Plan Review Notes
Plan Review Notes For Permit 19030147
Permit Number 19030147
Review Stop P
Sequence Number 2
Notes
Date Text
2019-07-03 12:39:34 
 2ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
  
 PREVIOUS COMMENTS NOT COMPLIED : COPIED FROM RESPONSE
 LETTER
  
 3) PROVIDE A MATRIX FOR THE FHA REQUIREMENTS INDICATE
 THE DESIGN SPEC FOR THE BATHROOMS A OR B PER WPB AMEND
 TO FBC 107.2.1
 RESPONSE: THE FAIR HOUSING ACT CHECKLIST AS PRODUCED BY
 THE EQUAL RIGHTS CENTER IS REFERENCED ATTACHMENT
 A-3-FHA CHECKLIST.
 THE DESIGN SPEC FOR THE BATHROOMS IS A.
 THE COMPARTMENTALIZED BATHROOMS ARE RE-DESIGNED TO
 COMPLY WITH THIS STANDARD. PLEASE REFER TO REVISED AND
 CLOUDED DRAWINGS.
  
 THE FHA CHECKLIST REFERENCED ABOVE IS NOT AN APPROVED
 SAFE HARBOR AND SHALL NOT BE USED. PLEASE SHOW ON THE
 EXPANDED BATHROOM PLANS WHICH DESIGN SPEC THE BATHROOM
 IS COMPLYING WITH.
  
 HUD RECOGNIZES TEN SAFE HARBORS FOR COMPLIANCE WITH THE
 FAIR HOUSING ACT'S DESIGN AND CONSTRUCTION
 REQUIREMENTS. THEY ARE:
  
 HUD FAIR HOUSING ACCESSIBILITY GUIDELINES PUBLISHED ON
 MARCH 6, 1991 AND THE SUPPLEMENTAL NOTICE TO FAIR
 HOUSING ACCESSIBILITY GUIDELINES: QUESTIONS AND ANSWERS
 ABOUT THE GUIDELINES, PUBLISHED ON JUNE 28, 1994.
  
 HUD FAIR HOUSING ACT DESIGN MANUAL
  
 ANSI A117.1 (1986), USED WITH THE FAIR HOUSING ACT,
 HUD'S REGULATIONS, AND THE GUIDELINES.
  
 CABO/ANSI A117.1 (1992), USED WITH THE FAIR HOUSING
 ACT, HUD'S REGULATIONS, AND THE GUIDELINES.
  
 ICC/ANSI A117.1 (1998), USED WITH THE FAIR HOUSING ACT,
 HUD'S REGULATIONS, AND THE GUIDELINES.
  
 CODE REQUIREMENTS FOR HOUSING ACCESSIBILITY 2000
 (CRHA).
  
 INTERNATIONAL BUILDING CODE 2000 AS AMENDED BY THE 2001
 SUPPLEMENT TO THE INTERNATIONAL CODES.
  
 INTERNATIONAL BUILDING CODE 2003, WITH ONE CONDITION*.
  
 ICC/ANSI A117.1 (2003), USED WITH THE FAIR HOUSING ACT,
 HUD'S REGULATIONS, AND THE GUIDELINES.
  
 2006 INTERNATIONAL BUILDING CODE? (LOOSE LEAF)
  
 * EFFECTIVE FEBRUARY 28, 2005 HUD DETERMINED THAT THE
 IBC 2003 IS A SAFE HARBOR, CONDITIONED UPON ICC
 PUBLISHING AND DISTRIBUTING A STATEMENT TO
 JURISDICTIONS AND PAST AND FUTURE PURCHASERS OF THE
 2003 IBC STATING, "ICC INTERPRETS SECTION 1104.1, AND
 SPECIFICALLY, THE EXCEPTION TO SECTION 1104.1, TO BE
 READ TOGETHER WITH SECTION 1107.4, AND THAT THE CODE
 REQUIRES AN ACCESSIBLE PEDESTRIAN ROUTE FROM SITE
 ARRIVAL POINTS TO ACCESSIBLE BUILDING ENTRANCES, UNLESS
 SITE IMPRACTICALITY APPLIES. EXCEPTION 1 TO SECTION
 1107.4 IS NOT APPLICABLE TO SITE ARRIVAL POINTS FOR ANY
 TYPE B DWELLING UNITS BECAUSE SITE IMPRACTICALITY IS
 ADDRESSED UNDER SECTION 1107.7."
  
 INFORMATION ABOUT THESE SAFE HARBORS AS WELL AS HUD?S
 POLICY WITH RESPECT TO THEIR USE MAY BE FOUND IN REPORT
 OF HUD REVIEW OF THE FAIR HOUSING ACCESSIBILITY
 REQUIREMENTS IN THE 2006 INTERNATIONAL BUILDING CODE
  
  
 13) SHOW CLEAR FLOOR SPACE FOR THE LAUNDRY ROOM AND THE
 HEIGHT AND DEPTH OF THE APPLIANCES AND SINK SHALL
 COMPLY WITH FHA AND ANSI 4.32.6, 4.25, 4.19
 RESPONSE: THE DRAWINGS ARE MODIFIED TO INDICATE THE
 CLEAR FLOOR REQUIREMENTS. PLEASE REFER TO SHEET A2.3
 FOR AN ENLARGED PLAN.
  
 PLEASE SHOW ON PLAN A 30X48 CLEAR FLOOR SPACE IS
 REQUIRED. PLACE NOTE ON PLAN THE WASHER AND DRYER SHALL
 COMPLY WITH ANSI 1986 4.32.6, 4.25, 4.19
  
  
 19) SHEET P5.2 PROVIDE PIPING DETAIL FOR BOOSTER PUMP
 WITH LOCATION OF BLADDER TANK CALLED FOR IN NOTE G. PER
 WPB AMEND TO FBC 107.2.1
 RESPONSE: PLEASE REFER TO SHEET P2.4 FOR ADDED BLADDER
 TANK. BLADDER TANK IS TO BE LOCATED IN MECHANICAL ROOM
 M-09 ON THE FOURTH FLOOR.
  
 I COULD NOT LOCATE PIPING DETAILS FOR BOOSTER PUMP.
 SHOW BLADDER TANK AND BOOSTER PUMP ON WATER RISER AND
 FLOOR PLAN. PER WPB AMEND TO FBC 107.2.1
  
  
 22) SHEET PROVIDE SIZING CALCULATION FOR THE LINT TRAP.
 PER WPB AMEND TO FBC 107.2.1
 RESPONSE: PLEASE REFER TO SHEET P6.1 FOR LINT
 INTERCEPTOR CALCULATION.
 COULD NOT FIND CALCULATIONS
  
 NEW COMMENT :
  
 1. A RECIRCULATION LINE FOR HOT WATER SYSTEM WILL BE
 REQUIRED ON THE 3RD + 4TH FLOOR PER FBC PL 607.2 HOT OR
 TEMPERED WATER SUPPLY TO FIXTURES. THE DEVELOPED LENGTH
 OF HOT OR TEMPERED WATER PIPING, FROM THE SOURCE OF HOT
 WATER TO THE FIXTURES THAT REQUIRE HOT OR TEMPERED
 WATER, SHALL NOT EXCEED 50 FEET (15 240 MM).
 RECIRCULATING SYSTEM PIPING AND HEAT-TRACED PIPING
 SHALL BE CONSIDERED TO BE SOURCES OF HOT OR TEMPERED
 WATER.
  
 2. PROVIDE SIZING CALCULATIONS OR SIZING CHART FOR
 EXPANSION TANK. PER WPB AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]