| 2019-03-26 12:41:11 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) SHEET A 0.1 - THERE IS AN INDICATION UNDER THE |
| | BUILDING DATA SECTION OF THE FBC OCCUPANCY AS |
| | APARTMENT: HOWEVER THERE IS NO FLORIDA FIRE PREVENTION |
| | CODE REFERENCE. |
| | |
| | PER NFPA 101, CH 3 DEFINITIONS THIS IS DORMITORY |
| | OCCUPANCY AND SHALL COMPLY WITH THE REQUIREMENTS; |
| | HOWEVER, IT SHALL BE CLASSIFIED AS AN APARTMENT |
| | |
| | 3.3.64* DORMITORY. A BUILDING OR A SPACE IN A BUILDING |
| | IN WHICH |
| | GROUP SLEEPING ACCOMMODATIONS ARE PROVIDED FOR MORE |
| | THAN 16 |
| | PERSONS WHO ARE NOT MEMBERS OF THE SAME FAMILY IN ONE |
| | ROOM, OR A |
| | SERIES OF CLOSELY ASSOCIATED ROOMS, UNDER JOINT |
| | OCCUPANCY AND SINGLE |
| | MANAGEMENT, WITH OR WITHOUT MEALS, BUT WITHOUT |
| | INDIVIDUAL COOKING |
| | FACILITIES. |
| | |
| | 28.1.1.4 ANY DORMITORY DIVIDED INTO SUITES OF ROOMS, |
| | WITH ONE OR |
| | MORE BEDROOMS OPENING INTO A LIVING ROOM OR STUDY THAT |
| | HAS A |
| | DOOR OPENING INTO A COMMON CORRIDOR SERVING A NUMBER OF |
| | SUITES, |
| | SHALL BE CLASSIFIED AS AN APARTMENT BUILDING. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 2) SHEET A 2.1 - THERE ARE ROOM DOORS THAT OPEN INTO |
| | THE CORRIDOR. THESE DOORS MAY BE OPENED AT THE SAME |
| | TIME AND ENCROACH THE REQUIRED WIDTH OF THE MEANS OF |
| | EGRESS. |
| | |
| | THERE ARE NO DIMENSIONS INDICATED ON THE PLAN TO |
| | CONFIMR THE REQUIRED WIDTH 44" IS MAINTAINED. |
| | |
| | PLEASE REVIEW AND PROVIDE OF JUSTIFY.CLARIFY. |
| | |
| | |
| | |
| | |
| | |
| | 3) SHEET A 2.2 - THERE ARE ROOM DOORS THAT OPEN INTO |
| | THE CORRIDOR. THESE DOORS MAY BE OPENED AT THE SAME |
| | TIME AND ENCROACH THE REQUIRED WIDTH OF THE MEANS OF |
| | EGRESS. |
| | |
| | THERE ARE NO DIMENSIONS INDICATED ON THE PLAN TO |
| | CONFIMR THE REQUIRED WIDTH 44" IS MAINTAINED. |
| | |
| | PLEASE REVIEW AND PROVIDE OF JUSTIFY.CLARIFY. |
| | |
| | |
| | |
| | 4) SHEET A 2.3 - THERE ARE WINDOWS INDICATED WITHIN THE |
| | STAIRWELL WALLS. |
| | |
| | PER NFPA 101, CH 28 |
| | |
| | 28.2.2.3 STAIRS. STAIRS COMPLYING WITH 7.2.2 SHALL BE |
| | PERMITTED. |
| | |
| | PER NFPA 101, CH 7 |
| | |
| | 7.2.2.5 ENCLOSURE AND PROTECTION OF STAIRS. |
| | 7.2.2.5.1 ENCLOSURES. |
| | 7.2.2.5.1.1 ALL INSIDE STAIRS SERVING AS AN EXIT OR |
| | EXIT COMPONENT |
| | SHALL BE ENCLOSED IN ACCORDANCE WITH 7.1.3.2. |
| | |
| | *OPENINGS IN EXIT ENCLOSURES SHALL BE LIMITED TO DOOR |
| | ASSEMBLIES FROM NORMALLY OCCUPIED SPACES AND CORRIDORS |
| | AND |
| | DOOR ASSEMBLIES FOR EGRESS FROM THE ENCLOSURE, UNLESS |
| | ONE OF |
| | THE FOLLOWING CONDITIONS EXISTS: |
| | (A) VESTIBULES THAT SEPARATE NORMALLY UNOCCUPIED SPACES |
| | FROM AN EXIT ENCLOSURE SHALL BE PERMITTED, PROVIDED THE |
| | VESTIBULE IS SEPARATED FROM ADJACENT SPACES BY CORRIDOR |
| | WALLS AND RELATED OPENING PROTECTIVES AS REQUIRED FOR |
| | THE |
| | OCCUPANCY INVOLVED BUT NOT LESS THAN A SMOKE PARTITION |
| | IN ACCORDANCE WITH SECTION 8.4. |
| | (B) IN BUILDINGS OF TYPE I OR TYPE II CONSTRUCTION, AS |
| | DEFINED |
| | IN NFPA 220, STANDARD ON TYPES OF BUILDING |
| | CONSTRUCTION, (SEE 8.2.1.2) FIRE PROTECTION?RATED DOOR |
| | ASSEMBLIES TO NORMALLY UNOCCUPIED BUILDING SERVICE |
| | EQUIPMENT SUPPORT AREAS AS ADDRESSED IN SECTION 7.13 |
| | SHALL BE PERMITTED, PROVIDED THE SPACE IS SEPARATED |
| | FROM |
| | THE EXIT ENCLOSURE BY FIRE BARRIERS AS REQUIRED BY |
| | 7.1.3.2.1(3). |
| | (C) OPENINGS IN EXIT PASSAGEWAYS IN MALL BUILDINGS AS |
| | PROVIDED IN CHAPTERS 36 AND 37 SHALL BE PERMITTED. |
| | (D) IN BUILDINGS OF TYPE I OR TYPE II CONSTRUCTION, AS |
| | DEFINED |
| | IN NFPA 220, STANDARD ON TYPES OF BUILDING |
| | CONSTRUCTION, (SEE 8.2.1.2) EXISTING FIRE PROTECTION? |
| | RATED |
| | DOOR ASSEMBLIES TO INTERSTITIAL SPACES SHALL BE |
| | PERMITTED, |
| | PROVIDED THAT SUCH SPACES MEET ALL OF THE FOLLOWING |
| | CRITERIA: |
| | I. THE SPACE IS USED SOLELY FOR DISTRIBUTION OF PIPES, |
| | DUCTS, AND CONDUITS. |
| | II. THE SPACE CONTAINS NO STORAGE. |
| | III. THE SPACE IS SEPARATED FROM THE EXIT ENCLOSURE IN |
| | ACCORDANCE WITH SECTION 8.3. |
| | (E) EXISTING OPENINGS TO MECHANICAL EQUIPMENT SPACES |
| | PROTECTED BY APPROVED EXISTING FIRE PROTECTION?RATED |
| | DOOR ASSEMBLIES SHALL BE PERMITTED, PROVIDED THAT THE |
| | FOLLOWING CRITERIA ARE MET: |
| | I. THE SPACE IS USED SOLELY FOR NON-FUEL-FIRED |
| | MECHANICAL EQUIPMENT. |
| | II. THE SPACE CONTAINS NO STORAGE OF COMBUSTIBLE |
| | MATERIALS. |
| | III. THE BUILDING IS PROTECTED THROUGHOUT BY AN |
| | APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM |
| | IN ACCORDANCE WITH SECTION 9.7. |
| | (10) PENETRATIONS INTO, AND OPENINGS THROUGH, AN EXIT |
| | ENCLOSURE |
| | ASSEMBLY SHALL BE LIMITED TO THE FOLLOWING: |
| | (A) DOOR ASSEMBLIES PERMITTED BY 7.1.3.2.1(9) |
| | (B) *ELECTRICAL CONDUIT SERVING THE EXIT ENCLOSURE |
| | (C) REQUIRED EXIT DOOR OPENINGS |
| | (D) DUCTWORK AND EQUIPMENT NECESSARY FOR INDEPENDENT |
| | STAIR PRESSURIZATION |
| | (E) WATER OR STEAM PIPING NECESSARY FOR THE HEATING OR |
| | COOLING OF THE EXIT ENCLOSURE |
| | (F) SPRINKLER PIPING |
| | (G) STANDPIPES |
| | (H) EXISTING PENETRATIONS PROTECTED IN ACCORDANCE WITH |
| | 8.3.5 |
| | (I) PENETRATIONS FOR FIRE ALARM CIRCUITS, WHERE THE |
| | CIRCUITS |
| | ARE INSTALLED IN METAL CONDUIT AND THE PENETRATIONS ARE |
| | PROTECTED IN ACCORDANCE WITH 8.3.5 |
| | (11) PENETRATIONS OR COMMUNICATING OPENINGS SHALL BE |
| | PROHIBITED BETWEEN ADJACENT EXIT ENCLOSURES. |
| | (12) MEMBRANE PENETRATIONS SHALL BE PERMITTED ON THE |
| | EXIT |
| | ACCESS SIDE OF THE EXIT ENCLOSURE AND SHALL BE |
| | PROTECTED IN |
| | ACCORDANCE WITH 8.3.5.6. |
| | |
| | |
| | A WINDOW SCHEDULE COULD NOT BE IDENTIFIED THAT SHOWED |
| | THESE WINDOWS WITH A 2 HOUR RATING. |
| | |
| | PLEASE REVIEW AND CORRECT WITH DETAILS. |
| | |
| | |
| | |
| | 5) SHEET E 0.1 - THERE ARE INDICATIONS OF FIRE ALARM |
| | EQUIPMENT. |
| | |
| | ANY INSTALLATION OF FIRE ALARM EQUIPMENT SHALL BE DONE |
| | UNDER SEPARATE PERMIT AND SHOP DRAWINGS BY A CERTIFIED |
| | FIRE ALARM CONTRACTOR. |
| | |
| | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF |
| | ACKNOWLEDGEMENT AND COMPLIANCE. |
| | |
| | |
| | |
| | 6) SHEET A 2.1 - THERE ARE ELVATORS INDICATED. |
| | |
| | PLEASE CONFIRM MEETING THE REQUIREMENTS BELOW AND |
| | IDENTIFY WHICH ELEVATOR WILL HOLD THE STAR OF LIFE |
| | SYMBOL. |
| | |
| | 28.5.3 ELEVATORS, ESCALATORS, AND CONVEYORS. |
| | 28.5.3.1 ELEVATORS, ESCALATORS, AND CONVEYORS SHALL |
| | COMPLY WITH |
| | THE PROVISIONS OF SECTION 9.4. |
| | 9.4.3 FIRE FIGHTERS? EMERGENCY OPERATIONS. |
| | 9.4.3.1 ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE |
| | FIGHTERS? |
| | EMERGENCY OPERATIONS REQUIREMENTS OF ASME A17.1/CSA |
| | B44, |
| | SAFETY CODE FOR ELEVATORS AND ESCALATORS. |
| | |
| | PLEASE PROVIDE DETAILS. |
| | |
| | |
| | |
| | 7) SHEET A 4.1 - THERE IS AN INDICATION OF A ROOF |
| | ACCESS OPENING THAT APPEARS TO BE IN AN UNSAFE |
| | POSITION. |
| | |
| | THERE APPEARS TO BE CURBING WITHIN A FOOT OF THE EDGE |
| | OF THE HATCH WHICH REPRESENTS A TRIP HAZARD. |
| | |
| | A GUARD/RAILING SHOULD BE PROVIDED TO ASSIST THE USER. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 8) SHEET A 6.3 - THERE ARE NO INDICATIONS OF STAIR |
| | SIGNAGE, INCLUDING BUT NOT LIMITED TO : |
| | |
| | NFPA 1 CH 10 |
| | |
| | 10.11.3.1.13* SIGNAGE THAT READS NO ROOF ACCESS SHALL |
| | DESIGNATE STAIRWAYS THAT DO NOT PROVIDE ROOF ACCESS. |
| | LETTERING |
| | SHALL BE A MINIMUM OF 1 IN. (25 MM) HIGH AND SHALL BE |
| | IN |
| | ACCORDANCE WITH 14.14.8.2. |
| | |
| | NFPA 101, CH 7 |
| | |
| | 7.2.2.5.4* STAIRWAY IDENTIFICATION. |
| | 7.2.2.5.4.1 NEW ENCLOSED STAIRS SERVING THREE OR MORE |
| | STORIES AND |
| | EXISTING ENCLOSED STAIRS, OTHER THAN THOSE ADDRESSED IN |
| | 7.2.2.5.4.1(P), SERVING FIVE OR MORE STORIES SHALL |
| | COMPLY WITH |
| | 7.2.2.5.4.1(A) THROUGH 7.2.2.5.4.1(O). |
| | |
| | (M)* SIGNAGE THAT READS NO ROOF ACCESS SHALL DESIGNATE |
| | STAIRWAYS THAT DO NOT PROVIDE ROOF ACCESS. LETTERING |
| | SHALL BE A |
| | MINIMUM OF 1 IN. (25 MM) HIGH AND SHALL BE IN |
| | ACCORDANCE WITH |
| | 7.10.8.2. |
| | |
| | HOWEVER, "4TH FL ROOF HATCH" SHOULD BE PROVIDED IN LIEU |
| | OF NO ROOF ACCESS, AS WELL AS A SIGN ON THE DOOR OF THE |
| | ROOM CONTAINING THE HATCH. |
| | |
| | PLEASE REVIEW AND PROVIDE. |
| | |
| | |
| | |
| | 9) SHEET A 6.3 - THERE ARE NO INDICATIONS OF |
| | HARNDRAIL/GUARDS FOR THE STAIRWELLS. |
| | |
| | 7.2.2.4 GUARDS AND HANDRAILS. |
| | 7.2.2.4.1 HANDRAILS. |
| | 7.2.2.4.1.1 STAIRS AND RAMPS SHALL HAVE HANDRAILS ON |
| | BOTH SIDES, |
| | UNLESS OTHERWISE PERMITTED IN 7.2.2.4.1.5 OR |
| | 7.2.2.4.1.6. |
| | |
| | PLEASE REIVEW AND PROVIDE. |
| | |
| | |
| | |
| | 10) SHEET A 4.3 - ON THE OUTSIDE WALL PARAPET, THERE IS |
| | NO INDICATION OF THE HEIGHT. |
| | |
| | WILL THERE BE AT ANY POINT ALONG THIS WALL EDGE WILL |
| | THE PARAPET BECOME LESS THAN DISCERNABLE? |
| | |
| | WHAT WILL BE THE MINIMUM HEIGHT? |
| | |
| | THIS IS IMPORTANT FOR FIREFIGHTER SAFETY. |
| | |
| | PLEASE PROVIDE DETAILS. |
| | |
| | |
| | |
| | |
| | 11) SHEET A 2.1 - DOOR 21 IS NOT INDICATED WITH A RIFE |
| | RESISTIVE RATING. |
| | |
| | THIS DOOR SEPARATES THE CORRIDOR FROM A ROOM INDICATED |
| | AS TRASH, ADDITIONALLY, CORRIDOR WALLS ARE REQUIRED TO |
| | BE SEPARATED. |
| | |
| | PLEASE REVIEW AND PROVIDE FOR THE REQUIRED SEPARATION. |
| | |
| | |
| | |
| | 12) SHEET F 1.1 - THERE IS AN INDICATION OF A FIRE PUMP |
| | ENCLOSURE. THIS ENCLOSURE WILL NOT BE APPROVED WITH |
| | THIS PERMIT. |
| | |
| | THE FIRE PUMP ENCLOSURE SHALL BE UNDER SEPARATE PERMIT |
| | SUBMITTAL AND COMPLY WITH THE APPLICABLE REQUIREMENTS |
| | INCLUDING, BUT NOT LIMITED TO, FBS, FFPC & NFPA 20. |
| | |
| | IT APPEARS TO BE TOO CLOSE TO THE BUILDING. |
| | |
| | 4.12.1.2 OUTDOOR FIRE PUMP UNITS. |
| | 4.12.1.2.1 FIRE PUMP UNITS THAT ARE OUTDOORS SHALL BE |
| | LOCATED |
| | AT LEAST 50 FT (15.3 M) AWAY FROM ANY BUILDINGS AND |
| | OTHER FIRE |
| | EXPOSURES EXPOSING THE BUILDING. |
| | 4.12.1.2.2 OUTDOOR INSTALLATIONS SHALL BE REQUIRED TO |
| | BE PROVIDED |
| | WITH PROTECTION AGAINST POSSIBLE INTERRUPTION, IN |
| | ACCORDANCE |
| | WITH 4.12.1. |
| | 4.12.1.3 FIRE PUMP BUILDINGS OR ROOMS WITH DIESEL |
| | ENGINES. |
| | FIRE PUMP BUILDINGS OR ROOMS ENCLOSING DIESEL ENGINE |
| | PUMP |
| | DRIVERS AND DAY TANKS SHALL BE PROTECTED WITH AN |
| | AUTOMATIC |
| | SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH NFPA 13, |
| | STANDARD |
| | FOR THE INSTALLATION OF SPRINKLER SYSTEMS. |
| | |
| | PLEASE REVIEW AND ENSURE COMPLIANCE WITH APPLICABLE |
| | CODES. |
| | |
| | PROVIDE A NOTE OF ACKNOWLEDGEMENT AND COMPLIANCE. |
| | |
| | |
| | |
| | |
| | 13) SHEET F 1.1 - THE FOUNDATION OF THE FIRE PUMP |
| | ENCLOSURE SHALL HAVE A FLOOR DRAIN TIED INTO THE |
| | PLUMBING SYSTEM AS APPLICABLE PER UTILITIES |
| | REQUIREMENTS. |
| | |
| | PER NFPA 20 |
| | |
| | 4.12.7* DRAINAGE. |
| | 4.12.7.1 FLOORS SHALL BE PITCHED FOR ADEQUATE DRAINAGE |
| | OF ESCAPING |
| | WATER AWAY FROM CRITICAL EQUIPMENT SUCH AS THE PUMP, |
| | DRIVER, CONTROLLER, AND SO FORTH. |
| | 4.12.7.2 THE PUMP ROOM OR PUMP HOUSE SHALL BE PROVIDED |
| | WITH A FLOOR DRAIN THAT WILL DISCHARGE TO A FROST-FREE |
| | LOCATION. |
| | |
| | PLEASE REVIEW AND ENSURE COMPLIANCE. |
| | |
| | |
| | |
| | |
| | 14) SHEET F 1.1 - THE PROPOSED FIRE HYDRANT AND FDC |
| | LOCATIONS ARE ON OPPOSITE SIDES OF THE ROADWAY. |
| | |
| | FOR THE MOST EFFECTIVE AND EFFICIENT FIRE GROUND |
| | OPERATIONS THE FDC AND FIRE HYDRANT SHOULD BE ON THE |
| | SAME SIDE. |
| | |
| | IT IS HIGHLY RECOMMENDED TO MOVE THE HYDRANT, IF |
| | POSSIBLE, TO THE OTHER SIDE OF THE ROADWAY, (IT WOULD |
| | ALSO BE ACCPETABLE TO MOVE THE FDC TO THE HYDRANT SIDE) |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | |
| | |
| | 15) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 16) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |