| 2019-03-06 10:35:04 | PERMIT #19030087 | | | FIRE REVIEW COMMENTS: | | | | | | 1) APPLICATION STATES THAT TENTS ARE OF "VARIOUS | | | SIZES". THE TENT DIAGRAM PROVIDED STATES 10' X 20'. THE | | | SITE PLAN SHOWS WHAT MAY BE 40 OR MORE TENTS VARYING IN | | | SIZE. PLEASE SPECIFY THE SIZES AND LOCATIONS OF EACH | | | TENT. | | | | | | 2) PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE | | | OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS. | | | | | | 3) TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE, | | | OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS | | | ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET. | | | | | | 4) POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS | | | LOCATIONS. | | | | | | 5) IF APPLICABLE, GENERATORS AND OTHER INTERNAL | | | COMBUSTION POWER SOURCES SHALL BE SEPARATED FROM TENTS | | | BY A MINIMUM OF 5 FEET AND SHALL BE PROTECTED FROM | | | CONTACT BY FENCING OR ENCLOSURE. | | | | | | SUE ELLEN CALDERON | | | ASST. FIRE MARSHAL | | | [email protected] | | | | | | |
|