| Plan Review Notes For Permit 19030060 |
| Permit Number |
19030060 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-03-18 13:53:03 | PLUMBING 1ST REVIEW PERMIT # 19030060**DENIED** | | | | | | 1) SHT A106 CALLS OUT GRAB BARS TO BE MOUNTED 33"-36" | | | TO THE CENTER LINE OF THE BAR.GRAB BARS SHALL BE | | | INSTALLED IN A HORIZONTAL POSITION, 33 INCHES (840 MM) | | | MINIMUM AND 36 INCHES (915 MM) MAXIMUM ABOVE THE FINISH | | | FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE | | | FBC-ACC 609.4\ | | | | | | 2) SHT A106 CALLS OUT FOR PAPER DISPENSER 7"-9" TO THE | | | CENTER OF A MUILT ROLL HOLDER. THE INTENT OF THE CODE | | | IS TO BE CENTERED ON THE 1ST ROLL IN MUILT HOLDER | | | UNITS. FBC-ACC 604.9.6 | | | | | | 3) BOTH UNISEX TOILET ROOMS ARE MISSING BOTH THE 60" | | | CLEAR FLOOR SPACE FOR THE TOILET AND THE 60" TURNING | | | SPACE. FBC-ACC 604.3.1**603.2.1. THE URINAL SHALL NOT | | | ENCROACH IN THE CLEAR FLOOR SPACE OF THE TOILET. | | | FBC-ACC 604.3.2 | | | | | | TIM HUNT | | | PLUMBING INSPECTOR/PLUMBING PLAN EXAMINER | | | BUILDING DIVISION | | | CITY OF WEST PALM BEACH | | | 561-248-2703 | | | [email protected] |
|