| 2019-03-21 08:32:26 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 19030060 |
| | REVIEWED: MARCH 18, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[B] = FBC BUILDING |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | |
| | 1) 301.1 FBC[EXISTING] GENERAL. THE REPAIR, ALTERATION, |
| | CHANGE OF OCCUPANCY, ADDITION OR RELOCATION OF ALL |
| | EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS |
| | LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED |
| | BY THE APPLICANT. SECTIONS 301.1.1 THROUGH 301.1.3 |
| | SHALL NOT BE APPLIED IN COMBINATION WITH EACH OTHER. |
| | -WHICH METHOD IS BEING USED FOR COMPLIANCE? |
| | (PRESCRIPTIVE,WORK AREA OR PERFORMANCE) |
| | |
| | 2) 501 FBC[EXISTING] STATE THE LEVEL OF ALTERATION FOR |
| | WORK BEING PERFORMED. |
| | -PLEASE ADD LEVEL OF ALTERATION TO DESIGN DATA. |
| | |
| | 3) 1017.3 FBC[B] MEASUREMENT. EXIT ACCESS TRAVEL |
| | DISTANCE SHALL BE MEASURED FROM THE MOST REMOTE POINT |
| | WITHIN A STORY ALONG THE NATURAL AND UNOBSTRUCTED PATH |
| | OF HORIZONTAL AND VERTICAL EGRESS TRAVEL TO THE |
| | ENTRANCE TO AN EXIT. (EXIT COMPONENTS INCLUDE EXTERIOR |
| | EXIT DOORS AT THE LEVEL OF EXIT DISCHARGE, INTERIOR |
| | EXIT STAIRWAYS AND RAMPS, EXIT PASSAGEWAYS, EXTERIOR |
| | EXIT STAIRWAYS AND RAMPS AND HORIZONTAL EXITS) |
| | |
| | 1006.2.1 FBC TABLE[B] MAXIMUM COMMON PATH OF EGRESS |
| | TRAVEL DISTANCE. |
| | |
| | 1029.7 FBC[B] TRAVEL DISTANCE. EXITS AND AISLES SHALL |
| | BE SO LOCATED THAT THE TRAVEL DISTANCE TO AN EXIT DOOR |
| | SHALL BE NOT GREATER THAN 200 FEET (60 960 MM) MEASURED |
| | ALONG THE LINE OF TRAVEL IN NONSPRINKLERED BUILDINGS. |
| | TRAVEL DISTANCE SHALL BE NOT MORE THAN 250 FEET (76 200 |
| | MM) IN SPRINKLERED BUILDINGS. WHERE AISLES ARE PROVIDED |
| | FOR SEATING, THE DISTANCE SHALL BE MEASURED ALONG THE |
| | AISLES AND AISLE ACCESSWAYS WITHOUT TRAVEL OVER OR ON |
| | THE SEATS. |
| | |
| | 1029.8 FBC[B] COMMON PATH OF EGRESS TRAVEL. THE COMMON |
| | PATH OF EGRESS TRAVEL SHALL NOT EXCEED 30 FEET FROM ANY |
| | SEAT TO A POINT WHERE AN OCCUPANT HAS A CHOICE OF TWO |
| | PATHS OF EGRESS TRAVEL TO TWO EXITS. EXCEPTIONS: |
| | -FOR AREAS SERVING LESS THAN 50 OCCUPANTS, THE COMMON |
| | PATH OF EGRESS TRAVEL SHALL NOT EXCEED 75 FEET. |
| | -FOR SMOKE-PROTECTED ASSEMBLY SEATING, THE COMMON PATH |
| | OF EGRESS TRAVEL SHALL NOT EXCEED 50 FEET. |
| | |
| | A. STATE THE MAXIMUM COMMON PATH OF TRAVEL ON ONE OR |
| | ALL LIFE SAFETY SHEETS. |
| | B. STATE THE MAXIMUM EXIT ACCESS TRAVEL DISTANCE. |
| | C. SHOW THE MAXIMUM COMMON PATH OF TRAVEL AND MAXIMUM |
| | EXIT ACCESS TRAVEL DISTANCE ON THE PLANS FOR EACH |
| | AUDITORIUM BEING OCCUPIED. |
| | D. SHEET LEGEND ON ALL EGRESS PLANS SHOWS R=3 |
| | REPRESENTS REQUIRED EGRESS UNITS AND P=3 FOR PROVIDED |
| | EGRESS UNITS. ARE THESE UNITS SUPPOSED TO BE THE NUMBER |
| | OF EXITS REQUIRED AND PROVIDED? |
| | WHERE USED ON THE PLANS THE R AND P BECOME EGRESS |
| | WIDTH. IT APPEARS THAT THE EGRESS WIDTH SHOULD BE IN |
| | THE TABLE WHERE THE COLUMN STATES EGRESS WIDTH AND THE |
| | R= AND P= SHOULD BE THE NUMBER OF EXITS AT EACH |
| | AUDITORIUM. |
| | |
| | 4) 1013.1 FBC[B] EXIT SIGNS. |
| | -MARK EXIT SIGNS ON LIFE SAFETY SHEETS. |
| | |
| | 5) 1004.3 FBC[B] POSTING OF OCCUPANT LOAD. EVERY ROOM |
| | OR SPACE THAT IS AN ASSEMBLY OCCUPANCY SHALL HAVE THE |
| | OCCUPANT LOAD OF THE ROOM OR SPACE POSTED IN A |
| | CONSPICUOUS PLACE, NEAR THE MAIN EXIT OR EXIT ACCESS |
| | DOORWAY FROM THE ROOM OR SPACE. POSTED SIGNS SHALL BE |
| | OF AN APPROVED LEGIBLE PERMANENT DESIGN AND SHALL BE |
| | MAINTAINED BY THE OWNER OR THE OWNER?S AUTHORIZED |
| | AGENT. |
| | -PLEASE ADD NOTE TO PLANS, OR TELL ME WHERE THE NOTE |
| | IS LOCATED. |
| | |
| | 6) 1008.3.1 FBC[B] GENERAL. IN THE EVENT OF POWER |
| | SUPPLY FAILURE IN ROOMS AND SPACES THAT REQUIRE TWO OR |
| | MORE MEANS OF EGRESS, AN EMERGENCY ELECTRICAL SYSTEM |
| | SHALL AUTOMATICALLY ILLUMINATE ALL OF THE FOLLOWING |
| | AREAS: |
| | -AISLES. |
| | -CORRIDORS. |
| | -EXIT ACCESS STAIRWAYS AND RAMPS. |
| | |
| | 1008.3.2 FBC[B] BUILDINGS. IN THE EVENT OF POWER SUPPLY |
| | FAILURE IN BUILDINGS THAT REQUIRE TWO OR MORE MEANS OF |
| | EGRESS, AN EMERGENCY ELECTRICAL SYSTEM SHALL |
| | AUTOMATICALLY ILLUMINATE ALL OF THE FOLLOWING AREAS: |
| | -INTERIOR EXIT ACCESS STAIRWAYS AND RAMPS. |
| | -INTERIOR AND EXTERIOR EXIT STAIRWAYS AND RAMPS. |
| | -EXIT PASSAGEWAYS. |
| | -VESTIBULES AND AREAS ON THE LEVEL OF DISCHARGE USED |
| | FOR EXIT DISCHARGE IN ACCORDANCE WITH SECTION 1028.1. |
| | -EXTERIOR LANDINGS AS REQUIRED BY SECTION 1010.1.6 FOR |
| | EXIT DOORWAYS THAT LEAD DIRECTLY TO THE EXIT DISCHARGE. |
| | |
| | 1008.3.3 FBC[B] ROOMS AND SPACES. IN THE EVENT OF POWER |
| | SUPPLY FAILURE, AN EMERGENCY ELECTRICAL SYSTEM SHALL |
| | AUTOMATICALLY ILLUMINATE ALL OF THE FOLLOWING AREAS: |
| | -ELECTRICAL EQUIPMENT ROOMS. |
| | -FIRE COMMAND CENTERS. |
| | -FIRE PUMP ROOMS. |
| | -GENERATOR ROOMS. |
| | -PUBLIC RESTROOMS WITH AN AREA GREATER THAN 300 SQUARE |
| | FEET |
| | |
| | A) I SEE GENERATOR FEEDING PANELS, BUT NOT SURE WHAT |
| | THOSE PANELS COVER. CAN YOU PLEASE PROVIDE PANEL |
| | SCHEDULES AND EMERGENCY LIGHTING PLAN TO SHOW |
| | COMPLIANCE WITH 1008.3.1 ? 1008.3.3.? |
| | B) WHAT HAPPENS TO MOTORIZED CHAIRS IN POWER FAILURE? |
| | |
| | 5) THE FOLLOWING ITEMS WILL BE DEFERRED SUBMITTALS (NO |
| | RESPONSE REQD) |
| | A. GUARDS/RAILS |
| | B. INTERIOR FINISH FOR DRAPES/CURTAINS |
| | |
| | NOTES: |
| | |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |