| Plan Review Notes For Permit 19030147 |
| Permit Number |
19030147 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-06-21 11:20:54 | BUILDING REVIEW COMMENTS: | | | | | | W.P.B. PERMIT: 19030147 | | | REVIEWED: JUNE 21, 2019 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER PX4191 | | | [email protected] | | | 561-805-6718 | | | | | | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) | | | FBC[B] = FBC BUILDING | | | | | | 1) 107.3.4 FBC[AMENDED] THE REGISTERED DESIGN | | | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE | | | FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS | | | PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED | | | SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF | | | THE BUILDING. THOSE PRODUCTS WHICH ARE REGULATED BY FAC | | | RULE 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY | | | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. | | | -PLEASE SELECT THE SYSTEM BE USED IN THE PRODUCT | | | APPROVAL. THIS WILL PROVIDE THE MAXIMUM DESIGN | | | PRESSURE. | | | | | | 2) [RAS 117]PROVIDE ENGINEERING FOR ENHANCED MECHANICAL | | | ATTACHMENT AS STATED IN PRODUCT APPROVAL NOTES #9. | | | | | | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F | | | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME | | | [email protected] | | | | | | | | | |
|