| 2019-07-18 17:15:44 | FAILED |
| | |
| | PROVIDE WRITTEN RESPONSES TO COMMENTS. |
| | |
| | 1) THE ELECTRICAL AND TRASH ROOMS HAVE BEEN FLIPPED |
| | FROM THE CITY COMMISSION APPROVAL, SO THE ELEVATIONS |
| | HAVE CHANGED. ADDITIONALLY, THE FINAL ELEVATIONS SHOW |
| | LOUVERS AND CANOPIES THAT WERE NOT INCLUDED ON THE |
| | ORIGINAL APPROVAL. AN AS BUILT MINOR PD AMENDMENT IS |
| | REQUIRED TO BE SUBMITTED TO THE PLANNING DIVISION PRIOR |
| | TO THE FINAL INSPECTION. |
| | |
| | 2) THE ROOF PLANS SHOW MOUNTING CURBS FOR ROOFTOP |
| | EQUIPMENT. |
| | |
| | A. THE APPROVED PLANS DID NOT INCLUDE ANY ROOFTOP |
| | MECHANICAL EQUIPMENT. THE MECHANICAL EQUIPMENT, TO |
| | INCLUDE THE CHILLERS, WATER STORAGE TANKS AND THE |
| | GENERATOR WERE SHOWN THROUGH THE APPROVAL PROCESS IN |
| | THE SCREENED EQUIPMENT YARD ENCLOSURE AT GROUND LEVEL. |
| | |
| | B. EXPLAIN WHAT EQUIPMENT IS PROPOSED TO BE MOUNTED ON |
| | THE ROOF? THE MECHANICAL ROOF PLAN SHOWS OAR1, EAR2 AND |
| | EAR2 EQUIPMENT ON THE ROOF. ZONING STAFF WAS UNABLE TO |
| | LOCATED THE DETAILS FOR THESE FEATURES. |
| | |
| | C. PROVIDE INFORMATION THAT THE PROPOSED BUILDING |
| | PARAPETS ARE OF SUFFICIENT HEIGHT TO SCREEN THE ROOFTOP |
| | MECHANICAL EQUIPMENT, TO INCLUDE THE TRASH CHUTE VENT. |
| | |
| | 3) PRIOR TO ZONING APPROVAL OF THIS PERMIT, A TREE |
| | ALTERATION PERMIT MUST BE SUBMITTED TO THE PLANNING |
| | DIVISION AND APPROVED BY THE CITY'S LANDSCAPE PLANNER |
| | FOR THE DEVELOPMENT AREA. |
| | |
| | 4) SHEET C-5 SITE LAYOUT SHOWS A NEW 10 FOOT FPL |
| | EASEMENT AND LINE AND A RELOCATED EXISTING 12 FOOT |
| | UTILITY EASEMENT COMPARED TO THE APPROVED PLANS (NOTE: |
| | THE SURVEY PROVIDED WITH THE APPROVAL PROCESS SHOWS A |
| | 10 FOOT SOUTHERN BELL EASEMENT AT THIS LOCATION). THE |
| | PROPOSED FPL EASEMENT AND LINE DIRECTLY INTERFERE WITH |
| | THE LOCATION OF TREE LOCATIONS ON THE CITY COMMISSION |
| | APPROVED PLANS. ALL UTILITIES MUST USE THE EXISTING |
| | EASEMENT, SUBJECT TO ADJUSTMENT TO AVOID THE PROPOSED |
| | BUILDING, AND AVOID THE APPROVED TREES. THERE IS NO |
| | JUSTIFICATION FOR 22 FEET OF UTILITY EASEMENT. |
| | |
| | 5) SINCE THE BUILDING IS SHOWN ON TOP OF THE EXISTING |
| | EASEMENT RECORDED IN ORB 5832 PB 1420, YOU WILL NEED TO |
| | PROVIDE THE RELEASE AND RELOCATION AGREEMENT FOR THE |
| | EASEMENT PRIOR TO ZONING APPROVAL OF THIS PERMIT. |
| | |
| | NOTE: THE EXISTING CONDITIONS PLAN DOES NOT SHOW |
| | ANYTHING IN THE RECORDED EASEMENT. |
| | |
| | 6) MANY OF THE DIMENSIONS LISTED ON SHEET C-5 ARE NO |
| | LONGER ACCURATE. IT APPEARS THAT DIGITS WERE LEFT OFF ? |
| | EX. 21.3 FEET BECAME 1.3 FEET. CORRECT ALL LABELS. |
| | |
| | 7) SEPARATE PERMITS REQUIRED FOR: |
| | |
| | A. DUMPSTER ENCLOSURE |
| | B. GENERATOR |
| | C. HARDSCAPE |
| | D. BICYCLE RACKS |
| | E. LANDSCAPE |
| | F. PARKING LOTS, INCLUDING STRIPING. |
| | E. DECK |
| | F. PAVILION |
| | |
| | CONTACT ERIC SCHNEIDER @ (561) 822-1446 |