| 2019-06-24 07:36:11 | BUILDING REVIEW COMMENTS |
| | W.P.B. PERMIT: 19030147 |
| | 2 ND REVIEW: JUNE 17, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[B] = FBC BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | |
| | 42) 1011.12 FBC[B] |
| | - ROOF HATCH OK SINCE NO MECHANICAL ACCESS. |
| | 1011.12.2 FBC[B] PLEASE DIMENSION THE ROOF HATCH TO |
| | SHOW IT IS 16 SQ. FT MINIMUM. |
| | |
| | 48) 1030.1 FBC[B] GENERAL. IN ADDITION TO THE MEANS OF |
| | EGRESS REQUIRED BY THIS CHAPTER, PROVISIONS SHALL BE |
| | MADE FOR EMERGENCY ESCAPE AND RESCUE OPENINGS IN GROUP |
| | R-2 OCCUPANCIES IN ACCORDANCE WITH TABLES 1006.3.2(1) |
| | AND 1006.3.2(2). |
| | - WINDOWS DON?T NEED TO OPERATE FOR EGRESS, BUT PLEASE |
| | REVIEW FOR VENTILATION |
| | 1203.5 NATURAL VENTILATION. |
| | IS ALL THE VENTILATION MECHANICAL? |
| | |
| | 52) 713.13.4 FBC[B] CHUTE DISCHARGE ROOM. WASTE OR |
| | LINEN CHUTES SHALL DISCHARGE INTO AN ENCLOSED ROOM |
| | SEPARATED BY FIRE BARRIERS WITH A FIRE-RESISTANCE |
| | RATING NOT LESS THAN THE REQUIRED FIRE RATING OF THE |
| | SHAFT ENCLOSURE AND CONSTRUCTED IN ACCORDANCE WITH |
| | SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED IN |
| | ACCORDANCE WITH SECTION 711, OR BOTH. OPENINGS INTO THE |
| | DISCHARGE ROOM FROM THE REMAINDER OF THE BUILDING SHALL |
| | BE PROTECTED BY OPENING PROTECTIVES HAVING A FIRE |
| | PROTECTION RATING EQUAL TO THE PROTECTION REQUIRED FOR |
| | THE SHAFT ENCLOSURE. DOORS SHALL BE SELF- OR |
| | AUTOMATICCLOSING UPON THE DETECTION OF SMOKE IN |
| | ACCORDANCE WITH SECTION 716.5.9.3. WASTE CHUTES SHALL |
| | NOT TERMINATE IN AN INCINERATOR ROOM. WASTE AND LINEN |
| | ROOMS THAT ARE NOT PROVIDED WITH CHUTES NEED ONLY |
| | COMPLY WITH TABLE 509. |
| | - PLEASE CHECK DOOR 20 TO MEET THE REQUIRED PROTECTION |
| | RATING EQUAL TO THE SHAFT ENCLOSURE. |
| | -NEW COMMENT-TYPICALLY YOU WOULD USE TABLE 716.5 TO |
| | SPECIFY FIRE RATING OF DOOR, BUT FOR THE CHUTE |
| | DISCHARGE ROOM 713.13.4 REQUIRES THE DOOR TO EQUAL THE |
| | FIRE PROTECTION RATING OF THE SHAFT (2 HOURS). |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |