Plan Review Notes
Plan Review Notes For Permit 19030147
Permit Number 19030147
Review Stop P
Sequence Number 1
Notes
Date Text
2019-04-17 10:07:401ST REVIEW: 19030147
  
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE INDICATE ON THE PLAN WHICH DESIGN DOCUMENT
 WAS USED TO COMPLY WITH FHA
  
 2. SHT. A0.1 UNDER CODE DATA FBC IN EFFECT IS THE 2017
 6TH EDITION ALSO LIST FBC ACCESSIBILITY AND THE PLAN
 WHICH DESIGN DOCUMENT WAS USED TO COMPLY WITH FHA. PER
 WPB AMEND TO FBC 107.2.1
  
 3. PROVIDE A MATRIX FOR THE FHA REQUIREMENTS INDICATE
 THE DESIGN SPEC FOR THE BATHROOMS A OR B PER WPB AMEND
 TO FBC 107.2.1
  
 4. SHT. A2.3 DETAIL #8
 A) PROVIDE DIMENSIONS FOR THE TOILET ROOMS.
 B) SHOW CLEAR FLOOR SPACE FOR SHOWER.
 C) SHOW DIMENSIONS ON CLEAR FLOOR SPACE OR LABEL THEM
 TO MATCH THE NOTES.
 PER WPB AMEND TO FBC 107.2.1
  
 5. JUST FOR CLARIFICATION IS THERE ANY FEDERAL FUNDING
 ON THIS PROJECT IF THERE IS IT WILL BE REQUIRED TO
 COMPLY WITH UFAS. PER FHA
  
 6. SHT. A2.3 DETAIL #4
 A) SHOW CLEAR FLOOR SPACE FOR THE TOILET, LAVATORY AND
 SHOWER.
 B) PROVIDE DIMENSIONS FOR THE TOILET ROOM.
  
 7. SHT. A2.3 SHOW LOCATION OF THE GRAB BAR BACKING ON
 THE ENLARGED FLOOR PLANS FOR THE FHA UNITS.PER WPB
 AMEND TO FBC 107.2.1
  
 8. THE GRAB BARS IN THE FBC ACC COMPLIANT DWELLING
 UNITS D-1 + C-1 SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE NOT THE CENTER OF THE BAR. PER FBC ACC
 609.4
  
 9. THE HEIGHT OF THE TOILET SEATS IN THE ACCESSIBILITY
 DWELLING UNITS D-1 + C-1 AND COMMON AREA BATHROOMS
 SHALL BE 17"- 19". PER FBC ACC 604.4 AND ANSI
 117.1-1986 4.16.3
  
 10. THE TOILET PAPER DISPENSER IN D-1 AND C-1 SHALL BE
 7"-9" MEASURED FROM THE FRONT OF THE TOILET TO THE
 CENTERLINE OF THE DISPENSER. PER FBC ACC 604.7
  
 11. PROVIDE MOUNTING DETAILS FOR BACKING IN SHOWERS IN
 BATHROOMS C-2, D-2, C-3, D-3, C-4, D-4. PER FHA
  
 12. PROVIDE ENLARGED DETAIL FOR THE KITCHENS SHOWING
 THE REQUIRED CLEAR FLOOR SPACE AT THE APPLIANCES AND
 SINK ALSO INCLUDE THE DIMENSIONS BETWEEN THE CABINETS
 AND ANY ADJACENT ELEMENTS. PER FHA
  
 13. SHOW CLEAR FLOOR SPACE FOR THE LAUNDRY ROOM AND THE
 HEIGHT AND DEPTH OF THE APPLIANCES AND SINK SHALL
 COMPLY WITH FHA AND ANSI 4.32.6, 4.25, 4.19
  
 14. SHOW COMPLIANCE FOR THE SHOWERS IN C-1, D-1 FBC ACC
 608.3.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS.
 WHERE A SEAT IS PROVIDED IN STANDARD ROLL-IN TYPE
 SHOWER COMPARTMENTS, GRAB BARS SHALL BE PROVIDED ON THE
 BACK WALL AND THE SIDE WALL OPPOSITE THE SEAT. GRAB
 BARS SHALL NOT BE PROVIDED ABOVE THE SEAT. WHERE A SEAT
 IS NOT PROVIDED IN STANDARD ROLL-IN TYPE SHOWER
 COMPARTMENTS, GRAB BARS SHALL BE PROVIDED ON THREE
 WALLS. GRAB BARS SHALL BE INSTALLED 6 INCHES MAXIMUM
 FROM ADJACENT WALLS.
 608.5.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS. IN
 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS, THE
 CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT SHALL BE
 LOCATED ABOVE THE GRAB BAR, BUT NO HIGHER THAN 48
 INCHES ABOVE THE SHOWER FLOOR. WHERE A SEAT IS
 PROVIDED, THE CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT
 SHALL BE INSTALLED ON THE BACK WALL ADJACENT TO THE
 SEAT WALL AND SHALL BE LOCATED 27 INCHES MAXIMUM FROM
 THE SEAT WALL.
 608.4 SEATS. A FOLDING OR NON-FOLDING SEAT SHALL BE
 PROVIDED IN TRANSFER TYPE SHOWER COMPARTMENTS. A
 FOLDING SEAT SHALL BE PROVIDED IN ROLL-IN TYPE SHOWERS
 REQUIRED IN TRANSIENT LODGING GUEST ROOMS WITH MOBILITY
 FEATURES COMPLYING WITH 806.2. SEATS SHALL COMPLY WITH
 610.
  
 15. SHOW COMPLIANCE FOR ACCESSIBLE WATER FOUNTAIN. PER
 ANSI A117.1-1986 4.15
  
 16. PROVIDE STORM DRAIN SIZING CALCULATIONS. PER WPB
 AMEND TO FBC 107.2.1
  
 17. PROVIDE OVERALL WATER ISOMETRIC DRAWING.
 107.3.5.1.3(13)
  
 18. PROVIDE AN UNDERGROUND COLLECTION SANITARY
 ISOMETRIC DRAWING WITH TAGGED STACKS. 107.3.5.1.3(13)
  
 19. SHT P5.2 PROVIDE PIPING DETAIL FOR BOOSTER PUMP
 WITH LOCATION OF BLADDER TANK CALLED FOR IN NOTE G).
 PER WPB AMEND TO FBC 107.2.1
  
 20. SHT P6.1 PROVIDE AN EXPANDED ISOMETRIC SHOWING
 DIRECTION OF FLOW AND TYPE OF WATER. PER WPB AMEND TO
 FBC 107.2.1
  
 21. SHT P6.1 I COULD NOT FIND ET-1 ON SCHEDULE PLEASE
 CLARIFY.
  
 22. SHT PROVIDE SIZING CALCULATION FOR THE LINT TRAP.
 PER WPB AMEND TO FBC 107.2.1
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]