| 2019-04-22 10:52:01 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19030147 |
| | 4/18/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) COMMENTS A-I LISTED BELOW ARE APPLICABLE TO ALL OR |
| | SOME OF 1-4 FLOOR LEVEL PLAN SHEETS M2.1A, M2.1B, |
| | M2.1C, M2.2A, M2.2B, M2.2C, M2.3A, M.2.3B, M2.3C, |
| | M2.4A, M.2.4B, & M2.4C: |
| | |
| | A) RETURN AIR FROM BEDROOMS SHALL BE DUCTED OR |
| | TRANSFERRED IN COMBINATION WITH 1" DOOR UNDERCUTS- |
| | SECTION 601.6 FBC M. |
| | B) SHOW THE LOCATIONS AND INDICATE THE TYPES OF |
| | AUTOMATIC DAMPERS (MOTORIZED OR GRAVITY) TO BE USED TO |
| | CONTROL O/A SUPPLY TO THE AHU'S- SECTION C403.2.4.3 FBC |
| | EC. |
| | C) NO VENTILATION HAS BEEN PROVIDED FOR TRASH ROOM 112 |
| | ON 1ST FLOOR LEVEL. THIS SAME ROOM ON LEVELS 2-4 IS NOT |
| | IDENTIFIED ON THE PLANS, AND ALSO NO VENTILATION HAS |
| | BEEN PROVIDED TO THOSE ROOMS. |
| | D) MAKEUP AIR FOR TRASH ROOM AND JANITOR ROOM EXHAUST |
| | SYSTEMS NOT PROVIDED- SECTION 501.4 FBC M. PLEASE |
| | PROVIDE A SEQUENCE OF OPERATION FOR THE FANS- SECTION |
| | 501.4 FBC M. |
| | E) THE 12X12 RETURN BY THE COOKING APPLIANCE IN SUITE |
| | 101 KITCHEN IS PROHIBITED PER SECTION 601.5 (7) FBC M. |
| | THIS 12X12 RETURN IS ALSO SHOWN ON FLOOR LEVELS 2-4 |
| | HOWEVER THE ROOMS ARE NOT IDENTIFIED. |
| | F) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DRYERS |
| | IN THE LAUNDRIES- SECTION 504.1 FBC M |
| | G) INDICATE HOW MAKEUP AIR IS BEING PROVIDED FOR THE |
| | DRYERS- 504.6 FBC M. |
| | H) THE FIRE DAMPER SHOWN IN THE DRYER EXHAUST DUCT ON |
| | SHEET M2.1B IS PROHIBITED- SECTION 504.2 FBC M. |
| | I) FIRE DAMPERS MISSING FOR THE 16X12 SUPPLY DUCTS AND |
| | 14X8 RETURN DUCTS PENETRATING THE CORRIDOR/MECHANICAL |
| | ROOM WALLS- SECTION 607.5.3 FBC M. |
| | |
| | 2) SHEET M3.1: PROVIDE WIND LOAD ENGINEERING FOR |
| | INSTALLATION OF THE EXTERIOR CHILLERS, BOILERS, STORAGE |
| | TANKS, GENERATOR, AND THE ROOFTOP O/A INTAKES, EXHAUST |
| | OUTLETS, AND ELEVATOR RELIEF HOOD- SECTION 301.15 FBC |
| | M. |
| | |
| | 3) M3.1, GENERATOR: |
| | A) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | GENERATOR, GAS PIPING, ENGINE EXHAUST PIPE, MUFFLER, |
| | AND ALL OTHER ASSOCIATED SYSTEM COMPONENTS- SECTION |
| | 616.1 FBC FG |
| | B) SUBMIT THE UL 2200 CERTIFICATE OF COMPLIANCE FOR THE |
| | GENERATOR- SECTION 616.1 FBC FG. THE MANUFACTURER'S |
| | SPECIFICATIONS AND/OR UL CERTIFICATE SHALL INDICATE THE |
| | GENERATOR IS IN COMPLIANCE WITH NFPA 37. |
| | C) PROVIDE A GAS PIPING PLAN AND ISOMETRIC DRAWING- |
| | SECTION 616.2 |
| | D) PROVIDE AN EXHAUST PIPE DIAGRAM SHOWING THE TOTAL |
| | SYSTEM RUN AND LENGTH MEASUREMENT, AND TERMINATION |
| | LOCATION, AND CLEARANCE DISTANCES GRAVITY OR MECHANICAL |
| | AIR INTAKES INTO THE BUILDING. PLEASE INCLUDE ALL |
| | COMPONENTS OF THE SYSTEM INCLUDING THE SILENCER.- SEE |
| | SECTION 8.1- 8.4 NFPA 37, AND SECTION 501.3.1 FBC M. |
| | E) PROVIDE DETAILS AND SPECIFICATIONS FOR NORMAL AND |
| | EMERGENCY RELIEF VENTING OF THE TANK, INCLUDING VENT |
| | PIPING RUNS AND TERMINATION LOCATIONS- SECTION 24.13 |
| | NFPA 30. |
| | |
| | 4) ASHRAE O/A CALCULATIONS: THE CALCULATIONS SHOW AN |
| | O/A CFM TOTAL USING THE VENTILATION RATE PROCEDURE, AND |
| | A TOTAL USING A 30% INCREASE. WHICH OF THESE TWO TOTAL |
| | SUMS IS THE TOTAL BEING PROVIDED. |
| | |
| | 5) REQUIRED SUBMITTALS LISTED BELOW SHALL HAVE SHOP |
| | DRAWING STAMPS BY THE EOR AND BE IN THE FIELD AT TIME |
| | OF INSPECTION. |
| | A) FIRE DAMPERS AND FIRE/SMOKE DAMPERS. |
| | B) MOTORIZED O/A DAMPERS |
| | C) DUCT SMOKE DETECTORS |
| | D) LOUVERS FOR EXHAUST AND OUTSIDE AIR INTAKES |
| | INCLUDING MANUFACTURER'S SPECIFICATIONS AND FL. PRODUCT |
| | APPROVALS AND/OR MIAMI-DADE NOA'S |
| | E) AC STAND NOA'S OR FL. PRODUCT APPROVALS |
| | F) CHILLERS |
| | G) CLOTHES DRYERS |
| | H) COOKING APPLIANCES |
| | I) TEST AND BALANCE REPORTS |
| | |
| | SUBMITTALS TO BE PROVIDED TO THE BUILDING DEPARTMENT |
| | FOR REVIEW. |
| | A) SIGNED AND SEALED STRUCTURAL ENGINEERING FOR |
| | INSTALLATION OF ALL EXTERIOR MECHANICAL EQUIPMENT AND |
| | APPLIANCES. ALTERNATELY, SIGNED AND SEALED, OR |
| | DELEGATED ENGINEERING MAY BE AVAILABLE ONSITE AT THE |
| | TIME OF INSPECTION. PLEASE NOTE THAT DELEGATED |
| | ENGINEERING SHALL BEAR THE SHOP DRAWING STAMP OF THE |
| | STRUCTURAL ENGINEER RECORD. |
| | B) GENERATOR |
| | C) BOILERS AND WATER HEATERS INCLUDING VENT FLUES |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |