| Plan Review Notes For Permit 19030087 |
| Permit Number |
19030087 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-04-10 12:09:15 | PERMIT #19030087 | | | FIRE REVIEW COMMENTS: | | | | | | 1) PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE | | | OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS. | | | | | | 2) TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE, | | | OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS | | | ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET. | | | | | | 3) POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS | | | LOCATIONS. | | | | | | 4) IF APPLICABLE, GENERATORS AND OTHER INTERNAL | | | COMBUSTION POWER SOURCES SHALL BE SEPARATED FROM TENTS | | | BY A MINIMUM OF 5 FEET AND SHALL BE PROTECTED FROM | | | CONTACT BY FENCING OR ENCLOSURE. | | | | | | SUE ELLEN CALDERON | | | ASST. FIRE MARSHAL | | | [email protected] | | | | | | |
|