| 2019-04-23 11:42:59 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | PGS. E3.1. THOUGH E3.4 NO NOTE FRO ARC FAULT PROTECTION |
| | PER 210.12(C) |
| | |
| | ELECTRICAL ROOM #120 MAIN SWBD REQUIRES WORK SPACE IN |
| | FRONT ATS-LS DOES NOT APPEAR TO BE 3' AWAY, SAME FOR |
| | PANEL 10-S. |
| | |
| | PG. E5.1 NOTE #13 NEED TO FIGURE SIZE OF GUTTER. |
| | |
| | TRANSFER SWITCH OFF CT CAN REQUIRES COMPLIANCE WITH |
| | 240.87 |
| | |
| | 240.87 ARC ENERGY REDUCTION |
| | WHERE THE HIGHEST CONTINUOUS CURRENT TRIP SETTING FOR |
| | WHICH THE |
| | ACTUAL OVERCURRENT DEVICE INSTALLED IN A CIRCUIT |
| | BREAKER IS RATED |
| | OR CAN BE ADJUSTED IS 1200 A OR HIGHER, 240.87(A) AND |
| | (B) SHALL |
| | APPLY. |
| | (A) DOCUMENTATION. DOCUMENTATION SHALL BE AVAILABLE TO |
| | THOSE |
| | AUTHORIZED TO DESIGN, INSTA LL, OPERATE, OR INSPECT THE |
| | INSTALLATION |
| | AS TO THE LOCATION OF THE CIRCUIT BREAKER(S). |
| | (B) METHOD TO REDUCE CLEARING TIME. ONE OF THE |
| | FOLLOWING |
| | OR APPROVED EQUIVALENT MEANS SH ALL BE PROVIDED: |
| | (1) ZONE-SELECTIVE INTERLOCKING |
| | (2) DIFFERENTIAL RELAYING |
| | (3) ENERGY-REDUCING MAINTENANCE SWITCHING WITH LOCAL |
| | STATUS |
| | INDICATOR |
| | (4) ENERGY-REDUCING ACTIVE ARC FLASH MITIGATION SYSTEM |
| | (5) AN APPROVED EQUIVALENT MEANS |
| | |
| | FIRE PUMP FEED OFF GENERATOR HAS TWO DISCONNECT BEFORE |
| | FP CONTROLLER 695.4(B)(1) |
| | 800A AT GENERATOR AND 125A UNDER GUTTER. |
| | |
| | SUPPLY CUT SHEETS FOR FIRE PUMP CONTROLLER 110.3 |
| | |
| | SEPARATE PERMITS REQUIRED FOR FIRE ALARM, GENRATOR, |
| | SITE LIGHTING, LOW VOLTAGE, LIGHTNING PROTECTION. |
| | |
| | |
| | |