| Date |
Text |
| 2019-07-02 08:48:49 | 3RD SIGNATURE REVIEW BY CHRISTOPHER L. COLE |
| | PERMIT #19030060 |
| | 7/2/19 |
| | |
| | 1) THE FOLLOWING LIST OF MECHANICAL PLANS DO NOT HAVE |
| | VALID ELECTRONIC SIGNATURES AND SEALS: M101, M102, |
| | M103, M104, M701, DM101, DM102, DM103, DM104. |
| | THE DIGITALLY SIGNED PLANS SHALL ALSO BEAR THIS |
| | STATEMENT IN ACCORDANCE WITH SECTION 61G15-23.005- |
| | "THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY |
| | _________ON DATE________USING A SHA-1 AUTHENTICATION |
| | CODE." THE CURRENT MECHANICAL PLANS INDICATE THEY ARE |
| | SIGNED ONLY. IN ADDITION ENGINEERS MAY NOT SELF-CERTIFY |
| | ELECTRONIC SIGNATURES AND SEALS. CERTIFICATION SHALL BE |
| | BY A THIRD-PARTY AGENCY. |
| | |
| | 2) FOR ELECTRICAL SHEETS: PER THE WPB AMENDMENTS TO THE |
| | FBC, EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND |
| | SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. THE |
| | DIGITAL SIGNATURE MUST INCLUDE THE STATEMENT "SIGNED |
| | AND SEALED" AS PER FAC 61G15-23.004. PROVIDE |
| | CORRECTION. WPB FBC 107.1; FS 471/481 |
| | |
| | 3) PLEASE REVIEW SIGNATURE REVIEW COMMENTS BELOW BY |
| | SAMANTHA HILL DATED 5/21/19 AND DYLAN BATTLES DATED |
| | 3/21/19 |
| | |
| | 5/21/19 |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 1. THE FIRE SPRINKLER PLANS ARE NOT SIGNED AND SEALED, |
| | FS471. |
| | |
| | NOTE THAT THE TITLE BLOCK FOR THE FIRE PROTECTION PAGES |
| | LACK THE PRINTED NAME, LICENSE NUMBER FOR THE ENGINEER |
| | AND LACK CERTIFICATE OF AUTHORIZATION FOR ENVIRONETICS |
| | INC. |
| | |
| | OTHER PAGES ARE OK. |
| | |
| | 2. PLEASE ADVISE WHERE THE CITY PLACE STAMP CAN BE |
| | LOCATED. BUILDING OFFICIAL'S SUGGESTION IS, IF CITY |
| | PLACE IS UNABLE TO APPLY A REVIEW STAMP DIGITALLY TO A |
| | PDF, HAVE CITY PLACE STAMP A REDUCED SIZE PLAN AND |
| | PERMIT COORDINATOR CAN SCAN AND UPLOAD THE APPROVAL |
| | INTO "SUPPORTING DOCUMENTS". |
| | |
| | PLEASE CONTACT ME IF YOU WISH TO DISCUSS. |
| | |
| | 3/21/19 |
| | FIRE SPRINKLER (FS) SHEETS NOT DIGITALLY SIGNED. |
| | WAY FINDING (WF) SHEETS NOT DIGITALLY SIGNED. |
| | ALL OTHER STRUCTURAL SHEET OK FROM 1ST REVIEW. |
| | ANY ADDITIONAL SHEETS WIL NEED TO BE |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | BUILDING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| 2019-06-22 16:34:25 | FOR ELECTRICAL SHEETS: PER THE WPB AMENDMENTS TO THE |
| | FBC, EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND |
| | SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. THE |
| | DIGITAL SIGNATURE MUST INCLUDE THE STATEMENT "SIGNED |
| | AND SEALED" AS PER FAC 61G15-23.004. PROVIDE |
| | CORRECTION. WPB FBC 107.1; FS 471/481 |