2019-04-23 11:42:59ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PGS. E3.1. THOUGH E3.4 NO NOTE FRO ARC FAULT PROTECTION
 PER 210.12(C)
  
 ELECTRICAL ROOM #120 MAIN SWBD REQUIRES WORK SPACE IN
 FRONT ATS-LS DOES NOT APPEAR TO BE 3' AWAY, SAME FOR
 PANEL 10-S.
  
 PG. E5.1 NOTE #13 NEED TO FIGURE SIZE OF GUTTER.
  
 TRANSFER SWITCH OFF CT CAN REQUIRES COMPLIANCE WITH
 240.87
  
 240.87 ARC ENERGY REDUCTION
 WHERE THE HIGHEST CONTINUOUS CURRENT TRIP SETTING FOR
 WHICH THE
 ACTUAL OVERCURRENT DEVICE INSTALLED IN A CIRCUIT
 BREAKER IS RATED
 OR CAN BE ADJUSTED IS 1200 A OR HIGHER, 240.87(A) AND
 (B) SHALL
 APPLY.
 (A) DOCUMENTATION. DOCUMENTATION SHALL BE AVAILABLE TO
 THOSE
 AUTHORIZED TO DESIGN, INSTA LL, OPERATE, OR INSPECT THE
 INSTALLATION
 AS TO THE LOCATION OF THE CIRCUIT BREAKER(S).
 (B) METHOD TO REDUCE CLEARING TIME. ONE OF THE
 FOLLOWING
 OR APPROVED EQUIVALENT MEANS SH ALL BE PROVIDED:
 (1) ZONE-SELECTIVE INTERLOCKING
 (2) DIFFERENTIAL RELAYING
 (3) ENERGY-REDUCING MAINTENANCE SWITCHING WITH LOCAL
 STATUS
 INDICATOR
 (4) ENERGY-REDUCING ACTIVE ARC FLASH MITIGATION SYSTEM
 (5) AN APPROVED EQUIVALENT MEANS
  
 FIRE PUMP FEED OFF GENERATOR HAS TWO DISCONNECT BEFORE
 FP CONTROLLER 695.4(B)(1)
 800A AT GENERATOR AND 125A UNDER GUTTER.
  
 SUPPLY CUT SHEETS FOR FIRE PUMP CONTROLLER 110.3
  
 SEPARATE PERMITS REQUIRED FOR FIRE ALARM, GENRATOR,
 SITE LIGHTING, LOW VOLTAGE, LIGHTNING PROTECTION.
  
  
  