Plan Review Notes
Plan Review Notes For Permit 19030060
Permit Number 19030060
Review Stop SIGNATURE
Sequence Number 3
Notes
Date Text
2019-07-02 08:48:493RD SIGNATURE REVIEW BY CHRISTOPHER L. COLE
 PERMIT #19030060
 7/2/19
  
 1) THE FOLLOWING LIST OF MECHANICAL PLANS DO NOT HAVE
 VALID ELECTRONIC SIGNATURES AND SEALS: M101, M102,
 M103, M104, M701, DM101, DM102, DM103, DM104.
 THE DIGITALLY SIGNED PLANS SHALL ALSO BEAR THIS
 STATEMENT IN ACCORDANCE WITH SECTION 61G15-23.005-
 "THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY
 _________ON DATE________USING A SHA-1 AUTHENTICATION
 CODE." THE CURRENT MECHANICAL PLANS INDICATE THEY ARE
 SIGNED ONLY. IN ADDITION ENGINEERS MAY NOT SELF-CERTIFY
 ELECTRONIC SIGNATURES AND SEALS. CERTIFICATION SHALL BE
 BY A THIRD-PARTY AGENCY.
  
 2) FOR ELECTRICAL SHEETS: PER THE WPB AMENDMENTS TO THE
 FBC, EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. THE
 DIGITAL SIGNATURE MUST INCLUDE THE STATEMENT "SIGNED
 AND SEALED" AS PER FAC 61G15-23.004. PROVIDE
 CORRECTION. WPB FBC 107.1; FS 471/481
  
 3) PLEASE REVIEW SIGNATURE REVIEW COMMENTS BELOW BY
 SAMANTHA HILL DATED 5/21/19 AND DYLAN BATTLES DATED
 3/21/19
  
 5/21/19
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE FIRE SPRINKLER PLANS ARE NOT SIGNED AND SEALED,
 FS471.
  
 NOTE THAT THE TITLE BLOCK FOR THE FIRE PROTECTION PAGES
 LACK THE PRINTED NAME, LICENSE NUMBER FOR THE ENGINEER
 AND LACK CERTIFICATE OF AUTHORIZATION FOR ENVIRONETICS
 INC.
  
 OTHER PAGES ARE OK.
  
 2. PLEASE ADVISE WHERE THE CITY PLACE STAMP CAN BE
 LOCATED. BUILDING OFFICIAL'S SUGGESTION IS, IF CITY
 PLACE IS UNABLE TO APPLY A REVIEW STAMP DIGITALLY TO A
 PDF, HAVE CITY PLACE STAMP A REDUCED SIZE PLAN AND
 PERMIT COORDINATOR CAN SCAN AND UPLOAD THE APPROVAL
 INTO "SUPPORTING DOCUMENTS".
  
 PLEASE CONTACT ME IF YOU WISH TO DISCUSS.
  
 3/21/19
 FIRE SPRINKLER (FS) SHEETS NOT DIGITALLY SIGNED.
 WAY FINDING (WF) SHEETS NOT DIGITALLY SIGNED.
 ALL OTHER STRUCTURAL SHEET OK FROM 1ST REVIEW.
 ANY ADDITIONAL SHEETS WIL NEED TO BE
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  
2019-06-22 16:34:25FOR ELECTRICAL SHEETS: PER THE WPB AMENDMENTS TO THE
 FBC, EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. THE
 DIGITAL SIGNATURE MUST INCLUDE THE STATEMENT "SIGNED
 AND SEALED" AS PER FAC 61G15-23.004. PROVIDE
 CORRECTION. WPB FBC 107.1; FS 471/481