Plan Review Notes
Plan Review Notes For Permit 19030147
Permit Number 19030147
Review Stop B
Sequence Number 1
Notes
Date Text
2019-05-17 10:42:57****CORRECTIONS****
 W.P.B. PERMIT: 19030147
 REVIEWED: MAY 17, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH
 ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES
 TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH
 THE PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/14, AND
 THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR
 GREATER THAN $750,000 WILL NEED TO COMPLY WITH THIS
 ORDINANCE. PER CITY OF WEST PALM BEACH ORDINANCE NO.
 4504-14, AND CITY OF WEST PALM BEACH CODE OF
 ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION
 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS
 1% OF THE TOTAL PROJECT CONSTRUCTION COST. PER CITY OF
 WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, ART IN
 PUBLIC PLACES, SECTION 78-122, RENOVATION AND NEW
 CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO THE
 ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS. SEC. 78-129. - PUBLIC ART ASSESSMENT FOR
 PRIVATE DEVELOPMENT. (A) APPLICABILITY. THE PROVISIONS
 OF THIS ARTICLE AND THE PUBLIC ART ASSESSMENT SECTION
 SHALL APPLY TO ALL PRIVATE DEVELOPMENT PROJECTS,
 INCLUDING NEW CONSTRUCTION, OR THE RENOVATION OR
 IMPROVEMENT OF AN EXISTING BUILDING, WHERE TOTAL
 CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000.00. ALL BUILDINGS WITHIN NEW PLANNED
 DEVELOPMENTS SHALL BE ASSESSED CUMULATIVELY TOWARDS
 THIS ART IN PUBLIC PLACES REQUIREMENT, EVEN IF THE
 BUILDINGS ARE PERMITTED SEPARATELY OR DEVELOPED IN
 PHASES. THE PROVISIONS OF THIS SECTION APPLY TO NEW
 DEVELOPMENT OR NEW CONSTRUCTION WITHIN EXISTING PLANNED
 DEVELOPMENTS.
 - THIS PROJECT MEETS THE CRITERIA TO PROVIDE AIPP.
 PLEASE CONTACT: MS. SYBILLE WELTER ART IN PUBLIC PLACES
 COORDINATOR 822-1515 E-MAIL: [email protected]
  
 2) 1603.1 FBC[B] GENERAL. CONSTRUCTION DOCUMENTS SHALL
 SHOW THE SIZE, SECTION AND RELATIVE LOCATIONS OF
 STRUCTURAL MEMBERS WITH FLOOR LEVELS, COLUMN CENTERS
 AND OFFSETS DIMENSIONED. THE DESIGN LOADS AND OTHER
 INFORMATION PERTINENT TO THE STRUCTURAL DESIGN REQUIRED
 BY SECTIONS 1603.1.1 THROUGH 1603.1.8 SHALL BE
 INDICATED ON THE CONSTRUCTION DOCUMENTS. EXCEPTION:
 CONSTRUCTION DOCUMENTS FOR BUILDINGS CONSTRUCTED IN
 ACCORDANCE WITH THE CONVENTIONAL LIGHT-FRAME
 CONSTRUCTION PROVISIONS OF SECTION 2308 (SEE 1603.1 FOR
 LIGHT STEEL FRAME EXCEPTION AND REQUIREMENTS)
 - PLEASE ADD STRUCTURAL DESIGN CALCULATIONS TO
 SUPPORTING DOCUMENTS FOLDER IN PROJECTDOX.
  
 3) C103.1.1.1.2 FBC[ENERGY] COMMERCIAL AND
 MULTIPLE-FAMILY RESIDENTIAL.DESIGN PROFESSIONALS
 RESPONSIBLE UNDER FLORIDA LAW FOR THE DESIGN OF
 LIGHTING, ELECTRICAL, MECHANICAL, AND PLUMBING SYSTEMS
 AND THE BUILDING SHELL, SHALL CERTIFY COMPLIANCE OF
 THOSE BUILDING SYSTEMS WITH THE CODE BY SIGNING AND
 PROVIDING THEIR PROFESSIONAL REGISTRATION NUMBER ON THE
 ENERGY CODE FORM PROVIDED AS PART OF THE PLANS AND
 SPECIFICATIONS TO THE BUILDING DEPARTMENT.
 - ENERGY CALCULATIONS TO BE SIGNED BY THE PREPARER.
  
 4) C103.1.1.2 FBC[ENERGY] CODE COMPLIANCE
 CERTIFICATION. THE BUILDING?S OWNER, THE OWNER?S
 ARCHITECT, OR OTHER AUTHORIZED AGENT LEGALLY DESIGNATED
 BY THE OWNER SHALL CERTIFY THAT THE BUILDING IS IN
 COMPLIANCE WITH THE CODE, AS PER SECTION 553.907,
 FLORIDA STATUTES, PRIOR TO RECEIVING THE PERMIT TO
 BEGIN CONSTRUCTION OR RENOVATION.
 - ENERGY CALCULATIONS TO BE SIGNED BY APPROPRIATE PARTY
 AS OUTLINED IN C103.1.1.2.
  
 5) C103.3 ENERGY CALCULATIONS.
 - VERIFY PROJECT DATA ON ENERGY CALCULATIONS PAGE 2.
 CONDITIONED AREA AND NON CONDITIONED AREA ARE THE SAME,
 THE NUMBER OF STORIES SHOWS 1.
  
 6) C103.3 ENERGY CALCULATIONS.
 - UNDER SECTION FOR DOORS THERE ARE NO ENTRIES FOR THE
 DOORS. DOORS SHOULD BE INCLUDED WITH THE OVERHANGS
 PROVIDED.
  
 7) C103.2 INFORMATION ON CONSTRUCTION DOCUMENTS.
 - DRAWINGS SHOULD SHOW DESIGN R-VALUE AT ROOF
 ESTABLISHED BY ENERGY CALCULATIONS. THEY STATE R-30.
  
 9) C103.2 INFORMATION ON CONSTRUCTION DOCUMENTS.
 - DRAWINGS SHOULD SHOW DESIGN R-VALUE AT WALL THERMAL
 ENVELOPE ESTABLISHED BY ENERGY CALCULATIONS. THEY STATE
 R-13. PROVIDE CUT SHEET TO SHOW RIDIG BOARD PANEL THAT
 CAN PROVIDE R VALUE NEEDED AFTER ALL OTHER ENVELOPE
 COMPONANTS ARE INCLUDED.
  
 10) GENERAL COMMENT
 - IF POSSIBLE CAN THE DOTTED GRIDLINES BE TURNED OFF
 FOR FLOOR PLANS ON SHEETA2.1 AND A2.2. THIS IS JUST A
 REQUEST TO MAKE DRAWINGS MORE READABLE. WITH FIRE WALLS
 USING DASH DOT LINE TYPE IT WOULD HELP CLARIFY THE
 SEPARATIONS.
  
 FAIRHOUSING REVIEW BEGIN: COMMENTS 11-24
 GENERAL COMMENT
 - IT LOOKS LIKE FLORIDA ACCESSIBLITY CODE WAS APPLIED
 TO THIS PROJECT INSTEAD OF FAIRHOUSING GUIDELINES. THE
 COMMON AREAS USING FLORIDA ACCESSIBILITY WOULD MEET OR
 EXCEED FAIRHOUSING GUIDELINES, BUT THE RESIDENT ROOMS
 WILL FALL SHORT OF MEETING REQUIREMENTS 6 AND 7 BECAUSE
 THEY APPLY TO ALL ROOMS. WITH FAIRHOUSING BEING APPLIED
 THE ADA SUITES WOULD NOT NEED TO BE PROVIDED, BUT THE
 FOLLOWING FAIRHOUSING REQUIREMENTS WOULD APPLY TO ALL
 DWELLING UNITS.
  
 11) 1986 ANSI [A117.1] IF A DESIGNER OR BUILDER CHOOSES
 TO FOLLOW AN ACCESSIBILITY STANDARD OTHER THAN THE 1986
 ANSI A117.1 STANDARD, OR A MORE RECENT VERSION OF THE
 ANSI A117.1, SUCH AS THE 1992 CABO/ANSI, THAT CARE BE
 TAKEN TO ENSURE THE STANDARD USED IS AT LEAST
 EQUIVALENT TO OR STRICTER THAN THE 1986 ANSI A117.1
 STANDARD.
 - WHAT STANDARD IS BEING APPLIED FOR COMPLIANCE WITH
 FAIR HOUSING? YOU CAN USE GUIDELINES THAT FALL WITHIN
 THE SAFE HARBOR FOR COMPLIANCE?
  
 12) REQUIREMENT 1 - PROVIDE AT LEAST ONE ACCESSIBLE
 ROUTE TO BUILDING ENTERANCE. WALKS THAT ARE PART OF
 ACCESSIBLE ROUTES BECOME RAMPS WHEN THEIR SLOPE EXCEEDS
 5% (1 IN 20). HANDRAILS ARE NOT REQUIRED ON WALKS WITH
 SLOPES BETWEEN 0% AND 5%, BUT THEY ARE REQUIRED ON
 THOSE STEEPER THAN 5% AND UP TO 8.33% (1 IN 12)
 - PROVIDE CIVIL PLANS TO VERIFY SLOPES THAT WILL OCCUR
 ON THE ACCESSIBLE PATH. PROVIDE SITE PLAN TO SHOW THE
 ACCESSIBLE PATH FROM PARKING OR OTHER PUBLIC ACCESS
 POINTS SUCH AS BUS STOP OR DROP OFF ZONE.
  
 13) REQUIREMENT 1 - PARKING
 - PROVIDE SITE PLAN WITH PARKING, IF PROVIDED, REVIEW
 OF PARKING WILL BE DONE BASED ON SITE PLAN AND
 GUIDELINES BEING USED FOR FAIR HOUSING.
  
 14) REQUIREMENT 2 - ACCESSIBLE AND USABLE PUBLIC AND
 COMMON USE AREAS
 - IF AMENITIES ARE PROVIDED OUTSIDE OF BUILDING FOR THE
 USERS OF THIS BUILDING, THEN PLEASE SHOW ACCESSIBLE
 PATHS TO THE AMENITIES.
  
 15) IS THERE A MAILROOM?
 - IF SO PLEASE SHOW HOW REACH RANGES ARE ACHIEVED FOR
 MAILBOXES.
  
 16) REQUIREMENT 3 - USABLE DOORS. THE DOORS IN COMMON
 SPACES AND THE SIDE ENTERING INTO DWELLING UNITS NEED
 TO HAVE USABLE HARDWARE THAT CAN BE USED WITHOUT TIGHT
 GRASPING OR TWISTING.
 - TYPICALLY THE HARDWARE WOULD BE A LEVER TYPE. THIS
 TYPE OF HARDWARE WOULD NOT BE REQUIRED ONCE INSIDE THE
 UNIT. YOU MAY WANT TO CLARIFY HARDWARE ON THE DOOR
 SCHEDULE.
  
 17) ONCE INSIDE THE DWELLING UNIT HARDWARE NO LONGER
 APPLIES, BUT CLEAR SPACE ON ALL DOORS REQUIRE 32 INCHES
 NOMINAL CLEAR SPACE.
 - CHECK DOORS INSIDE DWELLING UNITS LABELED E, F, P, Q,
 V, U, EE AND FF AS THEY WOULD NOT PROVIDE THE NOMINAL
 CLEARANCE REQUIRED.
  
 18) REQUIREMENT 4 - ACCESSIBLE ROUTE INTO AND THROUGH
 THE DWELLING UNIT.
 - THEY LOOK OK SINCE ALL FURNITURE IS USABLE AND IF
 DOORS PROVIDE 32 INCH NOMINAL THAN ACCESS WILL BE
 PROVIDED. ALSO, REQUIREMENT 6 WILL HELP ACHIEVE
 ACCESSIBLE ROUTE.
  
 19) REQUIREMENT 5 - LIGHT SWITCHES, OUTLETS,
 THERMOSTATS AND OTHE CONTROLS IN ACCESSIBLE LOCATIONS.
 - THIS CAN BE HANDLED WITH NOTES TO STATE MAXIMUM AND
 MINIMUM HEIGHTS THAT COMPLY WITH THE GUIDELINES BEING
 FOLLOWED. THE NOTES CAN BE IN A FAIRHOUSING OVERVIEW,
 BUT SHOULD ALSO BE ON APPROPRIATE M OR ESHEETS SO THEY
 DON'T GET OVERLOOKED BY THE SPECIFIC TRADES.
  
 20) REQUIREMENT 6 - REINFORCED WALLS FOR GRAB BARS
 - BARS ONLY NEED TO BE INSTALLED IN THE PUBLIC OR
 COMMON USE AREAS. ALL OF THE DWELLING UNITS ONLY NEED
 BLOCKING INSTALLED. SHEET A2.3 SHOWS THE BLOCKING AT
 TOILET AND WILL WORK. PLEASE ADD BLOCKING AT SHOWER
 BECAUSE I ONLY SEE CONTROL ZONE AND THAT WILL BE
 COVERED IN REQUIREMENT 7.
  
 21) REQUIREMENT 7 - USABLE KITCHENS.
 - I ONLY SEE ONE KITCHEN IN UNIT S101. PLEASE SHOW
 CLEAR FLOOR SPACE AT COOKTOP,REFRIDGERATOR AND SINK.
 THE CLEAR SPACE SHOULD BE CENTERED ON THE APPLIANCE.THE
 SINK DOESN'T APPEAR THAT IT WOULD WORK, SO THIS MAY
 NEED TO BE RE-WORKED. ALSO, CHECK
  
 22) REQUIREMENT 7 - COMMON LAUNDRY ROOMS.
 - SHOW CLEAR FLOOR SPACE AT WASHER AND DRYER IN LAUNDRY
 ROOM 118 AND LAUNDRY ROOMS ON FLOORS 2-4. THE CLEAR
 SPACE SHOULD BE CENTERED ON THE APPLIANCES.
  
 23) REQUIREMENT 7 - USABLE BATHROOMS.
 - IN DWELLING UNITS CONTAINING MORE THAN ONE BATHROOM,
 IF SPECIFICATION A IS SELECTED AS THE BASIS FOR
 DESIGNING A BATHROOM, ALL BATHROOMS IN THE DWELLING
 UNIT ALSO MUST COMPLY WITH THE A SPECIFICATIONS. IF
 SPECIFICATION B IS SELECTED, ONLY ONE BATHROOM IN THE
 DWELLING UNIT MUST MEET THOSE REQUIREMENTS ALL
 BATHROOMS AS DEFINED IN THE GUIDELINES MUST:
  
 24) REQUIREMENT 7 - USABLE BATHROOMS.
 - STATE IF THE BATHROOMS IN DWELLING UNITS ARE
 SPECIFICATION A OR B. COMPARTMETALIZED BATHROOMS WILL
 BE CONSIDERED ONE BATHROOM AND BOTH AREAS WILL NEED TO
 SHOW CLEAR SPACE, 32 INCH NOMINAL OPENING, SWITH/OUTLET
 HEIGHTS AND BLOCKING IN WALLS. SHOWERS NEED MINIMUM
 30X48 AND THE SPACE NEEDS TO BE PARALLEL TO THE FIXTURE
 AND FLUSH WITH THE CONTROL WALL. CLEAR SPACE AT SINKS
 NEEDS TO BE CENTERED WITH FIXTURE.
  
 FAIRHOUSING REVIEW END
  
 25) 1606.2 FBC[B] DESIGN DEAD LOAD. FOR PURPOSES OF
 DESIGN, THE ACTUAL WEIGHTS OF MATERIALS OF CONSTRUCTION
 AND FIXED SERVICE EQUIPMENT SHALL BE USED. IN THE
 ABSENCE OF DEFINITE INFORMATION, VALUES USED SHALL BE
 SUBJECT TO THE APPROVAL OF THE BUILDING OFFICIAL.
 - PLEASE PROVIDE DEAD LOAD DATA. STRUCTURAL CALCULATION
 S WERE REQUESTED IN OTHER COMMENT, SO NO RESPONSE
 NEEDED IF THEY ARE BEING SUPPLIED IN THE SUPPORTING
 DOCUMENTS FOLDER.
  
 26) 1604.3.1 FBC[B] DEFLECTIONS. THE DEFLECTIONS OF
 STRUCTURAL MEMBERS SHALL NOT EXCEED THE MORE
 RESTRICTIVE OF THE LIMITATIONS OF SECTIONS 1604.3.2
 THROUGH 1604.3.5 OR THAT PERMITTED BY TABLE 1604.3.
 - ARE THERE STRUCTURAL CALCULATIONS THAT SHOW
 DEFLECTIONS. IF SO PLEASE UPLOAD THEM TO SUPPORTING
 DOCUMENTS, OR INDICATE WHERE THE PLANS HAVE DEFLECTION
 LIMITS.
  
 27)
 28)
 29)
 30)
 COMMENTS 27-30 WERE A MISTKAE ON MY PART AND DO NOT
 APPLY. YOUR AREA, CONSTRUCTION TYPE AND SPRINKLERS TYPE
 WILL WORK FOR PROPOSED AREAS.
  
 31) TABLE 1020.1 AND 708.3 EXCEPTIONS
 - BUILDING DATA SHEET A0.1 STATES .5 SLEEPING UNITS AND
 ,5 COORIDOR. THAT IS CORRECT, BUT THE LINE USED ON LIFE
 SAFETY PLAN MATCHES 1 HOUR DASH DOT IN TABLE. IF .5 IS
 BEING USED THE LINE MAY NEED TO BE CHANGED.
  
 32) TABLE 1020.1 AND 708.3 EXCEPTIONS
 - VERIFY WALL TYPES ON FLOOR PLANS. SHEET A2.2 SUITES
 S-06 AND S-06 CALL FOR FS.2/FS. THIS TYPE DOESN'T MATCH
 CONDITION ON SHEET A7.1. ALSO, EXTERIOR WALLS HAVE NO
 WALL TYPE ASSIGNED.
  
 33) TABLE 1020.1 AND 708.3 EXCEPTIONS
 - PLEASE REVIEW ALL WALL TYPES ARE AS INTENDED PER
 DESIGN. I ONLY SEE SOME DESCREPENCY BETWEEN WALL TYPES
 CALLED OUT ON A0.1, FLOOR PLANS AND GRAPHIC DEPICTIONS
 ON LIFE SAFETY. THEY ARE NOT NECESSARILY NON COMPLIANT.
 I WILL NOT COMMENT ANY WALL THAT EXCEEDS CODE ON THE
 NEXT REVIEW.
  
 34) 602.1 FBC[B] WHERE REQUIRED TO HAVE A
 FIRERESISTANCE RATING BY TABLE 601, BUILDING ELEMENTS
 SHALL COMPLY WITH THE APPLICABLE PROVISIONS OF SECTION
 703.2
  
 35) 602.1 FBC[B] EXTERIOR WALLS SHALL HAVE A
 FIRE-RESISTANCE RATING NOT LESS THAN THAT SPECIFIED IN
 TABLE 602. WHERE REQUIRED TO HAVE A FIRERESISTANCE
 RATING BY TABLE 601, BUILDING ELEMENTS SHALL COMPLY
 WITH THE APPLICABLE PROVISIONS OF SECTION 703.2.
 - (SEE TABLE 601 FOR FIRE-RESISTANCE RATING
 REQUIREMENTS) REVIEW EXTERIOR WALL FOR IIIB .THE
 BUILDING DATA PROVIDED ON SHEET A0.1. SHOWS ZERO HOURS
 EXTERIOR, BUT TABLE 601 CALLS FOR 2 HOURS. IF TABLE 602
 CALLS FOR ZERO TABLE 601 STILL APPLIES.
  
 36) 1005.1 FBC[B] GENERAL. ALL PORTIONS OF THE MEANS OF
 EGRESS SYSTEM SHALL BE SIZED IN ACCORDANCE WITH THIS
 SECTION.
 - SHOW OCCUPANT LOAD PER FLOOR AT 200 PER OCCUPANT AND
 FIRST FLOOR BASED ON THE RESIDENT AREA AND PUBLIC ARES
 SEPARATELY. I CALCULATE 65 AT FLOOR 4, 3 AND 2. YOU DO
 NOT HAVE TO ADD OCCUPANT LOAD FROM ABOVE ON EXIT STAIRS
 (SEE 1005.3.1 STAIRWAYS)WHERE STAIRWAYS SERVE MORE THAN
 ONE STORY, ONLY THE OCCUPANT LOAD OF EACH STORY
 CONSIDERED INDIVIDUALLY SHALL BE USED IN CALCULATING
 THE REQUIRED CAPACITY OF THE STAIRWAYS SERVING THAT
 STORY. IF YOU DO THAN LOSING ONE EXIT WOULD DECREASE
 YOUR REQUIRED CAPACITY BY MORE THAN HALF(1005.5)
  
 37) 1005.1 FBC[B] GENERAL. ALL PORTIONS OF THE MEANS OF
 EGRESS SYSTEM SHALL BE SIZED IN ACCORDANCE WITH THIS
 SECTION.
 - THE FIRST FLOOR SHOULD BE 200 PER OCCUPANT AT
 DWELLING AREAS, BUT COMMON ARES MAY USE DIFFERENT
 NUMBER. FOR EXAMPLE BUSINESS AREA MAY BE 100. ALSO, THE
 COMMON AREAS (MULTI PURPOSE, EVENT, GREAT ROOM AND
 LOBBY) NEED TO BE ASSIGNED OCCUPANT LOADS BASED ON THE
 USE OF THE SPACE. CHECK DOOR SWING OF DOOR 25 BASED ON
 OCCUPANT LOAD IF GREATER THAN 50.
  
 38) 1004.3 FBC[B] POSTING OF OCCUPANT LOAD. EVERY ROOM
 OR SPACE THAT IS AN ASSEMBLY OCCUPANCY SHALL HAVE THE
 OCCUPANT LOAD OF THE ROOM OR SPACE POSTED IN A
 CONSPICUOUS PLACE, NEAR THE MAIN EXIT OR EXIT ACCESS
 DOORWAY FROM THE ROOM OR SPACE. POSTED SIGNS SHALL BE
 OF AN APPROVED LEGIBLE PERMANENT DESIGN AND SHALL BE
 MAINTAINED BY THE OWNER OR THE OWNER?S AUTHORIZED
 AGENT.
  
 39) 1005.7.1 FBC[B] DOORS. DOORS, WHEN FULLY OPENED,
 SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE THAN 7
 INCHES (178 MM). DOORS IN ANY POSITION SHALL NOT REDUCE
 THE REQUIRED WIDTH BY MORE THAN ONE-HALF.
 - WITH A MINIMUM CORRIDOR WIDTH OF 44 INCHES AND DOORS
 SWINGING INTO THE REQUIRED WIDTH, A DIMENSION BETWEEN
 DOORS WOULD HELP BECAUSE IT IS VERY CLOSE TO EXCEEDING
 SWING ALLOWED BY 1005.7.1
  
 40) 1009.1 FBC[B] ACCESSIBLE MEANS OF EGRESS REQUIRED.
 ACCESSIBLE MEANS OF EGRESS SHALL BE PROVIDED IN
 ACCORDANCE WITH THE APPLICABLE SECTIONS OF THE FLORIDA
 BUILDING CODE, ACCESSIBILITY.
 - SEE FBC ACCESSIBILITY CODE
  
 41) 207.1 FBC[A] GENERAL. MEANS OF EGRESS SHALL COMPLY
 WITH SECTION 1003.2.13 OF THE INTERNATIONAL BUILDING
 CODE (2000 EDITION AND 2001 SUPPLEMENT) OR SECTION 1007
 OF THE INTERNATIONAL BUILDING CODE (2003 EDITION)
 (INCORPORATED BY REFERENCE, SEE ?REFERENCED STANDARDS?
 IN CHAPTER 1). EXCEPTIONS:
 - SHOW HOW ACCESSIBLE EGRESS IS ACHIEVED ON LIFE SAFETY
 SHEET.
  
 42) 1011.12 FBC[B] STAIRWAY TO ROOF. IN BUILDINGS FOUR
 OR MORE STORIES ABOVE GRADE PLANE, ONE STAIRWAY SHALL
 EXTEND TO THE ROOF SURFACE UNLESS THE ROOF HAS A SLOPE
 STEEPER THAN FOUR UNITS VERTICAL IN 12 UNITS HORIZONTAL
 (33-PERCENT SLOPE).
 - REVIEW THIS CODE SECTION FOR COMPLIANCE BECAUSE ROOF
 HATCH IS PROPOSED. PROVIDE CODE SECTION THAT ALLOWS
 ROOF HATCH FOR A 4 STORY BUILDING.
  
 43) 1006.2.2.1 FBC[B] BOILER, INCINERATOR AND FURNACE
 ROOMS. TWO EXIT ACCESS DOORWAYS ARE REQUIRED IN BOILER,
 INCINERATOR AND FURNACE ROOMS WHERE THE AREA IS OVER
 500 SQUARE FEET (46 M2) AND ANY FUEL-FIRED EQUIPMENT
 EXCEEDS 400,000 BRITISH THERMAL UNITS (BTU) (422 000
 KJ) INPUT CAPACITY. WHERE TWO EXIT ACCESS DOORWAYS ARE
 REQUIRED, ONE IS PERMITTED TO BE A FIXED LADDER OR AN
 ALTERNATING TREAD DEVICE. EXIT ACCESS DOORWAYS SHALL BE
 SEPARATED BY A HORIZONTAL DISTANCE EQUAL TO ONE HALF
 THE LENGTH OF THE MAXIMUM OVERALL DIAGONAL DIMENSION OF
 THE ROOM.
 - REVIEW THIS CODE SECTION AT MECHANICAL YARD FOR
 EXITS.
  
 44) 1607.8.1 FBC[B] HANDRAILS AND GUARDS. HANDRAILS AND
 GUARDS SHALL BE DESIGNED TO RESIST A LINEAR LOAD OF 50
 POUNDS PER LINEAR FOOT (PLF) (0.73 KN/M) IN ACCORDANCE
 WITH SECTION 4.5.1 OF ASCE 7. GLASS HANDRAIL ASSEMBLIES
 AND GUARDS SHALL ALSO COMPLY WITH SECTION 2407. (SEE
 EXCEPTIONS FOR 1607.8.1)
 - ADD HANDRAILS AND GUARDS TO DEFERRED SUBMITTAL LIST
 ON SHEET A0.1.
  
 45) 1023.6 FBC[B] VENTILATION. EQUIPMENT AND DUCTWORK
 FOR INTERIOR EXIT STAIRWAY AND RAMP VENTILATION AS
 PERMITTED BY SECTION 1023.5 SHALL COMPLY WITH ONE OF
 THE FOLLOWING ITEMS:
 1. SUCH EQUIPMENT AND DUCTWORK SHALL BE LOCATED
 EXTERIOR TO THE BUILDING AND SHALL BE DIRECTLY
 CONNECTED TO THE INTERIOR EXIT STAIRWAY AND RAMP BY
 DUCTWORK ENCLOSED IN CONSTRUCTION AS REQUIRED FOR
 SHAFTS.
 2. WHERE SUCH EQUIPMENT AND DUCTWORK IS LOCATED WITHIN
 THE INTERIOR EXIT STAIRWAY AND RAMP, THE INTAKE AIR
 SHALL BE TAKEN DIRECTLY FROM THE OUTDOORS AND THE
 EXHAUST AIR SHALL BE DISCHARGED DIRECTLY TO THE
 OUTDOORS, OR SUCH AIR SHALL BE CONVEYED THROUGH DUCTS
 ENCLOSED IN CONSTRUCTION AS REQUIRED FOR SHAFTS.
 3. WHERE LOCATED WITHIN THE BUILDING, SUCH EQUIPMENT
 AND DUCTWORK SHALL BE SEPARATED FROM THE REMAINDER OF
 THE BUILDING, INCLUDING OTHER MECHANICAL EQUIPMENT,
 WITH CONSTRUCTION AS REQUIRED FOR SHAFTS. IN EACH CASE,
 OPENINGS INTO THE FIRE-RESISTANCE-RATED CONSTRUCTION
 SHALL BE LIMITED TO THOSE NEEDED FOR MAINTENANCE AND
 OPERATION AND SHALL BE PROTECTED BY OPENING PROTECTIVES
 IN ACCORDANCE WITH SECTION 716 FOR SHAFT ENCLOSURES.
 THE INTERIOR EXIT STAIRWAY AND RAMP VENTILATION SYSTEMS
 SHALL BE INDEPENDENT OF OTHER BUILDING VENTILATION
 SYSTEMS.
 -IS THERE ANY VENTILATION PROVIDED AT ENCLOSED
 STAIRWAYS?
  
 46) 1023.9 FBC[B] STAIRWAY IDENTIFICATION SIGNS. A SIGN
 SHALL BE PROVIDED AT EACH FLOOR LANDING IN AN INTERIOR
 EXIT STAIRWAY AND RAMP CONNECTING MORE THAN THREE
 STORIES DESIGNATING THE FLOOR LEVEL, THE TERMINUS OF
 THE TOP AND BOTTOM OF THE INTERIOR EXIT STAIRWAY AND
 RAMP AND THE IDENTIFICATION OF THE STAIRWAY OR RAMP.
 THE SIGNAGE SHALL ALSO STATE THE STORY OF, AND THE
 DIRECTION TO, THE EXIT DISCHARGE AND THE AVAILABILITY
 OF ROOF ACCESS FROM THE INTERIOR EXIT STAIRWAY AND RAMP
 FOR THE FIRE DEPARTMENT. THE SIGN SHALL BE LOCATED 5
 FEET (1524 MM) ABOVE THE FLOOR LANDING IN A POSITION
 THAT IS READILY VISIBLE WHEN THE DOORS ARE IN THE OPEN
 AND CLOSED POSITIONS. IN ADDITION TO THE STAIRWAY
 IDENTIFICATION SIGN, A FLOOR-LEVEL SIGN IN VISUAL
 CHARACTERS, RAISED CHARACTERS AND BRAILLE COMPLYING
 WITH THE FLORIDA BUILDING CODE, ACCESSIBILITY SHALL BE
 LOCATED AT EACH FLOOR-LEVEL LANDING ADJACENT TO THE
 DOOR LEADING FROM THE INTERIOR EXIT STAIRWAY AND RAMP
 INTO THE CORRIDOR TO IDENTIFY THE FLOOR LEVEL.
  
 47) 1023.9.1 FBC[B] SIGNAGE REQUIREMENTS. STAIRWAY
 IDENTIFICATION SIGNS SHALL COMPLY WITH ALL OF THE
 FOLLOWING REQUIREMENTS:
  
 48) 1030.1 FBC[B] GENERAL. IN ADDITION TO THE MEANS OF
 EGRESS REQUIRED BY THIS CHAPTER, PROVISIONS SHALL BE
 MADE FOR EMERGENCY ESCAPE AND RESCUE OPENINGS IN GROUP
 R-2 OCCUPANCIES IN ACCORDANCE WITH TABLES 1006.3.2(1)
 AND 1006.3.2(2).
 - HOW ARE PROVISIONS OF THIS SECTION BEING PROVIDED
 FOR. I DON?T SEE A WINDOW SCHEDULE FOR THIS PROJECT.
 ARE THE WINDOWS OPERABLE? PLEASE PROVIDE WINDOW
 SCHEDULE, OR INDICATE WHERE I CAN FIND THIS INFORMATION
 ON THE PLANS. SHEET A0.1 MENTIONS NO FIRE ESCAPE
 WINDOWS DUE TO SPRINKLER PROVIDED. IF THERE IS
 EXCEPTION TO 1030.1 PLEASE PROVIDE THE APPLICABLE CODE
 SECTION FOR 2ND REVIEW.
  
 49) 705.8.1 FBC[B] ALLOWABLE AREA OF OPENINGS. THE
 MAXIMUM AREA OF UNPROTECTED AND PROTECTED OPENINGS
 PERMITTED IN AN EXTERIOR WALL IN ANY STORY OF A
 BUILDING SHALL NOT EXCEED THE PERCENTAGES SPECIFIED IN
 TABLE 705.8.
 - (SEE TABLE 705.8) THIS WILL BE REVIEWED ONCE A SITE
 PLAN WITH SEPARATION DISTANCES IS PROVIDED.
  
 50) 705.8 TABLE FBC[B] MAXIMUM AREA OF EXTERIOR WALL
 OPENINGS BASED ON FIRE SEPARATION DISTANCE AND DEGREE
 OF OPENING PROTECTION
 - (SEE TABLE 705.8 FOR ALLOWABLE AMOUNTS OF OPENINGS)
  
 51) 705.8 TABLE FBC[B] MAXIMUM AREA OF EXTERIOR WALL
 OPENINGS BASED ON FIRE SEPARATION DISTANCE AND DEGREE
 OF OPENING PROTECTION
  
 52) 713.13.4 FBC[B] CHUTE DISCHARGE ROOM. WASTE OR
 LINEN CHUTES SHALL DISCHARGE INTO AN ENCLOSED ROOM
 SEPARATED BY FIRE BARRIERS WITH A FIRE-RESISTANCE
 RATING NOT LESS THAN THE REQUIRED FIRE RATING OF THE
 SHAFT ENCLOSURE AND CONSTRUCTED IN ACCORDANCE WITH
 SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED IN
 ACCORDANCE WITH SECTION 711, OR BOTH. OPENINGS INTO THE
 DISCHARGE ROOM FROM THE REMAINDER OF THE BUILDING SHALL
 BE PROTECTED BY OPENING PROTECTIVES HAVING A FIRE
 PROTECTION RATING EQUAL TO THE PROTECTION REQUIRED FOR
 THE SHAFT ENCLOSURE. DOORS SHALL BE SELF- OR
 AUTOMATICCLOSING UPON THE DETECTION OF SMOKE IN
 ACCORDANCE WITH SECTION 716.5.9.3. WASTE CHUTES SHALL
 NOT TERMINATE IN AN INCINERATOR ROOM. WASTE AND LINEN
 ROOMS THAT ARE NOT PROVIDED WITH CHUTES NEED ONLY
 COMPLY WITH TABLE 509.
 - PLEASE CHECK DOOR 20 TO MEET THE REQUIRED PROTECTION
 RATING EQUAL TO THE SHAFT ENCLOSURE.
  
 53) 714.4 FBC[B] HORIZONTAL ASSEMBLIES. PENETRATIONS OF
 A FIRE-RESISTANCE- RATED FLOOR, FLOOR/CEILING ASSEMBLY
 OR THE CEILING MEMBRANE OF A ROOF/CEILING ASSEMBLY NOT
 REQUIRED TO BE ENCLOSED IN A SHAFT BY SECTION 712.1
 SHALL BE PROTECTED IN ACCORDANCE WITH SECTIONS 714.4.1
 THROUGH 714.4.4. 714.4.1 THROUGH PENETRATIONS. THROUGH
 PENETRATIONS OF HORIZONTAL ASSEMBLIES SHALL COMPLY WITH
 SECTION 714.4.1.1 OR 714.4.1.2. EXCEPTIONS:
 1. PENETRATIONS BY STEEL, FERROUS OR COPPER CONDUITS,
 PIPES, TUBES OR VENTS OR CONCRETE OR MASONRY ITEMS
 THROUGH A SINGLE FIRE-RESISTANCE- RATED FLOOR ASSEMBLY
 WHERE THE ANNULAR SPACE IS PROTECTED WITH MATERIALS
 THAT PREVENT THE PASSAGE OF FLAME AND HOT GASES
 SUFFICIENT TO IGNITE COTTON WASTE WHEN SUBJECTED TO
 ASTM E119 OR UL 263 TIME-TEMPERATURE FIRE CONDITIONS
 UNDER A MINIMUM POSITIVE PRESSURE DIFFERENTIAL OF 0.01
 INCH (2.49 PA) OF WATER AT THE LOCATION OF THE
 PENETRATION FOR THE TIME PERIOD EQUIVALENT TO THE
 FIRE-RESISTANCE RATING OF THE CONSTRUCTION PENETRATED.
 PENETRATING ITEMS WITH A MAXIMUM 6-INCH (152 MM)
 NOMINAL DIAMETER SHALL NOT BE LIMITED TO THE
 PENETRATION OF A SINGLE FIRE-RESISTANCE-RATED FLOOR
 ASSEMBLY, PROVIDED THE AGGREGATE AREA OF THE OPENINGS
 THROUGH THE ASSEMBLY DOES NOT EXCEED 144 SQUARE INCHES
 (92 900 MM2) IN ANY 100 SQUARE FEET (9.3 M2) OF FLOOR
 AREA.
 2. PENETRATIONS IN A SINGLE CONCRETE FLOOR BY STEEL,
 FERROUS OR COPPER CONDUITS, PIPES, TUBES OR VENTS WITH
 A MAXIMUM 6-INCH (152 MM) NOMINAL DIAMETER, PROVIDED
 THE CONCRETE, GROUT OR MORTAR IS INSTALLED THE FULL
 THICKNESS OF THE FLOOR OR THE THICKNESS REQUIRED TO
 MAINTAIN THE FIRE-RESISTANCE RATING. THE PENETRATING
 ITEMS SHALL NOT BE LIMITED TO THE PENETRATION OF A
 SINGLE CONCRETE FLOOR, PROVIDED THE AREA OF THE OPENING
 THROUGH EACH FLOOR DOES NOT EXCEED 144 SQUARE INCHES
 (92 900 MM2).
 3. PENETRATIONS BY LISTED ELECTRICAL BOXES OF ANY
 MATERIAL, PROVIDED SUCH BOXES HAVE BEEN TESTED FOR USE
 IN FIRE-RESISTANCE-RATED ASSEMBLIES AND INSTALLED IN
 ACCORDANCE WITH THE INSTRUCTIONS INCLUDED IN THE
 LISTING.
 - SHEETS A7.1 AND 7.2 DO NOT MENTION HOW CEILING
 PENETRATIONS ARE HANDLED. 420.3 HORIZONTAL SEPARATION
 OF DWELLING UNIT FLOORS TO BE HORIZONTAL ASSEMBLIES
 WITH SECTION 711.
  
  
 54) 714.4.2 FBC[B] MEMBRANE PENETRATIONS. PENETRATIONS
 OF MEMBRANES THAT ARE PART OF A HORIZONTAL ASSEMBLY
 SHALL COMPLY WITH SECTION 714.4.1.1 OR 714.4.1.2. WHERE
 FLOOR/CEILING ASSEMBLIES ARE REQUIRED TO HAVE A
 FIRE-RESISTANCE RATING, RECESSED FIXTURES SHALL BE
 INSTALLED SUCH THAT THE REQUIRED FIRE RESISTANCE WILL
 NOT BE REDUCED.
 - (SEE 714.4.2 FOR EXCEPTIONS)
  
 55) 715.1 FBC[B] GENERAL. JOINTS INSTALLED IN OR
 BETWEEN FIRE-RESISTANCE RATED WALLS, FLOOR OR
 FLOOR/CEILING ASSEMBLIES AND ROOFS OR ROOF/CEILING
 ASSEMBLIES SHALL BE PROTECTED BY AN APPROVED
 FIRE-RESISTANT JOINT SYSTEM DESIGNED TO RESIST THE
 PASSAGE OF FIRE FOR A TIME PERIOD NOT LESS THAN THE
 REQUIRED FIRE-RESISTANCE RATING OF THE WALL, FLOOR OR
 ROOF IN OR BETWEEN WHICH THE SYSTEM IS INSTALLED.
 FIRE-RESISTANT JOINT SYSTEMS SHALL BE TESTED IN
 ACCORDANCE WITH SECTION 715.3.
 - COMMENT IS FOR HORIZONTAL FLOOR ASSEMBLIES
  
 56) 716.5 FBC TABLE[B] OPENING FIRE PROTECTION
 ASSEMBLIES, RATINGS AND MARKINGS
 - IF FIRE PARTITIONS ARE .5 HOURS AS STATED ON A0.1
 DOORS WOULD ONLY REQUIRE 1/3 HOUR RATING MINIMUM. THIS
 IS GENERAL COMMENT AND NO RESPONSE IS REQUIRED.
  
 57) 107.2.5 FBC[AMENDED] PROVIDE SURVEY OF PROPERTY
 SHOWING EASEMENTS AND DISTANCE FROM PROPERTY LINES TO
 NEW STRUCTURE. SURVEY TO INCLUDE SLAB ELEVATION AND
 SHOW POSITIVE DRAINAGE FROM FOUNDATION.
 - 107.2.5 FBC[AMENDED](FL. STATUTE 472.025)SURVEY TO BE
 SIGNED AND SEALED BY THE SURVEYOR OF RECORD.
  
 58) 401.4 FBC[R] PROVIDE SOIL REPORT TO SHOW BEARING
 CAPACITY AND FOUNDATION RECOMMENDATIONS.
 - THIS CAN BE ADDED TO SUPPORTING DOCUMENTS AS MULTI
 PAGE PDF.
  
 59) 107.3.5.3 FBC[AMENDED] PROVIDE SEDIMENT CONTROL TO
 KEEP CONSTRUCTION DEBRIS FROM ENTERING ADJACENT
 PROPERTIES AND STORM DRAINS DURING CONSTRUCTION. YOU
 CAN JUST ADD SILT FENCE DETAIL AND HOW DRAINS ARE
 PROTECTED TO THE DRAINAGE PLAN. SOME ENGINEERING
 STANDARD DETAILS CAN BE USED FROM WPB WEBSITE-POLLUTION
 CONTROL. HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUB
 LIC-WORKS/FORMS,-PERMITS-APPLICATIONS
 - PROVIDE CIVIL PLANS THAT SHOW DRAINAGE AND ELEVATIONS
 RELEVANT TO PARKING, BUILDING ENTRY AND ACCESSIBLE
 PATH.
  
 60) 1804.6 FBC[B] COMPACTED FILL MATERIAL. WHERE
 SHALLOW FOUNDATIONS WILL BEAR ON COMPACTED FILL
 MATERIAL, THE COMPACTED FILL SHALL COMPLY WITH THE
 PROVISIONS OF AN APPROVED GEOTECHNICAL REPORT, AS SET
 FORTH IN SECTION 1803. EXCEPTION: COMPACTED FILL
 MATERIAL 12 INCHES (305 MM) IN DEPTH OR LESS NEED NOT
 COMPLY WITH AN APPROVED REPORT, PROVIDED THE IN-PLACE
 DRY DENSITY IS NOT LESS THAN 90 PERCENT OF THE MAXIMUM
 DRY DENSITY AT OPTIMUM MOISTURE CONTENT DETERMINED IN
 ACCORDANCE WITH ASTM D1557.
 - THIS WILL BE VERIFIED WITH CIVIL PLANS AND
 GEOTECHNICAL REPORT THAT HAVE BEEN REQUESTED IN THIS
 REVIEW.
  
 61) 1603.1.4 FBC[B] WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCERESISTING SYSTEM OF THE STRUCTURE:
  
 62) 3002.1.2 FBC[B] HARDWARE. HARDWARE ON OPENING
 PROTECTIVES SHALL BE OF AN APPROVED TYPE INSTALLED AS
 TESTED, EXCEPT THAT APPROVED INTERLOCKS, MECHANICAL
 LOCKS AND ELECTRIC CONTACTS, DOOR AND GATE ELECTRIC
 CONTACTS AND DOOR-OPERATING MECHANISMS SHALL BE EXEMPT
 FROM THE FIRE TEST REQUIREMENTS. 3002.2 NUMBER OF
 ELEVATOR CARS IN A HOISTWAY. WHERE FOUR OR MORE
 ELEVATOR CARS SERVE ALL OR THE SAME PORTION OF A
 BUILDING, THE ELEVATORS SHALL BE LOCATED IN NOT FEWER
 THAN TWO SEPARATE HOISTWAYS. NOT MORE THAN FOUR
 ELEVATOR CARS SHALL BE LOCATED IN ANY SINGLE HOISTWAY
 ENCLOSURE.
  
 63) 3002.3 FBC[B] EMERGENCY SIGNS. AN APPROVED
 PICTORIAL SIGN OF A STANDARDIZED DESIGN SHALL BE POSTED
 ADJACENT TO EACH ELEVATOR CALL STATION ON ALL FLOORS
 INSTRUCTING OCCUPANTS TO USE THE EXIT STAIRWAYS AND NOT
 TO USE THE ELEVATORS IN CASE OF FIRE. THE SIGN SHALL
 READ: IN CASE OF FIRE, ELEVATORS ARE OUT OF SERVICE.
 USE EXIT STAIRS. EXCEPTIONS: (SEE 3002.3 FOR
 EXCEPTIONS)
  
 64) 3002.4 FBC[B] ELEVATOR CAR TO ACCOMMODATE AMBULANCE
 STRETCHER. ANY BUILDING THAT IS MORE THAN THREE STORIES
 HIGH OR IN WHICH THE VERTICAL DISTANCE BETWEEN THE
 BOTTOM TERMINAL LANDING AND THE TOP TERMINAL LANDING
 EXCEEDS 25 FEET (7620 MM), MUST BE CONSTRUCTED TO
 CONTAIN AT LEAST ONE PASSENGER ELEVATOR THAT IS
 OPERATIONAL FOR BUILDING OCCUPANTS AND FIRE DEPARTMENT
 EMERGENCY ACCESS TO ALL FLOORS. THE ELEVATOR CAR SHALL
 BE OF SUCH A SIZE AND ARRANGEMENT TO ACCOMMODATE AN
 AMBULANCE STRETCHER 24 INCHES BY 76 INCHES (610 MM BY
 1950 MM) WITH NOT LESS THAN 5-INCH (127 MM) RADIUS
 CORNERS, IN THE HORIZONTAL, OPEN POSITION AND SHALL BE
 IDENTIFIED BY THE INTERNATIONAL SYMBOL FOR EMERGENCY
 MEDICAL SERVICES (STAR OF LIFE). THE SYMBOL SHALL BE
 NOT LESS THAN 3 INCHES (76 MM) IN HEIGHT AND SHALL BE
 PLACED INSIDE ON BOTH SIDES OF THE HOISTWAY DOOR FRAME.
 - SHOW HOW STRECHER WILL FIT IN ONE OF THE ELEVATORS. A
 GRAPHIC REPRESENTAION OF 24X74 INCH RECTANGLE WITH
 MAXIMUM 5 INCH RADIUS CORNERS FROM ENTRY TO FINAL
 POSITION ON PLAN VIEW WILL HELP CLARIFY THAT THIS
 REQUIREMENT IS MET.
  
 65) 2207.5 FBC[B] CERTIFICATION. AT COMPLETION OF
 MANUFACTURE, THE STEEL JOIST MANUFACTURER SHALL SUBMIT
 A CERTIFICATE OF COMPLIANCE TO THE OWNER OR THE OWNER?S
 AUTHORIZED AGENT FOR SUBMITTAL TO THE BUILDING OFFICIAL
 AS SPECIFIED IN SECTION 1704.5 STATING THAT WORK WAS
 PERFORMED IN ACCORDANCE WITH APPROVED CONSTRUCTION
 DOCUMENTS AND WITH SJI SPECIFICATIONS LISTED IN SECTION
 2207.1
 - ADD TO DEFFERED SUBMITTAL L;IST
  
 66) 1504.3 FBC[B] WIND RESISTANCE OF NONBALLASTED
 ROOFS. ROOF COVERINGS INSTALLED ON ROOFS IN ACCORDANCE
 WITH SECTION 1507 THAT ARE MECHANICALLY ATTACHED OR
 ADHERED TO THE ROOF DECK SHALL BE DESIGNED TO RESIST
 THE DESIGN WIND LOAD PRESSURES FOR COMPONENTS AND
 CLADDING IN ACCORDANCE WITH SECTION 1609.
 - ROOF PRODUCT APPROVAL 14083. PLEASE ADD THE 5 PAGE
 EVALUATION REPORT TO THE PRODUCT APPROVAL, AS STATED IN
 THE EVALUATION REPORT 5.7 THE INSULATION AND INSULATION
 ATTACHMENT NEEDS TO BE PART OF THE ROOFING SUBMITTAL.
 ALSO, SELECT THE SYSTEM BEING USED ON FL14803, OR ONLY
 PROVIDE THE SHEETS FOR THE SYSTEM BEING INSTALLED.
  
 THE ROOFING SUBMITTAL CAN BE DEFERRED SUBMITTAL IF THE
 FULL SUBMITTAL IS NOT READY YET.
 - IF THE SUBMITTAL ID TO BE DEFERRED, ADD IT TO THE
 LIST ON SHEET A0.1.
  
 67) FL 16554 AND FL 14218 FOR STOREFRONT.
 - PLEASE SELECT THE SYSTEMS BEING USED AS MORE THAN ONE
 OPTION IS SHOWN ON SUMMARY OF PRODUCTS
  
 68) 107.3.4.1 FBC[AMENDED] DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 - PLEASE ADD ANY ADDITIONAL DEFERRED SUBMITTALS TO THE
 LIST ON SHEET A0.1. AIPP COMPLIANCE REQUIRED;
 VERIFICATION REQUIRED PRIOR TO C.O., SHORING AND
 RE-SHORING(IF APPLICABLE), TILT UP TEMPORARY BRACING BY
 ENGINEER, ROOM DIVIDER IN EVENT ROOM, HANDRAILS AND
 GUARDRAILS, FLOOR UNDERLAYMENT/SOUNDPROOFING AND WASTE
 CHUTE ACCESS DOOR (713.13.1)
  
 69) PLEASE ADVISE ,VIA EMAIL, WHAT FLOORING AND
 UNDERLAYMENT ARE PROPOSED? IF THE UNDERLAYMENT PRODUCT
 PROPOSED IS NOT ONE FOR WHICH WE HAVE TEST REPORTS ON
 FILE, THE FOLLOWING REPORTS WILL BE REQUIRED:
 - THIS APPLIES TO FLOORING IN DWELLINGS ON FLOORS 2-4
  
 1207.2 FBC[B] AIR-BORNE SOUND. WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS AND
 SLEEPING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS OF
 NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED,
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E90.
  
 1207.3 FBC[B] STRUCTURE-BORNE SOUND. FLOOR/CEILING
 ASSEMBLIES BETWEEN DWELLING UNITS AND SLEEPING UNITS OR
 BETWEEN A DWELLING UNIT OR SLEEPING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS RATING OF NOT LESS THAN 50, OR
 NOT LESS THAN 45 IF FIELD TESTED, WHEN TESTED IN
 ACCORDANCE WITH ASTM E492.
  
 603.1 FBC[B] ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
 - IF FLOORING IS TO BE A DEFERRED SUBMITTAL, ADD IT TO
 THE LIST ON SHEET A0.1.
  
 70) 804.1 FBC[B] GENERAL. INTERIOR FLOOR FINISH AND
 FLOOR COVERING MATERIALS SHALL COMPLY WITH SECTIONS
 804.2 THROUGH 804.4.2. EXCEPTION: FLOOR FINISHES AND
 COVERINGS OF A TRADITIONAL TYPE, SUCH AS WOOD, VINYL,
 LINOLEUM OR TERRAZZO, AND RESILIENT FLOOR COVERING
 MATERIALS THAT ARE NOT COMPRISED OF FIBERS.
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -COMMENTS ARE A BRIEF OVERVIEW OF CODE SECTIONS.
 FURTHER REVIEW OF THE REFERENCED CODE SECTIONS WILL BE
 REQUIRED.
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  