Plan Review Notes
Plan Review Notes For Permit 19030147
Permit Number 19030147
Review Stop M
Sequence Number 2
Notes
Date Text
2019-07-12 12:38:082ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19030147
 7/12/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE O/A DUCTS THAT ARE PENETRATING THE FIRE-RATED
 FLOOR/CEILING ASSEMBLIES AT EACH LEVEL SHALL BE
 ENCLOSED IN FIRE-RATED SHAFTS PER SECTION 607.6, OR
 SHALL BE PROTECTED WITH LISTED CEILING RADIATION
 DAMPERS AT ECH FLOOR/CEILING PENETRATION.
  
 2) THE PLANS INDICATE DOOR UNDERCUTS FOR REQUIRED
 MAKEUP AIR FOR TRASH AND LAUNDRY ROOM EXHAUST SYSTEMS.
 PLEASE NOTE THAT THESE ROOMS ARE FIRE-RATED AND THE
 DOORS INTO THEM ARE FIRE-RATED. DOOR UNDERCUTS ON
 FIRE-RATED DOORS ARE NOT PERMITTED ON LABELED DOORS-
 SECTION 716.5.1 FBC B AND SECTION 1.3.4 NFPA 252.
 MAKEUP AIR IN THESE ROOMS MUST BE PROVIDED BY DUCTS OR
 TRANSFER GRILLS- SECTION 504.6. THWE LAUNDRY ROOM PLANS
 SHALL SHOW THE LOCATIONS AND NUMBER OF DRYERS TO BE
 INSTALLED- SECTION 107.2.1 WPB.
  
 3) COMMENT #3 FROM THE 1ST REVIEW STILL EXISTS. SHEET
 M3.1: PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF
 THE EXTERIOR CHILLERS, BOILERS, STORAGE TANKS,
 GENERATOR, AND THE ROOFTOP O/A INTAKES, EXHAUST
 OUTLETS, AND ELEVATOR RELIEF HOOD- SECTION 301.15 FBC
 M. PLEASE NOTE THAT THE PLANS SHOW A FIRE PUMP
 ENCLOSURE. IS THIS A MANUFACTURED PRODUCT, OR AN
 ENCLOSURE TO BE CONSTRUCTED ON-SITE? IF THIS IS A
 MANUFACTURED PRODUCT IT MUST EITHER HAVE FL.
 MANUFACTURED BUILDING APPROVAL OR FLORIDA PRODUCT
 APPROVAL- RULE 9N-3 FAC. TO BE CONSTRUCTED ON-SITE,
 PLEASE PROVIDE COMPLETE STRUCTURAL DRAWINGS AND
 DETAILS. PLEASE SEE SECTION 4.13 NFPA 20 FOR OTHER
 COMPLIANCE REQUIREMENTS.
  
 4) COMMENT #5 BELOW LISTED FOR REFERENCE
  
 5) REQUIRED SUBMITTALS LISTED BELOW SHALL HAVE SHOP
 DRAWING STAMPS BY THE EOR AND BE IN THE FIELD AT TIME
 OF INSPECTION.
 A) FIRE DAMPERS AND FIRE/SMOKE DAMPERS.
 B) MOTORIZED O/A DAMPERS
 C) DUCT SMOKE DETECTORS
 D) LOUVERS FOR EXHAUST AND OUTSIDE AIR INTAKES
 INCLUDING MANUFACTURER'S SPECIFICATIONS AND FL. PRODUCT
 APPROVALS AND/OR MIAMI-DADE NOA'S
 E) AC STAND NOA'S OR FL. PRODUCT APPROVALS
 F) CHILLERS
 G) CLOTHES DRYERS
 H) COOKING APPLIANCES
 I) TEST AND BALANCE REPORTS
  
 SUBMITTALS TO BE PROVIDED TO THE BUILDING DEPARTMENT
 FOR REVIEW.
 A) SIGNED AND SEALED STRUCTURAL ENGINEERING FOR
 INSTALLATION OF ALL EXTERIOR MECHANICAL EQUIPMENT AND
 APPLIANCES. ALTERNATELY, SIGNED AND SEALED, OR
 DELEGATED ENGINEERING MAY BE AVAILABLE ONSITE AT THE
 TIME OF INSPECTION. PLEASE NOTE THAT DELEGATED
 ENGINEERING SHALL BEAR THE SHOP DRAWING STAMP OF THE
 STRUCTURAL ENGINEER RECORD.
 B) GENERATOR
 C) BOILERS AND WATER HEATERS INCLUDING VENT FLUES
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE
  