLANS WHEN SUBMITTING
 DIGITALLY. F.S 471
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  