| 2019-03-12 09:47:48 | PERMIT # 19030248 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | 1) FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING | | | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A | | | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN | | | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE | | | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST | | | BE SUBMITTED BY EMAIL ([email protected]) OR IN WRITING | | | (FAX: 561-804-4774) AND APPROVED BY THE OFFICE OF THE | | | FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY. | | | | | | 2) ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A | | | LOCK/UNLOCK INDICATOR. | | | | | | 3) EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED | | | WITH SIGNS OR STENCILING READING FIRE BARRIER-PROTECT | | | ALL OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN | | | HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE | | | SPACED NOT MORE THAN 15 FEET ON CENTER. | | | | | | 4) SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO | | | THE FIRE ALARM AND SPRINKLER SYSTEM. | | | | | | | | | SUE ELLEN CALDERON | | | FIRE INSPECTOR & INVESTIGATOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 644-7326 | | | |
|