2019-03-18 13:53:03PLUMBING 1ST REVIEW PERMIT # 19030060**DENIED**
  
 1) SHT A106 CALLS OUT GRAB BARS TO BE MOUNTED 33"-36"
 TO THE CENTER LINE OF THE BAR.GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES (840 MM)
 MINIMUM AND 36 INCHES (915 MM) MAXIMUM ABOVE THE FINISH
 FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE
 FBC-ACC 609.4\
  
 2) SHT A106 CALLS OUT FOR PAPER DISPENSER 7"-9" TO THE
 CENTER OF A MUILT ROLL HOLDER. THE INTENT OF THE CODE
 IS TO BE CENTERED ON THE 1ST ROLL IN MUILT HOLDER
 UNITS. FBC-ACC 604.9.6
  
 3) BOTH UNISEX TOILET ROOMS ARE MISSING BOTH THE 60"
 CLEAR FLOOR SPACE FOR THE TOILET AND THE 60" TURNING
 SPACE. FBC-ACC 604.3.1**603.2.1. THE URINAL SHALL NOT
 ENCROACH IN THE CLEAR FLOOR SPACE OF THE TOILET.
 FBC-ACC 604.3.2
  