2019-03-05 10:10:26 
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY THE SYSTEM TYPE AND FASTENING OPTION THAT
 WILL BE USED TO ATTACH THE TPO ON THE FLAT ROOF. FBC
 107.2.1
  
 2) IF THE MAXIMUM DESIGN PRESSURE FOR THE FASTENING
 OPTION IS LESS THAN -63.6 PSF AT THE PERIMETER (ROOF
 ZONE 2) AND -95.7 PSF AT THE CORNERS (ROOF ZONE 3),
 THEN SUBMIT SIGNED AND SEALED RAS 117 CALCULATIONS PER
 GENERAL LIMITATION #7 ON PAGE 24. FBC 107.2.1.1 &
 107.2.1.2