2019-03-13 09:38:46PERMIT # 19030140
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED PROVISO:
  
 1) A COPY OF THE PLANS SHALL BE ON-SITE AND READILY
 AVAILABLE UPON FIRE INSPECTOR'S REQUEST.
  
 2) PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 3) FOOD VENDOR TENTS: PROVIDE TYPE K EXTINGUISHERS WHEN
 COOKING WITH GREASE OR WHEN PRODUCING SMOKE OR
 GREASE-LADEN VAPORS.
  
 4) TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM
 BUILDING STRUCTURES.
  
 5) TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE,
 OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS
 ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET.
  
 6) POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
 LOCATIONS.
  
 7) GENERATORS AND OTHER INTERNAL COMBUSTION POWER
 SOURCES SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5
 FEET AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR
 ENCLOSURE.
  
 8) TENTS WITH SEATING AREAS (TABLES/CHAIRS) SHALL HAVE
 THE SEATING ARRANGED IN A MANNER THAT COMPLIES WITH THE
 AISLE AND AISLEWAY REQUIREMENTS AS LISTED UNDER NFPA
 101: 12.2.5 (ARRANGEMENT OF MEANS OF EGRESS).
  
 9) ALL ASSEMBLY TENTS (COCKTAIL TENTS, BAR LOUNGES,
 DINING TENTS, ETC.), SHALL COMPLY WITH THE OCCUPANT
 LOAD FACTOR AS LISTED UNDER NFPA 101: CHAPTER 7, TABLE
 7.3.1.2. MORE SPECIFICALLY, ASSEMBLY USE: LESS
 CONCENTRATED USE, WITHOUT FIXED SEATING - 15 SQ
 FT/PERSON.
  
 10) A FIRE INSPECTION WILL BE CONDUCTED PRIOR TO START
 OF EVENT TO ENSURE COMPLIANCE WITH ALL APPLICABLE
 CODES.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  
  