| 2019-05-17 10:42:57 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 19030147 |
| | REVIEWED: MAY 17, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[B] = FBC BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | FBC[R] = FBC RESIDENTIAL |
| | |
| | 1) ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH |
| | ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES |
| | TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH |
| | THE PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/14, AND |
| | THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR |
| | GREATER THAN $750,000 WILL NEED TO COMPLY WITH THIS |
| | ORDINANCE. PER CITY OF WEST PALM BEACH ORDINANCE NO. |
| | 4504-14, AND CITY OF WEST PALM BEACH CODE OF |
| | ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION |
| | 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS |
| | 1% OF THE TOTAL PROJECT CONSTRUCTION COST. PER CITY OF |
| | WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, ART IN |
| | PUBLIC PLACES, SECTION 78-122, RENOVATION AND NEW |
| | CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO THE |
| | ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| | PROJECTS. SEC. 78-129. - PUBLIC ART ASSESSMENT FOR |
| | PRIVATE DEVELOPMENT. (A) APPLICABILITY. THE PROVISIONS |
| | OF THIS ARTICLE AND THE PUBLIC ART ASSESSMENT SECTION |
| | SHALL APPLY TO ALL PRIVATE DEVELOPMENT PROJECTS, |
| | INCLUDING NEW CONSTRUCTION, OR THE RENOVATION OR |
| | IMPROVEMENT OF AN EXISTING BUILDING, WHERE TOTAL |
| | CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN |
| | $750,000.00. ALL BUILDINGS WITHIN NEW PLANNED |
| | DEVELOPMENTS SHALL BE ASSESSED CUMULATIVELY TOWARDS |
| | THIS ART IN PUBLIC PLACES REQUIREMENT, EVEN IF THE |
| | BUILDINGS ARE PERMITTED SEPARATELY OR DEVELOPED IN |
| | PHASES. THE PROVISIONS OF THIS SECTION APPLY TO NEW |
| | DEVELOPMENT OR NEW CONSTRUCTION WITHIN EXISTING PLANNED |
| | DEVELOPMENTS. |
| | - THIS PROJECT MEETS THE CRITERIA TO PROVIDE AIPP. |
| | PLEASE CONTACT: MS. SYBILLE WELTER ART IN PUBLIC PLACES |
| | COORDINATOR 822-1515 E-MAIL: [email protected] |
| | |
| | 2) 1603.1 FBC[B] GENERAL. CONSTRUCTION DOCUMENTS SHALL |
| | SHOW THE SIZE, SECTION AND RELATIVE LOCATIONS OF |
| | STRUCTURAL MEMBERS WITH FLOOR LEVELS, COLUMN CENTERS |
| | AND OFFSETS DIMENSIONED. THE DESIGN LOADS AND OTHER |
| | INFORMATION PERTINENT TO THE STRUCTURAL DESIGN REQUIRED |
| | BY SECTIONS 1603.1.1 THROUGH 1603.1.8 SHALL BE |
| | INDICATED ON THE CONSTRUCTION DOCUMENTS. EXCEPTION: |
| | CONSTRUCTION DOCUMENTS FOR BUILDINGS CONSTRUCTED IN |
| | ACCORDANCE WITH THE CONVENTIONAL LIGHT-FRAME |
| | CONSTRUCTION PROVISIONS OF SECTION 2308 (SEE 1603.1 FOR |
| | LIGHT STEEL FRAME EXCEPTION AND REQUIREMENTS) |
| | - PLEASE ADD STRUCTURAL DESIGN CALCULATIONS TO |
| | SUPPORTING DOCUMENTS FOLDER IN PROJECTDOX. |
| | |
| | 3) C103.1.1.1.2 FBC[ENERGY] COMMERCIAL AND |
| | MULTIPLE-FAMILY RESIDENTIAL.DESIGN PROFESSIONALS |
| | RESPONSIBLE UNDER FLORIDA LAW FOR THE DESIGN OF |
| | LIGHTING, ELECTRICAL, MECHANICAL, AND PLUMBING SYSTEMS |
| | AND THE BUILDING SHELL, SHALL CERTIFY COMPLIANCE OF |
| | THOSE BUILDING SYSTEMS WITH THE CODE BY SIGNING AND |
| | PROVIDING THEIR PROFESSIONAL REGISTRATION NUMBER ON THE |
| | ENERGY CODE FORM PROVIDED AS PART OF THE PLANS AND |
| | SPECIFICATIONS TO THE BUILDING DEPARTMENT. |
| | - ENERGY CALCULATIONS TO BE SIGNED BY THE PREPARER. |
| | |
| | 4) C103.1.1.2 FBC[ENERGY] CODE COMPLIANCE |
| | CERTIFICATION. THE BUILDING?S OWNER, THE OWNER?S |
| | ARCHITECT, OR OTHER AUTHORIZED AGENT LEGALLY DESIGNATED |
| | BY THE OWNER SHALL CERTIFY THAT THE BUILDING IS IN |
| | COMPLIANCE WITH THE CODE, AS PER SECTION 553.907, |
| | FLORIDA STATUTES, PRIOR TO RECEIVING THE PERMIT TO |
| | BEGIN CONSTRUCTION OR RENOVATION. |
| | - ENERGY CALCULATIONS TO BE SIGNED BY APPROPRIATE PARTY |
| | AS OUTLINED IN C103.1.1.2. |
| | |
| | 5) C103.3 ENERGY CALCULATIONS. |
| | - VERIFY PROJECT DATA ON ENERGY CALCULATIONS PAGE 2. |
| | CONDITIONED AREA AND NON CONDITIONED AREA ARE THE SAME, |
| | THE NUMBER OF STORIES SHOWS 1. |
| | |
| | 6) C103.3 ENERGY CALCULATIONS. |
| | - UNDER SECTION FOR DOORS THERE ARE NO ENTRIES FOR THE |
| | DOORS. DOORS SHOULD BE INCLUDED WITH THE OVERHANGS |
| | PROVIDED. |
| | |
| | 7) C103.2 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | - DRAWINGS SHOULD SHOW DESIGN R-VALUE AT ROOF |
| | ESTABLISHED BY ENERGY CALCULATIONS. THEY STATE R-30. |
| | |
| | 9) C103.2 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | - DRAWINGS SHOULD SHOW DESIGN R-VALUE AT WALL THERMAL |
| | ENVELOPE ESTABLISHED BY ENERGY CALCULATIONS. THEY STATE |
| | R-13. PROVIDE CUT SHEET TO SHOW RIDIG BOARD PANEL THAT |
| | CAN PROVIDE R VALUE NEEDED AFTER ALL OTHER ENVELOPE |
| | COMPONANTS ARE INCLUDED. |
| | |
| | 10) GENERAL COMMENT |
| | - IF POSSIBLE CAN THE DOTTED GRIDLINES BE TURNED OFF |
| | FOR FLOOR PLANS ON SHEETA2.1 AND A2.2. THIS IS JUST A |
| | REQUEST TO MAKE DRAWINGS MORE READABLE. WITH FIRE WALLS |
| | USING DASH DOT LINE TYPE IT WOULD HELP CLARIFY THE |
| | SEPARATIONS. |
| | |
| | FAIRHOUSING REVIEW BEGIN: COMMENTS 11-24 |
| | GENERAL COMMENT |
| | - IT LOOKS LIKE FLORIDA ACCESSIBLITY CODE WAS APPLIED |
| | TO THIS PROJECT INSTEAD OF FAIRHOUSING GUIDELINES. THE |
| | COMMON AREAS USING FLORIDA ACCESSIBILITY WOULD MEET OR |
| | EXCEED FAIRHOUSING GUIDELINES, BUT THE RESIDENT ROOMS |
| | WILL FALL SHORT OF MEETING REQUIREMENTS 6 AND 7 BECAUSE |
| | THEY APPLY TO ALL ROOMS. WITH FAIRHOUSING BEING APPLIED |
| | THE ADA SUITES WOULD NOT NEED TO BE PROVIDED, BUT THE |
| | FOLLOWING FAIRHOUSING REQUIREMENTS WOULD APPLY TO ALL |
| | DWELLING UNITS. |
| | |
| | 11) 1986 ANSI [A117.1] IF A DESIGNER OR BUILDER CHOOSES |
| | TO FOLLOW AN ACCESSIBILITY STANDARD OTHER THAN THE 1986 |
| | ANSI A117.1 STANDARD, OR A MORE RECENT VERSION OF THE |
| | ANSI A117.1, SUCH AS THE 1992 CABO/ANSI, THAT CARE BE |
| | TAKEN TO ENSURE THE STANDARD USED IS AT LEAST |
| | EQUIVALENT TO OR STRICTER THAN THE 1986 ANSI A117.1 |
| | STANDARD. |
| | - WHAT STANDARD IS BEING APPLIED FOR COMPLIANCE WITH |
| | FAIR HOUSING? YOU CAN USE GUIDELINES THAT FALL WITHIN |
| | THE SAFE HARBOR FOR COMPLIANCE? |
| | |
| | 12) REQUIREMENT 1 - PROVIDE AT LEAST ONE ACCESSIBLE |
| | ROUTE TO BUILDING ENTERANCE. WALKS THAT ARE PART OF |
| | ACCESSIBLE ROUTES BECOME RAMPS WHEN THEIR SLOPE EXCEEDS |
| | 5% (1 IN 20). HANDRAILS ARE NOT REQUIRED ON WALKS WITH |
| | SLOPES BETWEEN 0% AND 5%, BUT THEY ARE REQUIRED ON |
| | THOSE STEEPER THAN 5% AND UP TO 8.33% (1 IN 12) |
| | - PROVIDE CIVIL PLANS TO VERIFY SLOPES THAT WILL OCCUR |
| | ON THE ACCESSIBLE PATH. PROVIDE SITE PLAN TO SHOW THE |
| | ACCESSIBLE PATH FROM PARKING OR OTHER PUBLIC ACCESS |
| | POINTS SUCH AS BUS STOP OR DROP OFF ZONE. |
| | |
| | 13) REQUIREMENT 1 - PARKING |
| | - PROVIDE SITE PLAN WITH PARKING, IF PROVIDED, REVIEW |
| | OF PARKING WILL BE DONE BASED ON SITE PLAN AND |
| | GUIDELINES BEING USED FOR FAIR HOUSING. |
| | |
| | 14) REQUIREMENT 2 - ACCESSIBLE AND USABLE PUBLIC AND |
| | COMMON USE AREAS |
| | - IF AMENITIES ARE PROVIDED OUTSIDE OF BUILDING FOR THE |
| | USERS OF THIS BUILDING, THEN PLEASE SHOW ACCESSIBLE |
| | PATHS TO THE AMENITIES. |
| | |
| | 15) IS THERE A MAILROOM? |
| | - IF SO PLEASE SHOW HOW REACH RANGES ARE ACHIEVED FOR |
| | MAILBOXES. |
| | |
| | 16) REQUIREMENT 3 - USABLE DOORS. THE DOORS IN COMMON |
| | SPACES AND THE SIDE ENTERING INTO DWELLING UNITS NEED |
| | TO HAVE USABLE HARDWARE THAT CAN BE USED WITHOUT TIGHT |
| | GRASPING OR TWISTING. |
| | - TYPICALLY THE HARDWARE WOULD BE A LEVER TYPE. THIS |
| | TYPE OF HARDWARE WOULD NOT BE REQUIRED ONCE INSIDE THE |
| | UNIT. YOU MAY WANT TO CLARIFY HARDWARE ON THE DOOR |
| | SCHEDULE. |
| | |
| | 17) ONCE INSIDE THE DWELLING UNIT HARDWARE NO LONGER |
| | APPLIES, BUT CLEAR SPACE ON ALL DOORS REQUIRE 32 INCHES |
| | NOMINAL CLEAR SPACE. |
| | - CHECK DOORS INSIDE DWELLING UNITS LABELED E, F, P, Q, |
| | V, U, EE AND FF AS THEY WOULD NOT PROVIDE THE NOMINAL |
| | CLEARANCE REQUIRED. |
| | |
| | 18) REQUIREMENT 4 - ACCESSIBLE ROUTE INTO AND THROUGH |
| | THE DWELLING UNIT. |
| | - THEY LOOK OK SINCE ALL FURNITURE IS USABLE AND IF |
| | DOORS PROVIDE 32 INCH NOMINAL THAN ACCESS WILL BE |
| | PROVIDED. ALSO, REQUIREMENT 6 WILL HELP ACHIEVE |
| | ACCESSIBLE ROUTE. |
| | |
| | 19) REQUIREMENT 5 - LIGHT SWITCHES, OUTLETS, |
| | THERMOSTATS AND OTHE CONTROLS IN ACCESSIBLE LOCATIONS. |
| | - THIS CAN BE HANDLED WITH NOTES TO STATE MAXIMUM AND |
| | MINIMUM HEIGHTS THAT COMPLY WITH THE GUIDELINES BEING |
| | FOLLOWED. THE NOTES CAN BE IN A FAIRHOUSING OVERVIEW, |
| | BUT SHOULD ALSO BE ON APPROPRIATE M OR ESHEETS SO THEY |
| | DON'T GET OVERLOOKED BY THE SPECIFIC TRADES. |
| | |
| | 20) REQUIREMENT 6 - REINFORCED WALLS FOR GRAB BARS |
| | - BARS ONLY NEED TO BE INSTALLED IN THE PUBLIC OR |
| | COMMON USE AREAS. ALL OF THE DWELLING UNITS ONLY NEED |
| | BLOCKING INSTALLED. SHEET A2.3 SHOWS THE BLOCKING AT |
| | TOILET AND WILL WORK. PLEASE ADD BLOCKING AT SHOWER |
| | BECAUSE I ONLY SEE CONTROL ZONE AND THAT WILL BE |
| | COVERED IN REQUIREMENT 7. |
| | |
| | 21) REQUIREMENT 7 - USABLE KITCHENS. |
| | - I ONLY SEE ONE KITCHEN IN UNIT S101. PLEASE SHOW |
| | CLEAR FLOOR SPACE AT COOKTOP,REFRIDGERATOR AND SINK. |
| | THE CLEAR SPACE SHOULD BE CENTERED ON THE APPLIANCE.THE |
| | SINK DOESN'T APPEAR THAT IT WOULD WORK, SO THIS MAY |
| | NEED TO BE RE-WORKED. ALSO, CHECK |
| | |
| | 22) REQUIREMENT 7 - COMMON LAUNDRY ROOMS. |
| | - SHOW CLEAR FLOOR SPACE AT WASHER AND DRYER IN LAUNDRY |
| | ROOM 118 AND LAUNDRY ROOMS ON FLOORS 2-4. THE CLEAR |
| | SPACE SHOULD BE CENTERED ON THE APPLIANCES. |
| | |
| | 23) REQUIREMENT 7 - USABLE BATHROOMS. |
| | - IN DWELLING UNITS CONTAINING MORE THAN ONE BATHROOM, |
| | IF SPECIFICATION A IS SELECTED AS THE BASIS FOR |
| | DESIGNING A BATHROOM, ALL BATHROOMS IN THE DWELLING |
| | UNIT ALSO MUST COMPLY WITH THE A SPECIFICATIONS. IF |
| | SPECIFICATION B IS SELECTED, ONLY ONE BATHROOM IN THE |
| | DWELLING UNIT MUST MEET THOSE REQUIREMENTS ALL |
| | BATHROOMS AS DEFINED IN THE GUIDELINES MUST: |
| | |
| | 24) REQUIREMENT 7 - USABLE BATHROOMS. |
| | - STATE IF THE BATHROOMS IN DWELLING UNITS ARE |
| | SPECIFICATION A OR B. COMPARTMETALIZED BATHROOMS WILL |
| | BE CONSIDERED ONE BATHROOM AND BOTH AREAS WILL NEED TO |
| | SHOW CLEAR SPACE, 32 INCH NOMINAL OPENING, SWITH/OUTLET |
| | HEIGHTS AND BLOCKING IN WALLS. SHOWERS NEED MINIMUM |
| | 30X48 AND THE SPACE NEEDS TO BE PARALLEL TO THE FIXTURE |
| | AND FLUSH WITH THE CONTROL WALL. CLEAR SPACE AT SINKS |
| | NEEDS TO BE CENTERED WITH FIXTURE. |
| | |
| | FAIRHOUSING REVIEW END |
| | |
| | 25) 1606.2 FBC[B] DESIGN DEAD LOAD. FOR PURPOSES OF |
| | DESIGN, THE ACTUAL WEIGHTS OF MATERIALS OF CONSTRUCTION |
| | AND FIXED SERVICE EQUIPMENT SHALL BE USED. IN THE |
| | ABSENCE OF DEFINITE INFORMATION, VALUES USED SHALL BE |
| | SUBJECT TO THE APPROVAL OF THE BUILDING OFFICIAL. |
| | - PLEASE PROVIDE DEAD LOAD DATA. STRUCTURAL CALCULATION |
| | S WERE REQUESTED IN OTHER COMMENT, SO NO RESPONSE |
| | NEEDED IF THEY ARE BEING SUPPLIED IN THE SUPPORTING |
| | DOCUMENTS FOLDER. |
| | |
| | 26) 1604.3.1 FBC[B] DEFLECTIONS. THE DEFLECTIONS OF |
| | STRUCTURAL MEMBERS SHALL NOT EXCEED THE MORE |
| | RESTRICTIVE OF THE LIMITATIONS OF SECTIONS 1604.3.2 |
| | THROUGH 1604.3.5 OR THAT PERMITTED BY TABLE 1604.3. |
| | - ARE THERE STRUCTURAL CALCULATIONS THAT SHOW |
| | DEFLECTIONS. IF SO PLEASE UPLOAD THEM TO SUPPORTING |
| | DOCUMENTS, OR INDICATE WHERE THE PLANS HAVE DEFLECTION |
| | LIMITS. |
| | |
| | 27) |
| | 28) |
| | 29) |
| | 30) |
| | COMMENTS 27-30 WERE A MISTKAE ON MY PART AND DO NOT |
| | APPLY. YOUR AREA, CONSTRUCTION TYPE AND SPRINKLERS TYPE |
| | WILL WORK FOR PROPOSED AREAS. |
| | |
| | 31) TABLE 1020.1 AND 708.3 EXCEPTIONS |
| | - BUILDING DATA SHEET A0.1 STATES .5 SLEEPING UNITS AND |
| | ,5 COORIDOR. THAT IS CORRECT, BUT THE LINE USED ON LIFE |
| | SAFETY PLAN MATCHES 1 HOUR DASH DOT IN TABLE. IF .5 IS |
| | BEING USED THE LINE MAY NEED TO BE CHANGED. |
| | |
| | 32) TABLE 1020.1 AND 708.3 EXCEPTIONS |
| | - VERIFY WALL TYPES ON FLOOR PLANS. SHEET A2.2 SUITES |
| | S-06 AND S-06 CALL FOR FS.2/FS. THIS TYPE DOESN'T MATCH |
| | CONDITION ON SHEET A7.1. ALSO, EXTERIOR WALLS HAVE NO |
| | WALL TYPE ASSIGNED. |
| | |
| | 33) TABLE 1020.1 AND 708.3 EXCEPTIONS |
| | - PLEASE REVIEW ALL WALL TYPES ARE AS INTENDED PER |
| | DESIGN. I ONLY SEE SOME DESCREPENCY BETWEEN WALL TYPES |
| | CALLED OUT ON A0.1, FLOOR PLANS AND GRAPHIC DEPICTIONS |
| | ON LIFE SAFETY. THEY ARE NOT NECESSARILY NON COMPLIANT. |
| | I WILL NOT COMMENT ANY WALL THAT EXCEEDS CODE ON THE |
| | NEXT REVIEW. |
| | |
| | 34) 602.1 FBC[B] WHERE REQUIRED TO HAVE A |
| | FIRERESISTANCE RATING BY TABLE 601, BUILDING ELEMENTS |
| | SHALL COMPLY WITH THE APPLICABLE PROVISIONS OF SECTION |
| | 703.2 |
| | |
| | 35) 602.1 FBC[B] EXTERIOR WALLS SHALL HAVE A |
| | FIRE-RESISTANCE RATING NOT LESS THAN THAT SPECIFIED IN |
| | TABLE 602. WHERE REQUIRED TO HAVE A FIRERESISTANCE |
| | RATING BY TABLE 601, BUILDING ELEMENTS SHALL COMPLY |
| | WITH THE APPLICABLE PROVISIONS OF SECTION 703.2. |
| | - (SEE TABLE 601 FOR FIRE-RESISTANCE RATING |
| | REQUIREMENTS) REVIEW EXTERIOR WALL FOR IIIB .THE |
| | BUILDING DATA PROVIDED ON SHEET A0.1. SHOWS ZERO HOURS |
| | EXTERIOR, BUT TABLE 601 CALLS FOR 2 HOURS. IF TABLE 602 |
| | CALLS FOR ZERO TABLE 601 STILL APPLIES. |
| | |
| | 36) 1005.1 FBC[B] GENERAL. ALL PORTIONS OF THE MEANS OF |
| | EGRESS SYSTEM SHALL BE SIZED IN ACCORDANCE WITH THIS |
| | SECTION. |
| | - SHOW OCCUPANT LOAD PER FLOOR AT 200 PER OCCUPANT AND |
| | FIRST FLOOR BASED ON THE RESIDENT AREA AND PUBLIC ARES |
| | SEPARATELY. I CALCULATE 65 AT FLOOR 4, 3 AND 2. YOU DO |
| | NOT HAVE TO ADD OCCUPANT LOAD FROM ABOVE ON EXIT STAIRS |
| | (SEE 1005.3.1 STAIRWAYS)WHERE STAIRWAYS SERVE MORE THAN |
| | ONE STORY, ONLY THE OCCUPANT LOAD OF EACH STORY |
| | CONSIDERED INDIVIDUALLY SHALL BE USED IN CALCULATING |
| | THE REQUIRED CAPACITY OF THE STAIRWAYS SERVING THAT |
| | STORY. IF YOU DO THAN LOSING ONE EXIT WOULD DECREASE |
| | YOUR REQUIRED CAPACITY BY MORE THAN HALF(1005.5) |
| | |
| | 37) 1005.1 FBC[B] GENERAL. ALL PORTIONS OF THE MEANS OF |
| | EGRESS SYSTEM SHALL BE SIZED IN ACCORDANCE WITH THIS |
| | SECTION. |
| | - THE FIRST FLOOR SHOULD BE 200 PER OCCUPANT AT |
| | DWELLING AREAS, BUT COMMON ARES MAY USE DIFFERENT |
| | NUMBER. FOR EXAMPLE BUSINESS AREA MAY BE 100. ALSO, THE |
| | COMMON AREAS (MULTI PURPOSE, EVENT, GREAT ROOM AND |
| | LOBBY) NEED TO BE ASSIGNED OCCUPANT LOADS BASED ON THE |
| | USE OF THE SPACE. CHECK DOOR SWING OF DOOR 25 BASED ON |
| | OCCUPANT LOAD IF GREATER THAN 50. |
| | |
| | 38) 1004.3 FBC[B] POSTING OF OCCUPANT LOAD. EVERY ROOM |
| | OR SPACE THAT IS AN ASSEMBLY OCCUPANCY SHALL HAVE THE |
| | OCCUPANT LOAD OF THE ROOM OR SPACE POSTED IN A |
| | CONSPICUOUS PLACE, NEAR THE MAIN EXIT OR EXIT ACCESS |
| | DOORWAY FROM THE ROOM OR SPACE. POSTED SIGNS SHALL BE |
| | OF AN APPROVED LEGIBLE PERMANENT DESIGN AND SHALL BE |
| | MAINTAINED BY THE OWNER OR THE OWNER?S AUTHORIZED |
| | AGENT. |
| | |
| | 39) 1005.7.1 FBC[B] DOORS. DOORS, WHEN FULLY OPENED, |
| | SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE THAN 7 |
| | INCHES (178 MM). DOORS IN ANY POSITION SHALL NOT REDUCE |
| | THE REQUIRED WIDTH BY MORE THAN ONE-HALF. |
| | - WITH A MINIMUM CORRIDOR WIDTH OF 44 INCHES AND DOORS |
| | SWINGING INTO THE REQUIRED WIDTH, A DIMENSION BETWEEN |
| | DOORS WOULD HELP BECAUSE IT IS VERY CLOSE TO EXCEEDING |
| | SWING ALLOWED BY 1005.7.1 |
| | |
| | 40) 1009.1 FBC[B] ACCESSIBLE MEANS OF EGRESS REQUIRED. |
| | ACCESSIBLE MEANS OF EGRESS SHALL BE PROVIDED IN |
| | ACCORDANCE WITH THE APPLICABLE SECTIONS OF THE FLORIDA |
| | BUILDING CODE, ACCESSIBILITY. |
| | - SEE FBC ACCESSIBILITY CODE |
| | |
| | 41) 207.1 FBC[A] GENERAL. MEANS OF EGRESS SHALL COMPLY |
| | WITH SECTION 1003.2.13 OF THE INTERNATIONAL BUILDING |
| | CODE (2000 EDITION AND 2001 SUPPLEMENT) OR SECTION 1007 |
| | OF THE INTERNATIONAL BUILDING CODE (2003 EDITION) |
| | (INCORPORATED BY REFERENCE, SEE ?REFERENCED STANDARDS? |
| | IN CHAPTER 1). EXCEPTIONS: |
| | - SHOW HOW ACCESSIBLE EGRESS IS ACHIEVED ON LIFE SAFETY |
| | SHEET. |
| | |
| | 42) 1011.12 FBC[B] STAIRWAY TO ROOF. IN BUILDINGS FOUR |
| | OR MORE STORIES ABOVE GRADE PLANE, ONE STAIRWAY SHALL |
| | EXTEND TO THE ROOF SURFACE UNLESS THE ROOF HAS A SLOPE |
| | STEEPER THAN FOUR UNITS VERTICAL IN 12 UNITS HORIZONTAL |
| | (33-PERCENT SLOPE). |
| | - REVIEW THIS CODE SECTION FOR COMPLIANCE BECAUSE ROOF |
| | HATCH IS PROPOSED. PROVIDE CODE SECTION THAT ALLOWS |
| | ROOF HATCH FOR A 4 STORY BUILDING. |
| | |
| | 43) 1006.2.2.1 FBC[B] BOILER, INCINERATOR AND FURNACE |
| | ROOMS. TWO EXIT ACCESS DOORWAYS ARE REQUIRED IN BOILER, |
| | INCINERATOR AND FURNACE ROOMS WHERE THE AREA IS OVER |
| | 500 SQUARE FEET (46 M2) AND ANY FUEL-FIRED EQUIPMENT |
| | EXCEEDS 400,000 BRITISH THERMAL UNITS (BTU) (422 000 |
| | KJ) INPUT CAPACITY. WHERE TWO EXIT ACCESS DOORWAYS ARE |
| | REQUIRED, ONE IS PERMITTED TO BE A FIXED LADDER OR AN |
| | ALTERNATING TREAD DEVICE. EXIT ACCESS DOORWAYS SHALL BE |
| | SEPARATED BY A HORIZONTAL DISTANCE EQUAL TO ONE HALF |
| | THE LENGTH OF THE MAXIMUM OVERALL DIAGONAL DIMENSION OF |
| | THE ROOM. |
| | - REVIEW THIS CODE SECTION AT MECHANICAL YARD FOR |
| | EXITS. |
| | |
| | 44) 1607.8.1 FBC[B] HANDRAILS AND GUARDS. HANDRAILS AND |
| | GUARDS SHALL BE DESIGNED TO RESIST A LINEAR LOAD OF 50 |
| | POUNDS PER LINEAR FOOT (PLF) (0.73 KN/M) IN ACCORDANCE |
| | WITH SECTION 4.5.1 OF ASCE 7. GLASS HANDRAIL ASSEMBLIES |
| | AND GUARDS SHALL ALSO COMPLY WITH SECTION 2407. (SEE |
| | EXCEPTIONS FOR 1607.8.1) |
| | - ADD HANDRAILS AND GUARDS TO DEFERRED SUBMITTAL LIST |
| | ON SHEET A0.1. |
| | |
| | 45) 1023.6 FBC[B] VENTILATION. EQUIPMENT AND DUCTWORK |
| | FOR INTERIOR EXIT STAIRWAY AND RAMP VENTILATION AS |
| | PERMITTED BY SECTION 1023.5 SHALL COMPLY WITH ONE OF |
| | THE FOLLOWING ITEMS: |
| | 1. SUCH EQUIPMENT AND DUCTWORK SHALL BE LOCATED |
| | EXTERIOR TO THE BUILDING AND SHALL BE DIRECTLY |
| | CONNECTED TO THE INTERIOR EXIT STAIRWAY AND RAMP BY |
| | DUCTWORK ENCLOSED IN CONSTRUCTION AS REQUIRED FOR |
| | SHAFTS. |
| | 2. WHERE SUCH EQUIPMENT AND DUCTWORK IS LOCATED WITHIN |
| | THE INTERIOR EXIT STAIRWAY AND RAMP, THE INTAKE AIR |
| | SHALL BE TAKEN DIRECTLY FROM THE OUTDOORS AND THE |
| | EXHAUST AIR SHALL BE DISCHARGED DIRECTLY TO THE |
| | OUTDOORS, OR SUCH AIR SHALL BE CONVEYED THROUGH DUCTS |
| | ENCLOSED IN CONSTRUCTION AS REQUIRED FOR SHAFTS. |
| | 3. WHERE LOCATED WITHIN THE BUILDING, SUCH EQUIPMENT |
| | AND DUCTWORK SHALL BE SEPARATED FROM THE REMAINDER OF |
| | THE BUILDING, INCLUDING OTHER MECHANICAL EQUIPMENT, |
| | WITH CONSTRUCTION AS REQUIRED FOR SHAFTS. IN EACH CASE, |
| | OPENINGS INTO THE FIRE-RESISTANCE-RATED CONSTRUCTION |
| | SHALL BE LIMITED TO THOSE NEEDED FOR MAINTENANCE AND |
| | OPERATION AND SHALL BE PROTECTED BY OPENING PROTECTIVES |
| | IN ACCORDANCE WITH SECTION 716 FOR SHAFT ENCLOSURES. |
| | THE INTERIOR EXIT STAIRWAY AND RAMP VENTILATION SYSTEMS |
| | SHALL BE INDEPENDENT OF OTHER BUILDING VENTILATION |
| | SYSTEMS. |
| | -IS THERE ANY VENTILATION PROVIDED AT ENCLOSED |
| | STAIRWAYS? |
| | |
| | 46) 1023.9 FBC[B] STAIRWAY IDENTIFICATION SIGNS. A SIGN |
| | SHALL BE PROVIDED AT EACH FLOOR LANDING IN AN INTERIOR |
| | EXIT STAIRWAY AND RAMP CONNECTING MORE THAN THREE |
| | STORIES DESIGNATING THE FLOOR LEVEL, THE TERMINUS OF |
| | THE TOP AND BOTTOM OF THE INTERIOR EXIT STAIRWAY AND |
| | RAMP AND THE IDENTIFICATION OF THE STAIRWAY OR RAMP. |
| | THE SIGNAGE SHALL ALSO STATE THE STORY OF, AND THE |
| | DIRECTION TO, THE EXIT DISCHARGE AND THE AVAILABILITY |
| | OF ROOF ACCESS FROM THE INTERIOR EXIT STAIRWAY AND RAMP |
| | FOR THE FIRE DEPARTMENT. THE SIGN SHALL BE LOCATED 5 |
| | FEET (1524 MM) ABOVE THE FLOOR LANDING IN A POSITION |
| | THAT IS READILY VISIBLE WHEN THE DOORS ARE IN THE OPEN |
| | AND CLOSED POSITIONS. IN ADDITION TO THE STAIRWAY |
| | IDENTIFICATION SIGN, A FLOOR-LEVEL SIGN IN VISUAL |
| | CHARACTERS, RAISED CHARACTERS AND BRAILLE COMPLYING |
| | WITH THE FLORIDA BUILDING CODE, ACCESSIBILITY SHALL BE |
| | LOCATED AT EACH FLOOR-LEVEL LANDING ADJACENT TO THE |
| | DOOR LEADING FROM THE INTERIOR EXIT STAIRWAY AND RAMP |
| | INTO THE CORRIDOR TO IDENTIFY THE FLOOR LEVEL. |
| | |
| | 47) 1023.9.1 FBC[B] SIGNAGE REQUIREMENTS. STAIRWAY |
| | IDENTIFICATION SIGNS SHALL COMPLY WITH ALL OF THE |
| | FOLLOWING REQUIREMENTS: |
| | |
| | 48) 1030.1 FBC[B] GENERAL. IN ADDITION TO THE MEANS OF |
| | EGRESS REQUIRED BY THIS CHAPTER, PROVISIONS SHALL BE |
| | MADE FOR EMERGENCY ESCAPE AND RESCUE OPENINGS IN GROUP |
| | R-2 OCCUPANCIES IN ACCORDANCE WITH TABLES 1006.3.2(1) |
| | AND 1006.3.2(2). |
| | - HOW ARE PROVISIONS OF THIS SECTION BEING PROVIDED |
| | FOR. I DON?T SEE A WINDOW SCHEDULE FOR THIS PROJECT. |
| | ARE THE WINDOWS OPERABLE? PLEASE PROVIDE WINDOW |
| | SCHEDULE, OR INDICATE WHERE I CAN FIND THIS INFORMATION |
| | ON THE PLANS. SHEET A0.1 MENTIONS NO FIRE ESCAPE |
| | WINDOWS DUE TO SPRINKLER PROVIDED. IF THERE IS |
| | EXCEPTION TO 1030.1 PLEASE PROVIDE THE APPLICABLE CODE |
| | SECTION FOR 2ND REVIEW. |
| | |
| | 49) 705.8.1 FBC[B] ALLOWABLE AREA OF OPENINGS. THE |
| | MAXIMUM AREA OF UNPROTECTED AND PROTECTED OPENINGS |
| | PERMITTED IN AN EXTERIOR WALL IN ANY STORY OF A |
| | BUILDING SHALL NOT EXCEED THE PERCENTAGES SPECIFIED IN |
| | TABLE 705.8. |
| | - (SEE TABLE 705.8) THIS WILL BE REVIEWED ONCE A SITE |
| | PLAN WITH SEPARATION DISTANCES IS PROVIDED. |
| | |
| | 50) 705.8 TABLE FBC[B] MAXIMUM AREA OF EXTERIOR WALL |
| | OPENINGS BASED ON FIRE SEPARATION DISTANCE AND DEGREE |
| | OF OPENING PROTECTION |
| | - (SEE TABLE 705.8 FOR ALLOWABLE AMOUNTS OF OPENINGS) |
| | |
| | 51) 705.8 TABLE FBC[B] MAXIMUM AREA OF EXTERIOR WALL |
| | OPENINGS BASED ON FIRE SEPARATION DISTANCE AND DEGREE |
| | OF OPENING PROTECTION |
| | |
| | 52) 713.13.4 FBC[B] CHUTE DISCHARGE ROOM. WASTE OR |
| | LINEN CHUTES SHALL DISCHARGE INTO AN ENCLOSED ROOM |
| | SEPARATED BY FIRE BARRIERS WITH A FIRE-RESISTANCE |
| | RATING NOT LESS THAN THE REQUIRED FIRE RATING OF THE |
| | SHAFT ENCLOSURE AND CONSTRUCTED IN ACCORDANCE WITH |
| | SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED IN |
| | ACCORDANCE WITH SECTION 711, OR BOTH. OPENINGS INTO THE |
| | DISCHARGE ROOM FROM THE REMAINDER OF THE BUILDING SHALL |
| | BE PROTECTED BY OPENING PROTECTIVES HAVING A FIRE |
| | PROTECTION RATING EQUAL TO THE PROTECTION REQUIRED FOR |
| | THE SHAFT ENCLOSURE. DOORS SHALL BE SELF- OR |
| | AUTOMATICCLOSING UPON THE DETECTION OF SMOKE IN |
| | ACCORDANCE WITH SECTION 716.5.9.3. WASTE CHUTES SHALL |
| | NOT TERMINATE IN AN INCINERATOR ROOM. WASTE AND LINEN |
| | ROOMS THAT ARE NOT PROVIDED WITH CHUTES NEED ONLY |
| | COMPLY WITH TABLE 509. |
| | - PLEASE CHECK DOOR 20 TO MEET THE REQUIRED PROTECTION |
| | RATING EQUAL TO THE SHAFT ENCLOSURE. |
| | |
| | 53) 714.4 FBC[B] HORIZONTAL ASSEMBLIES. PENETRATIONS OF |
| | A FIRE-RESISTANCE- RATED FLOOR, FLOOR/CEILING ASSEMBLY |
| | OR THE CEILING MEMBRANE OF A ROOF/CEILING ASSEMBLY NOT |
| | REQUIRED TO BE ENCLOSED IN A SHAFT BY SECTION 712.1 |
| | SHALL BE PROTECTED IN ACCORDANCE WITH SECTIONS 714.4.1 |
| | THROUGH 714.4.4. 714.4.1 THROUGH PENETRATIONS. THROUGH |
| | PENETRATIONS OF HORIZONTAL ASSEMBLIES SHALL COMPLY WITH |
| | SECTION 714.4.1.1 OR 714.4.1.2. EXCEPTIONS: |
| | 1. PENETRATIONS BY STEEL, FERROUS OR COPPER CONDUITS, |
| | PIPES, TUBES OR VENTS OR CONCRETE OR MASONRY ITEMS |
| | THROUGH A SINGLE FIRE-RESISTANCE- RATED FLOOR ASSEMBLY |
| | WHERE THE ANNULAR SPACE IS PROTECTED WITH MATERIALS |
| | THAT PREVENT THE PASSAGE OF FLAME AND HOT GASES |
| | SUFFICIENT TO IGNITE COTTON WASTE WHEN SUBJECTED TO |
| | ASTM E119 OR UL 263 TIME-TEMPERATURE FIRE CONDITIONS |
| | UNDER A MINIMUM POSITIVE PRESSURE DIFFERENTIAL OF 0.01 |
| | INCH (2.49 PA) OF WATER AT THE LOCATION OF THE |
| | PENETRATION FOR THE TIME PERIOD EQUIVALENT TO THE |
| | FIRE-RESISTANCE RATING OF THE CONSTRUCTION PENETRATED. |
| | PENETRATING ITEMS WITH A MAXIMUM 6-INCH (152 MM) |
| | NOMINAL DIAMETER SHALL NOT BE LIMITED TO THE |
| | PENETRATION OF A SINGLE FIRE-RESISTANCE-RATED FLOOR |
| | ASSEMBLY, PROVIDED THE AGGREGATE AREA OF THE OPENINGS |
| | THROUGH THE ASSEMBLY DOES NOT EXCEED 144 SQUARE INCHES |
| | (92 900 MM2) IN ANY 100 SQUARE FEET (9.3 M2) OF FLOOR |
| | AREA. |
| | 2. PENETRATIONS IN A SINGLE CONCRETE FLOOR BY STEEL, |
| | FERROUS OR COPPER CONDUITS, PIPES, TUBES OR VENTS WITH |
| | A MAXIMUM 6-INCH (152 MM) NOMINAL DIAMETER, PROVIDED |
| | THE CONCRETE, GROUT OR MORTAR IS INSTALLED THE FULL |
| | THICKNESS OF THE FLOOR OR THE THICKNESS REQUIRED TO |
| | MAINTAIN THE FIRE-RESISTANCE RATING. THE PENETRATING |
| | ITEMS SHALL NOT BE LIMITED TO THE PENETRATION OF A |
| | SINGLE CONCRETE FLOOR, PROVIDED THE AREA OF THE OPENING |
| | THROUGH EACH FLOOR DOES NOT EXCEED 144 SQUARE INCHES |
| | (92 900 MM2). |
| | 3. PENETRATIONS BY LISTED ELECTRICAL BOXES OF ANY |
| | MATERIAL, PROVIDED SUCH BOXES HAVE BEEN TESTED FOR USE |
| | IN FIRE-RESISTANCE-RATED ASSEMBLIES AND INSTALLED IN |
| | ACCORDANCE WITH THE INSTRUCTIONS INCLUDED IN THE |
| | LISTING. |
| | - SHEETS A7.1 AND 7.2 DO NOT MENTION HOW CEILING |
| | PENETRATIONS ARE HANDLED. 420.3 HORIZONTAL SEPARATION |
| | OF DWELLING UNIT FLOORS TO BE HORIZONTAL ASSEMBLIES |
| | WITH SECTION 711. |
| | |
| | |
| | 54) 714.4.2 FBC[B] MEMBRANE PENETRATIONS. PENETRATIONS |
| | OF MEMBRANES THAT ARE PART OF A HORIZONTAL ASSEMBLY |
| | SHALL COMPLY WITH SECTION 714.4.1.1 OR 714.4.1.2. WHERE |
| | FLOOR/CEILING ASSEMBLIES ARE REQUIRED TO HAVE A |
| | FIRE-RESISTANCE RATING, RECESSED FIXTURES SHALL BE |
| | INSTALLED SUCH THAT THE REQUIRED FIRE RESISTANCE WILL |
| | NOT BE REDUCED. |
| | - (SEE 714.4.2 FOR EXCEPTIONS) |
| | |
| | 55) 715.1 FBC[B] GENERAL. JOINTS INSTALLED IN OR |
| | BETWEEN FIRE-RESISTANCE RATED WALLS, FLOOR OR |
| | FLOOR/CEILING ASSEMBLIES AND ROOFS OR ROOF/CEILING |
| | ASSEMBLIES SHALL BE PROTECTED BY AN APPROVED |
| | FIRE-RESISTANT JOINT SYSTEM DESIGNED TO RESIST THE |
| | PASSAGE OF FIRE FOR A TIME PERIOD NOT LESS THAN THE |
| | REQUIRED FIRE-RESISTANCE RATING OF THE WALL, FLOOR OR |
| | ROOF IN OR BETWEEN WHICH THE SYSTEM IS INSTALLED. |
| | FIRE-RESISTANT JOINT SYSTEMS SHALL BE TESTED IN |
| | ACCORDANCE WITH SECTION 715.3. |
| | - COMMENT IS FOR HORIZONTAL FLOOR ASSEMBLIES |
| | |
| | 56) 716.5 FBC TABLE[B] OPENING FIRE PROTECTION |
| | ASSEMBLIES, RATINGS AND MARKINGS |
| | - IF FIRE PARTITIONS ARE .5 HOURS AS STATED ON A0.1 |
| | DOORS WOULD ONLY REQUIRE 1/3 HOUR RATING MINIMUM. THIS |
| | IS GENERAL COMMENT AND NO RESPONSE IS REQUIRED. |
| | |
| | 57) 107.2.5 FBC[AMENDED] PROVIDE SURVEY OF PROPERTY |
| | SHOWING EASEMENTS AND DISTANCE FROM PROPERTY LINES TO |
| | NEW STRUCTURE. SURVEY TO INCLUDE SLAB ELEVATION AND |
| | SHOW POSITIVE DRAINAGE FROM FOUNDATION. |
| | - 107.2.5 FBC[AMENDED](FL. STATUTE 472.025)SURVEY TO BE |
| | SIGNED AND SEALED BY THE SURVEYOR OF RECORD. |
| | |
| | 58) 401.4 FBC[R] PROVIDE SOIL REPORT TO SHOW BEARING |
| | CAPACITY AND FOUNDATION RECOMMENDATIONS. |
| | - THIS CAN BE ADDED TO SUPPORTING DOCUMENTS AS MULTI |
| | PAGE PDF. |
| | |
| | 59) 107.3.5.3 FBC[AMENDED] PROVIDE SEDIMENT CONTROL TO |
| | KEEP CONSTRUCTION DEBRIS FROM ENTERING ADJACENT |
| | PROPERTIES AND STORM DRAINS DURING CONSTRUCTION. YOU |
| | CAN JUST ADD SILT FENCE DETAIL AND HOW DRAINS ARE |
| | PROTECTED TO THE DRAINAGE PLAN. SOME ENGINEERING |
| | STANDARD DETAILS CAN BE USED FROM WPB WEBSITE-POLLUTION |
| | CONTROL. HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUB |
| | LIC-WORKS/FORMS,-PERMITS-APPLICATIONS |
| | - PROVIDE CIVIL PLANS THAT SHOW DRAINAGE AND ELEVATIONS |
| | RELEVANT TO PARKING, BUILDING ENTRY AND ACCESSIBLE |
| | PATH. |
| | |
| | 60) 1804.6 FBC[B] COMPACTED FILL MATERIAL. WHERE |
| | SHALLOW FOUNDATIONS WILL BEAR ON COMPACTED FILL |
| | MATERIAL, THE COMPACTED FILL SHALL COMPLY WITH THE |
| | PROVISIONS OF AN APPROVED GEOTECHNICAL REPORT, AS SET |
| | FORTH IN SECTION 1803. EXCEPTION: COMPACTED FILL |
| | MATERIAL 12 INCHES (305 MM) IN DEPTH OR LESS NEED NOT |
| | COMPLY WITH AN APPROVED REPORT, PROVIDED THE IN-PLACE |
| | DRY DENSITY IS NOT LESS THAN 90 PERCENT OF THE MAXIMUM |
| | DRY DENSITY AT OPTIMUM MOISTURE CONTENT DETERMINED IN |
| | ACCORDANCE WITH ASTM D1557. |
| | - THIS WILL BE VERIFIED WITH CIVIL PLANS AND |
| | GEOTECHNICAL REPORT THAT HAVE BEEN REQUESTED IN THIS |
| | REVIEW. |
| | |
| | 61) 1603.1.4 FBC[B] WIND DESIGN DATA. THE FOLLOWING |
| | INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN, |
| | REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF |
| | THE LATERAL FORCERESISTING SYSTEM OF THE STRUCTURE: |
| | |
| | 62) 3002.1.2 FBC[B] HARDWARE. HARDWARE ON OPENING |
| | PROTECTIVES SHALL BE OF AN APPROVED TYPE INSTALLED AS |
| | TESTED, EXCEPT THAT APPROVED INTERLOCKS, MECHANICAL |
| | LOCKS AND ELECTRIC CONTACTS, DOOR AND GATE ELECTRIC |
| | CONTACTS AND DOOR-OPERATING MECHANISMS SHALL BE EXEMPT |
| | FROM THE FIRE TEST REQUIREMENTS. 3002.2 NUMBER OF |
| | ELEVATOR CARS IN A HOISTWAY. WHERE FOUR OR MORE |
| | ELEVATOR CARS SERVE ALL OR THE SAME PORTION OF A |
| | BUILDING, THE ELEVATORS SHALL BE LOCATED IN NOT FEWER |
| | THAN TWO SEPARATE HOISTWAYS. NOT MORE THAN FOUR |
| | ELEVATOR CARS SHALL BE LOCATED IN ANY SINGLE HOISTWAY |
| | ENCLOSURE. |
| | |
| | 63) 3002.3 FBC[B] EMERGENCY SIGNS. AN APPROVED |
| | PICTORIAL SIGN OF A STANDARDIZED DESIGN SHALL BE POSTED |
| | ADJACENT TO EACH ELEVATOR CALL STATION ON ALL FLOORS |
| | INSTRUCTING OCCUPANTS TO USE THE EXIT STAIRWAYS AND NOT |
| | TO USE THE ELEVATORS IN CASE OF FIRE. THE SIGN SHALL |
| | READ: IN CASE OF FIRE, ELEVATORS ARE OUT OF SERVICE. |
| | USE EXIT STAIRS. EXCEPTIONS: (SEE 3002.3 FOR |
| | EXCEPTIONS) |
| | |
| | 64) 3002.4 FBC[B] ELEVATOR CAR TO ACCOMMODATE AMBULANCE |
| | STRETCHER. ANY BUILDING THAT IS MORE THAN THREE STORIES |
| | HIGH OR IN WHICH THE VERTICAL DISTANCE BETWEEN THE |
| | BOTTOM TERMINAL LANDING AND THE TOP TERMINAL LANDING |
| | EXCEEDS 25 FEET (7620 MM), MUST BE CONSTRUCTED TO |
| | CONTAIN AT LEAST ONE PASSENGER ELEVATOR THAT IS |
| | OPERATIONAL FOR BUILDING OCCUPANTS AND FIRE DEPARTMENT |
| | EMERGENCY ACCESS TO ALL FLOORS. THE ELEVATOR CAR SHALL |
| | BE OF SUCH A SIZE AND ARRANGEMENT TO ACCOMMODATE AN |
| | AMBULANCE STRETCHER 24 INCHES BY 76 INCHES (610 MM BY |
| | 1950 MM) WITH NOT LESS THAN 5-INCH (127 MM) RADIUS |
| | CORNERS, IN THE HORIZONTAL, OPEN POSITION AND SHALL BE |
| | IDENTIFIED BY THE INTERNATIONAL SYMBOL FOR EMERGENCY |
| | MEDICAL SERVICES (STAR OF LIFE). THE SYMBOL SHALL BE |
| | NOT LESS THAN 3 INCHES (76 MM) IN HEIGHT AND SHALL BE |
| | PLACED INSIDE ON BOTH SIDES OF THE HOISTWAY DOOR FRAME. |
| | - SHOW HOW STRECHER WILL FIT IN ONE OF THE ELEVATORS. A |
| | GRAPHIC REPRESENTAION OF 24X74 INCH RECTANGLE WITH |
| | MAXIMUM 5 INCH RADIUS CORNERS FROM ENTRY TO FINAL |
| | POSITION ON PLAN VIEW WILL HELP CLARIFY THAT THIS |
| | REQUIREMENT IS MET. |
| | |
| | 65) 2207.5 FBC[B] CERTIFICATION. AT COMPLETION OF |
| | MANUFACTURE, THE STEEL JOIST MANUFACTURER SHALL SUBMIT |
| | A CERTIFICATE OF COMPLIANCE TO THE OWNER OR THE OWNER?S |
| | AUTHORIZED AGENT FOR SUBMITTAL TO THE BUILDING OFFICIAL |
| | AS SPECIFIED IN SECTION 1704.5 STATING THAT WORK WAS |
| | PERFORMED IN ACCORDANCE WITH APPROVED CONSTRUCTION |
| | DOCUMENTS AND WITH SJI SPECIFICATIONS LISTED IN SECTION |
| | 2207.1 |
| | - ADD TO DEFFERED SUBMITTAL L;IST |
| | |
| | 66) 1504.3 FBC[B] WIND RESISTANCE OF NONBALLASTED |
| | ROOFS. ROOF COVERINGS INSTALLED ON ROOFS IN ACCORDANCE |
| | WITH SECTION 1507 THAT ARE MECHANICALLY ATTACHED OR |
| | ADHERED TO THE ROOF DECK SHALL BE DESIGNED TO RESIST |
| | THE DESIGN WIND LOAD PRESSURES FOR COMPONENTS AND |
| | CLADDING IN ACCORDANCE WITH SECTION 1609. |
| | - ROOF PRODUCT APPROVAL 14083. PLEASE ADD THE 5 PAGE |
| | EVALUATION REPORT TO THE PRODUCT APPROVAL, AS STATED IN |
| | THE EVALUATION REPORT 5.7 THE INSULATION AND INSULATION |
| | ATTACHMENT NEEDS TO BE PART OF THE ROOFING SUBMITTAL. |
| | ALSO, SELECT THE SYSTEM BEING USED ON FL14803, OR ONLY |
| | PROVIDE THE SHEETS FOR THE SYSTEM BEING INSTALLED. |
| | |
| | THE ROOFING SUBMITTAL CAN BE DEFERRED SUBMITTAL IF THE |
| | FULL SUBMITTAL IS NOT READY YET. |
| | - IF THE SUBMITTAL ID TO BE DEFERRED, ADD IT TO THE |
| | LIST ON SHEET A0.1. |
| | |
| | 67) FL 16554 AND FL 14218 FOR STOREFRONT. |
| | - PLEASE SELECT THE SYSTEMS BEING USED AS MORE THAN ONE |
| | OPTION IS SHOWN ON SUMMARY OF PRODUCTS |
| | |
| | 68) 107.3.4.1 FBC[AMENDED] DEFERRED SUBMITTALS. FOR THE |
| | PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE |
| | DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| | SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE |
| | TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| | - PLEASE ADD ANY ADDITIONAL DEFERRED SUBMITTALS TO THE |
| | LIST ON SHEET A0.1. AIPP COMPLIANCE REQUIRED; |
| | VERIFICATION REQUIRED PRIOR TO C.O., SHORING AND |
| | RE-SHORING(IF APPLICABLE), TILT UP TEMPORARY BRACING BY |
| | ENGINEER, ROOM DIVIDER IN EVENT ROOM, HANDRAILS AND |
| | GUARDRAILS, FLOOR UNDERLAYMENT/SOUNDPROOFING AND WASTE |
| | CHUTE ACCESS DOOR (713.13.1) |
| | |
| | 69) PLEASE ADVISE ,VIA EMAIL, WHAT FLOORING AND |
| | UNDERLAYMENT ARE PROPOSED? IF THE UNDERLAYMENT PRODUCT |
| | PROPOSED IS NOT ONE FOR WHICH WE HAVE TEST REPORTS ON |
| | FILE, THE FOLLOWING REPORTS WILL BE REQUIRED: |
| | - THIS APPLIES TO FLOORING IN DWELLINGS ON FLOORS 2-4 |
| | |
| | 1207.2 FBC[B] AIR-BORNE SOUND. WALLS, PARTITIONS AND |
| | FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS AND |
| | SLEEPING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS OF |
| | NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED, |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E90. |
| | |
| | 1207.3 FBC[B] STRUCTURE-BORNE SOUND. FLOOR/CEILING |
| | ASSEMBLIES BETWEEN DWELLING UNITS AND SLEEPING UNITS OR |
| | BETWEEN A DWELLING UNIT OR SLEEPING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS RATING OF NOT LESS THAN 50, OR |
| | NOT LESS THAN 45 IF FIELD TESTED, WHEN TESTED IN |
| | ACCORDANCE WITH ASTM E492. |
| | |
| | 603.1 FBC[B] ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. |
| | - IF FLOORING IS TO BE A DEFERRED SUBMITTAL, ADD IT TO |
| | THE LIST ON SHEET A0.1. |
| | |
| | 70) 804.1 FBC[B] GENERAL. INTERIOR FLOOR FINISH AND |
| | FLOOR COVERING MATERIALS SHALL COMPLY WITH SECTIONS |
| | 804.2 THROUGH 804.4.2. EXCEPTION: FLOOR FINISHES AND |
| | COVERINGS OF A TRADITIONAL TYPE, SUCH AS WOOD, VINYL, |
| | LINOLEUM OR TERRAZZO, AND RESILIENT FLOOR COVERING |
| | MATERIALS THAT ARE NOT COMPRISED OF FIBERS. |
| | |
| | NOTES: |
| | |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | |
| | -COMMENTS ARE A BRIEF OVERVIEW OF CODE SECTIONS. |
| | FURTHER REVIEW OF THE REFERENCED CODE SECTIONS WILL BE |
| | REQUIRED. |
| | |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |