| 2019-07-03 12:39:34 | |
| | 2ND REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | |
| | PREVIOUS COMMENTS NOT COMPLIED : COPIED FROM RESPONSE |
| | LETTER |
| | |
| | 3) PROVIDE A MATRIX FOR THE FHA REQUIREMENTS INDICATE |
| | THE DESIGN SPEC FOR THE BATHROOMS A OR B PER WPB AMEND |
| | TO FBC 107.2.1 |
| | RESPONSE: THE FAIR HOUSING ACT CHECKLIST AS PRODUCED BY |
| | THE EQUAL RIGHTS CENTER IS REFERENCED ATTACHMENT |
| | A-3-FHA CHECKLIST. |
| | THE DESIGN SPEC FOR THE BATHROOMS IS A. |
| | THE COMPARTMENTALIZED BATHROOMS ARE RE-DESIGNED TO |
| | COMPLY WITH THIS STANDARD. PLEASE REFER TO REVISED AND |
| | CLOUDED DRAWINGS. |
| | |
| | THE FHA CHECKLIST REFERENCED ABOVE IS NOT AN APPROVED |
| | SAFE HARBOR AND SHALL NOT BE USED. PLEASE SHOW ON THE |
| | EXPANDED BATHROOM PLANS WHICH DESIGN SPEC THE BATHROOM |
| | IS COMPLYING WITH. |
| | |
| | HUD RECOGNIZES TEN SAFE HARBORS FOR COMPLIANCE WITH THE |
| | FAIR HOUSING ACT'S DESIGN AND CONSTRUCTION |
| | REQUIREMENTS. THEY ARE: |
| | |
| | HUD FAIR HOUSING ACCESSIBILITY GUIDELINES PUBLISHED ON |
| | MARCH 6, 1991 AND THE SUPPLEMENTAL NOTICE TO FAIR |
| | HOUSING ACCESSIBILITY GUIDELINES: QUESTIONS AND ANSWERS |
| | ABOUT THE GUIDELINES, PUBLISHED ON JUNE 28, 1994. |
| | |
| | HUD FAIR HOUSING ACT DESIGN MANUAL |
| | |
| | ANSI A117.1 (1986), USED WITH THE FAIR HOUSING ACT, |
| | HUD'S REGULATIONS, AND THE GUIDELINES. |
| | |
| | CABO/ANSI A117.1 (1992), USED WITH THE FAIR HOUSING |
| | ACT, HUD'S REGULATIONS, AND THE GUIDELINES. |
| | |
| | ICC/ANSI A117.1 (1998), USED WITH THE FAIR HOUSING ACT, |
| | HUD'S REGULATIONS, AND THE GUIDELINES. |
| | |
| | CODE REQUIREMENTS FOR HOUSING ACCESSIBILITY 2000 |
| | (CRHA). |
| | |
| | INTERNATIONAL BUILDING CODE 2000 AS AMENDED BY THE 2001 |
| | SUPPLEMENT TO THE INTERNATIONAL CODES. |
| | |
| | INTERNATIONAL BUILDING CODE 2003, WITH ONE CONDITION*. |
| | |
| | ICC/ANSI A117.1 (2003), USED WITH THE FAIR HOUSING ACT, |
| | HUD'S REGULATIONS, AND THE GUIDELINES. |
| | |
| | 2006 INTERNATIONAL BUILDING CODE? (LOOSE LEAF) |
| | |
| | * EFFECTIVE FEBRUARY 28, 2005 HUD DETERMINED THAT THE |
| | IBC 2003 IS A SAFE HARBOR, CONDITIONED UPON ICC |
| | PUBLISHING AND DISTRIBUTING A STATEMENT TO |
| | JURISDICTIONS AND PAST AND FUTURE PURCHASERS OF THE |
| | 2003 IBC STATING, "ICC INTERPRETS SECTION 1104.1, AND |
| | SPECIFICALLY, THE EXCEPTION TO SECTION 1104.1, TO BE |
| | READ TOGETHER WITH SECTION 1107.4, AND THAT THE CODE |
| | REQUIRES AN ACCESSIBLE PEDESTRIAN ROUTE FROM SITE |
| | ARRIVAL POINTS TO ACCESSIBLE BUILDING ENTRANCES, UNLESS |
| | SITE IMPRACTICALITY APPLIES. EXCEPTION 1 TO SECTION |
| | 1107.4 IS NOT APPLICABLE TO SITE ARRIVAL POINTS FOR ANY |
| | TYPE B DWELLING UNITS BECAUSE SITE IMPRACTICALITY IS |
| | ADDRESSED UNDER SECTION 1107.7." |
| | |
| | INFORMATION ABOUT THESE SAFE HARBORS AS WELL AS HUD?S |
| | POLICY WITH RESPECT TO THEIR USE MAY BE FOUND IN REPORT |
| | OF HUD REVIEW OF THE FAIR HOUSING ACCESSIBILITY |
| | REQUIREMENTS IN THE 2006 INTERNATIONAL BUILDING CODE |
| | |
| | |
| | 13) SHOW CLEAR FLOOR SPACE FOR THE LAUNDRY ROOM AND THE |
| | HEIGHT AND DEPTH OF THE APPLIANCES AND SINK SHALL |
| | COMPLY WITH FHA AND ANSI 4.32.6, 4.25, 4.19 |
| | RESPONSE: THE DRAWINGS ARE MODIFIED TO INDICATE THE |
| | CLEAR FLOOR REQUIREMENTS. PLEASE REFER TO SHEET A2.3 |
| | FOR AN ENLARGED PLAN. |
| | |
| | PLEASE SHOW ON PLAN A 30X48 CLEAR FLOOR SPACE IS |
| | REQUIRED. PLACE NOTE ON PLAN THE WASHER AND DRYER SHALL |
| | COMPLY WITH ANSI 1986 4.32.6, 4.25, 4.19 |
| | |
| | |
| | 19) SHEET P5.2 PROVIDE PIPING DETAIL FOR BOOSTER PUMP |
| | WITH LOCATION OF BLADDER TANK CALLED FOR IN NOTE G. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | RESPONSE: PLEASE REFER TO SHEET P2.4 FOR ADDED BLADDER |
| | TANK. BLADDER TANK IS TO BE LOCATED IN MECHANICAL ROOM |
| | M-09 ON THE FOURTH FLOOR. |
| | |
| | I COULD NOT LOCATE PIPING DETAILS FOR BOOSTER PUMP. |
| | SHOW BLADDER TANK AND BOOSTER PUMP ON WATER RISER AND |
| | FLOOR PLAN. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | |
| | 22) SHEET PROVIDE SIZING CALCULATION FOR THE LINT TRAP. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | RESPONSE: PLEASE REFER TO SHEET P6.1 FOR LINT |
| | INTERCEPTOR CALCULATION. |
| | COULD NOT FIND CALCULATIONS |
| | |
| | NEW COMMENT : |
| | |
| | 1. A RECIRCULATION LINE FOR HOT WATER SYSTEM WILL BE |
| | REQUIRED ON THE 3RD + 4TH FLOOR PER FBC PL 607.2 HOT OR |
| | TEMPERED WATER SUPPLY TO FIXTURES. THE DEVELOPED LENGTH |
| | OF HOT OR TEMPERED WATER PIPING, FROM THE SOURCE OF HOT |
| | WATER TO THE FIXTURES THAT REQUIRE HOT OR TEMPERED |
| | WATER, SHALL NOT EXCEED 50 FEET (15 240 MM). |
| | RECIRCULATING SYSTEM PIPING AND HEAT-TRACED PIPING |
| | SHALL BE CONSIDERED TO BE SOURCES OF HOT OR TEMPERED |
| | WATER. |
| | |
| | 2. PROVIDE SIZING CALCULATIONS OR SIZING CHART FOR |
| | EXPANSION TANK. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |