| Notes |
| Date |
Text |
| 2019-03-05 10:10:26 | | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SPECIFY THE SYSTEM TYPE AND FASTENING OPTION THAT | | | WILL BE USED TO ATTACH THE TPO ON THE FLAT ROOF. FBC | | | 107.2.1 | | | | | | 2) IF THE MAXIMUM DESIGN PRESSURE FOR THE FASTENING | | | OPTION IS LESS THAN -63.6 PSF AT THE PERIMETER (ROOF | | | ZONE 2) AND -95.7 PSF AT THE CORNERS (ROOF ZONE 3), | | | THEN SUBMIT SIGNED AND SEALED RAS 117 CALCULATIONS PER | | | GENERAL LIMITATION #7 ON PAGE 24. FBC 107.2.1.1 & | | | 107.2.1.2 |
|