 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected]) OR IN WRITING
 (FAX: 561-804-4774) AND APPROVED BY THE OFFICE OF THE
 FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 2) ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR.
  
 3) EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED
 WITH SIGNS OR STENCILING READING FIRE BARRIER-PROTECT
 ALL OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 4) SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO
 THE FIRE ALARM AND SPRINKLER SYSTEM.
  
  