| 2019-03-13 10:14:35 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) SHEET S 504 & N 001 AND DOTHER LIFE SAFETY SHEETS - |
| | THERE ARE NO DIMENSIONS OF WIDTH BETWEEN THE SEAT BACK |
| | AND EXTENDED FOOT REST OF THE RECLINERS. |
| | |
| | PER NFPA 101, CH 12 |
| | |
| | 12.2.5.5* AISLE ACCESSWAYS SERVING SEATING NOT AT |
| | TABLES. |
| | 12.2.5.5.1* THE REQUIRED CLEAR WIDTH OF AISLE |
| | ACCESSWAYS BETWEEN |
| | ROWS OF SEATING SHALL BE DETERMINED AS FOLLOWS: |
| | (1) HORIZONTAL MEASUREMENTS SHALL BE MADE, BETWEEN |
| | VERTICAL |
| | PLANES, FROM THE BACK OF ONE SEAT TO THE FRONT OF THE |
| | MOST |
| | FORWARD PROJECTION OF THE SEAT IMMEDIATELY BEHIND IT. |
| | (2) WHERE THE ENTIRE ROW CONSISTS OF AUTOMATIC- OR |
| | SELF-RISING |
| | SEATS THAT COMPLY WITH ASTM F 851, STANDARD TEST METHOD |
| | FOR SELF-RISING SEAT MECHANISMS, THE MEASUREMENT SHALL |
| | BE |
| | PERMITTED TO BE MADE WITH THE SEATS IN THE UP POSITION. |
| | 12.2.5.5.2 THE AISLE ACCESSWAY BETWEEN ROWS OF SEATING |
| | SHALL HAVE |
| | A CLEAR WIDTH OF NOT LESS THAN 12 IN. (305 MM), AND |
| | THIS MINIMUM |
| | SHALL BE INCREASED AS A FUNCTION OF ROW LENGTH IN |
| | ACCORDANCE WITH |
| | 12.2.5.5.4, 12.2.5.5.5, AND 12.2.5.5.6. |
| | |
| | 12.2.5.5.5.1 THE 12 IN. (305 MM) MINIMUM CLEAR WIDTH OF |
| | AISLE |
| | ACCESSWAY SPECIFIED IN 12.2.5.5.2 SHALL BE INCREASED BY |
| | 0.3 IN. (7.6 |
| | MM) FOR EVERY SEAT OVER A TOTAL OF 14 BUT SHALL NOT BE |
| | REQUIRED TO |
| | EXCEED 22 IN. (560 MM). |
| | |
| | PLEASE REVIEW AND CORRECT AND PROVIDE THE DIMENSIONS IN |
| | COMPLIANCE. |
| | |
| | |
| | |
| | 2) SHEET N001 - THERE ARE NO INDICATIONS IF THIS |
| | PROJECT SCOPE INCLUDES CONTINUED OCCUPANCY OF THE |
| | REMAINDER OF THE THEATER. |
| | |
| | PLEASE REVIEW AND PROVIDE A DETAIL REVIEW OR PLAN |
| | SHEETS THAT INDICATE IF THE THEATER WILKL REMIAN OPEN |
| | AND OCCUPIED DURING CONSTRUCTION. |
| | |
| | ADDITIOANLLY, PLEASE PROVIDE HOW ALL CURRENT EXITS WILL |
| | BE MAINTAINED AND PROTECTED DURING ANY PHASING. |
| | |
| | |
| | |
| | 3) SHEET DE108 - COMMENT # 8 INDICATES "RELOCATE FIRE |
| | ALARM DEVICES". |
| | |
| | ALL FIRE ALARM WORK SHALL BE DONE UNDER SEPARATE PERMIT |
| | AND SHOP DRAWINGS BY CERTIFIED FIRE ALARM CONTRACTORS. |
| | |
| | THE FIRE ALARM SHALL BE MAINTAINED AND REMAIN |
| | FUNCTIONAL DURING ENTIRE CONSTRUCTION PERIOD. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT. |
| | |
| | |
| | |
| | 4) SHEET E 103 - THERE IS INDICATION OF FIRE ALARM WORK |
| | BUT NO INDICATION OF SHOP DRAWINGS. |
| | ALL FIRE ALARM WORK SHALL BE DONE UNDER SEPARATE PERMIT |
| | AND SHOP DRAWINGS BY CERTIFIED FIRE ALARM CONTRACTORS. |
| | |
| | THE FIRE ALARM SHALL BE MAINTAINED AND REMAIN |
| | FUNCTIONAL DURING ENTIRE CONSTRUCTION PERIOD. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT. |
| | |
| | |
| | |
| | |
| | 5) SHEET A 101 - THERE APPEARS TO BE A SHADED/NEW WALL |
| | IN THE CONCESSION AREA THAT IS NOT CALLED OUT UNDER KEY |
| | NOTES, COMMENTS, NOR LEGEND. |
| | |
| | PLEASE REVIEW AND CORRECT OR CLARIFY. |
| | |
| | |
| | |
| | |
| | 6) SHEET A 102 - THERE IS A SHADED/ NEW WALL INDICATED |
| | IN THE FRONT OF AUDITORIUM 3 THAT IS NOT CALLED OUT |
| | UNDER KEY NOTES, COMMENTS, NOR LEGEND. |
| | |
| | PLEASE REVIEW AND CORRECT OR CLARIFY. |
| | |
| | |
| | |
| | |
| | 7) ALL APPLICABLE SHEETS - ANY NEW WALL REQUIRES AN |
| | ELVALUATION FO THE FIRE SPRINKLER SYSTEM FOR CODE |
| | COMPLIANT COVERAGE. |
| | |
| | ANY MODICATION/ADDITION OF THE FIRE SPRINKLER SYSTEM |
| | SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS BY CERTIFIED |
| | FIRE SPRINKLER CONTRACTORS. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT ON THE SHEET. |
| | |
| | |
| | |
| | 8) SHEET A 104 - THERE ARE SHADED/ NEW WALLS INDICATED |
| | IN THE FRONT OF AUDITORIUM 7 & 8, AND OTHER AREAS THAT |
| | ARE NOT CALLED OUT UNDER KEY NOTES, COMMENTS, NOR |
| | LEGEND. |
| | |
| | PLEASE REVIEW AND CORRECT OR CLARIFY. |
| | |
| | |
| | |
| | |
| | 9) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 10) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |