Plan Review Notes
Plan Review Notes For Permit 19030147
Permit Number 19030147
Review Stop B
Sequence Number 2
Notes
Date Text
2019-06-24 07:36:11BUILDING REVIEW COMMENTS
 W.P.B. PERMIT: 19030147
 2 ND REVIEW: JUNE 17, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 42) 1011.12 FBC[B]
 - ROOF HATCH OK SINCE NO MECHANICAL ACCESS.
 1011.12.2 FBC[B] PLEASE DIMENSION THE ROOF HATCH TO
 SHOW IT IS 16 SQ. FT MINIMUM.
  
 48) 1030.1 FBC[B] GENERAL. IN ADDITION TO THE MEANS OF
 EGRESS REQUIRED BY THIS CHAPTER, PROVISIONS SHALL BE
 MADE FOR EMERGENCY ESCAPE AND RESCUE OPENINGS IN GROUP
 R-2 OCCUPANCIES IN ACCORDANCE WITH TABLES 1006.3.2(1)
 AND 1006.3.2(2).
 - WINDOWS DON?T NEED TO OPERATE FOR EGRESS, BUT PLEASE
 REVIEW FOR VENTILATION
 1203.5 NATURAL VENTILATION.
 IS ALL THE VENTILATION MECHANICAL?
  
 52) 713.13.4 FBC[B] CHUTE DISCHARGE ROOM. WASTE OR
 LINEN CHUTES SHALL DISCHARGE INTO AN ENCLOSED ROOM
 SEPARATED BY FIRE BARRIERS WITH A FIRE-RESISTANCE
 RATING NOT LESS THAN THE REQUIRED FIRE RATING OF THE
 SHAFT ENCLOSURE AND CONSTRUCTED IN ACCORDANCE WITH
 SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED IN
 ACCORDANCE WITH SECTION 711, OR BOTH. OPENINGS INTO THE
 DISCHARGE ROOM FROM THE REMAINDER OF THE BUILDING SHALL
 BE PROTECTED BY OPENING PROTECTIVES HAVING A FIRE
 PROTECTION RATING EQUAL TO THE PROTECTION REQUIRED FOR
 THE SHAFT ENCLOSURE. DOORS SHALL BE SELF- OR
 AUTOMATICCLOSING UPON THE DETECTION OF SMOKE IN
 ACCORDANCE WITH SECTION 716.5.9.3. WASTE CHUTES SHALL
 NOT TERMINATE IN AN INCINERATOR ROOM. WASTE AND LINEN
 ROOMS THAT ARE NOT PROVIDED WITH CHUTES NEED ONLY
 COMPLY WITH TABLE 509.
 - PLEASE CHECK DOOR 20 TO MEET THE REQUIRED PROTECTION
 RATING EQUAL TO THE SHAFT ENCLOSURE.
 -NEW COMMENT-TYPICALLY YOU WOULD USE TABLE 716.5 TO
 SPECIFY FIRE RATING OF DOOR, BUT FOR THE CHUTE
 DISCHARGE ROOM 713.13.4 REQUIRES THE DOOR TO EQUAL THE
 FIRE PROTECTION RATING OF THE SHAFT (2 HOURS).
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  