Plan Review Notes
Plan Review Notes For Permit 19030060
Permit Number 19030060
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-03-13 10:14:35THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET S 504 & N 001 AND DOTHER LIFE SAFETY SHEETS -
 THERE ARE NO DIMENSIONS OF WIDTH BETWEEN THE SEAT BACK
 AND EXTENDED FOOT REST OF THE RECLINERS.
  
 PER NFPA 101, CH 12
  
 12.2.5.5* AISLE ACCESSWAYS SERVING SEATING NOT AT
 TABLES.
 12.2.5.5.1* THE REQUIRED CLEAR WIDTH OF AISLE
 ACCESSWAYS BETWEEN
 ROWS OF SEATING SHALL BE DETERMINED AS FOLLOWS:
 (1) HORIZONTAL MEASUREMENTS SHALL BE MADE, BETWEEN
 VERTICAL
 PLANES, FROM THE BACK OF ONE SEAT TO THE FRONT OF THE
 MOST
 FORWARD PROJECTION OF THE SEAT IMMEDIATELY BEHIND IT.
 (2) WHERE THE ENTIRE ROW CONSISTS OF AUTOMATIC- OR
 SELF-RISING
 SEATS THAT COMPLY WITH ASTM F 851, STANDARD TEST METHOD
 FOR SELF-RISING SEAT MECHANISMS, THE MEASUREMENT SHALL
 BE
 PERMITTED TO BE MADE WITH THE SEATS IN THE UP POSITION.
 12.2.5.5.2 THE AISLE ACCESSWAY BETWEEN ROWS OF SEATING
 SHALL HAVE
 A CLEAR WIDTH OF NOT LESS THAN 12 IN. (305 MM), AND
 THIS MINIMUM
 SHALL BE INCREASED AS A FUNCTION OF ROW LENGTH IN
 ACCORDANCE WITH
 12.2.5.5.4, 12.2.5.5.5, AND 12.2.5.5.6.
  
 12.2.5.5.5.1 THE 12 IN. (305 MM) MINIMUM CLEAR WIDTH OF
 AISLE
 ACCESSWAY SPECIFIED IN 12.2.5.5.2 SHALL BE INCREASED BY
 0.3 IN. (7.6
 MM) FOR EVERY SEAT OVER A TOTAL OF 14 BUT SHALL NOT BE
 REQUIRED TO
 EXCEED 22 IN. (560 MM).
  
 PLEASE REVIEW AND CORRECT AND PROVIDE THE DIMENSIONS IN
 COMPLIANCE.
  
  
  
 2) SHEET N001 - THERE ARE NO INDICATIONS IF THIS
 PROJECT SCOPE INCLUDES CONTINUED OCCUPANCY OF THE
 REMAINDER OF THE THEATER.
  
 PLEASE REVIEW AND PROVIDE A DETAIL REVIEW OR PLAN
 SHEETS THAT INDICATE IF THE THEATER WILKL REMIAN OPEN
 AND OCCUPIED DURING CONSTRUCTION.
  
 ADDITIOANLLY, PLEASE PROVIDE HOW ALL CURRENT EXITS WILL
 BE MAINTAINED AND PROTECTED DURING ANY PHASING.
  
  
  
 3) SHEET DE108 - COMMENT # 8 INDICATES "RELOCATE FIRE
 ALARM DEVICES".
  
 ALL FIRE ALARM WORK SHALL BE DONE UNDER SEPARATE PERMIT
 AND SHOP DRAWINGS BY CERTIFIED FIRE ALARM CONTRACTORS.
  
 THE FIRE ALARM SHALL BE MAINTAINED AND REMAIN
 FUNCTIONAL DURING ENTIRE CONSTRUCTION PERIOD.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT.
  
  
  
 4) SHEET E 103 - THERE IS INDICATION OF FIRE ALARM WORK
 BUT NO INDICATION OF SHOP DRAWINGS.
 ALL FIRE ALARM WORK SHALL BE DONE UNDER SEPARATE PERMIT
 AND SHOP DRAWINGS BY CERTIFIED FIRE ALARM CONTRACTORS.
  
 THE FIRE ALARM SHALL BE MAINTAINED AND REMAIN
 FUNCTIONAL DURING ENTIRE CONSTRUCTION PERIOD.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT.
  
  
  
  
 5) SHEET A 101 - THERE APPEARS TO BE A SHADED/NEW WALL
 IN THE CONCESSION AREA THAT IS NOT CALLED OUT UNDER KEY
 NOTES, COMMENTS, NOR LEGEND.
  
 PLEASE REVIEW AND CORRECT OR CLARIFY.
  
  
  
  
 6) SHEET A 102 - THERE IS A SHADED/ NEW WALL INDICATED
 IN THE FRONT OF AUDITORIUM 3 THAT IS NOT CALLED OUT
 UNDER KEY NOTES, COMMENTS, NOR LEGEND.
  
 PLEASE REVIEW AND CORRECT OR CLARIFY.
  
  
  
  
 7) ALL APPLICABLE SHEETS - ANY NEW WALL REQUIRES AN
 ELVALUATION FO THE FIRE SPRINKLER SYSTEM FOR CODE
 COMPLIANT COVERAGE.
  
 ANY MODICATION/ADDITION OF THE FIRE SPRINKLER SYSTEM
 SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS BY CERTIFIED
 FIRE SPRINKLER CONTRACTORS.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT ON THE SHEET.
  
  
  
 8) SHEET A 104 - THERE ARE SHADED/ NEW WALLS INDICATED
 IN THE FRONT OF AUDITORIUM 7 & 8, AND OTHER AREAS THAT
 ARE NOT CALLED OUT UNDER KEY NOTES, COMMENTS, NOR
 LEGEND.
  
 PLEASE REVIEW AND CORRECT OR CLARIFY.
  
  
  
  
 9) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 10) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  
  
  