2019-03-21 08:32:26****CORRECTIONS****
 W.P.B. PERMIT: 19030060
 REVIEWED: MARCH 18, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 1) 301.1 FBC[EXISTING] GENERAL. THE REPAIR, ALTERATION,
 CHANGE OF OCCUPANCY, ADDITION OR RELOCATION OF ALL
 EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS
 LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED
 BY THE APPLICANT. SECTIONS 301.1.1 THROUGH 301.1.3
 SHALL NOT BE APPLIED IN COMBINATION WITH EACH OTHER.
  -WHICH METHOD IS BEING USED FOR COMPLIANCE?
 (PRESCRIPTIVE,WORK AREA OR PERFORMANCE)
  
 2) 501 FBC[EXISTING] STATE THE LEVEL OF ALTERATION FOR
 WORK BEING PERFORMED.
  -PLEASE ADD LEVEL OF ALTERATION TO DESIGN DATA.
  
 3) 1017.3 FBC[B] MEASUREMENT. EXIT ACCESS TRAVEL
 DISTANCE SHALL BE MEASURED FROM THE MOST REMOTE POINT
 WITHIN A STORY ALONG THE NATURAL AND UNOBSTRUCTED PATH
 OF HORIZONTAL AND VERTICAL EGRESS TRAVEL TO THE
 ENTRANCE TO AN EXIT. (EXIT COMPONENTS INCLUDE EXTERIOR
 EXIT DOORS AT THE LEVEL OF EXIT DISCHARGE, INTERIOR
 EXIT STAIRWAYS AND RAMPS, EXIT PASSAGEWAYS, EXTERIOR
 EXIT STAIRWAYS AND RAMPS AND HORIZONTAL EXITS)
  
 1006.2.1 FBC TABLE[B] MAXIMUM COMMON PATH OF EGRESS
 TRAVEL DISTANCE.
  
 1029.7 FBC[B] TRAVEL DISTANCE. EXITS AND AISLES SHALL
 BE SO LOCATED THAT THE TRAVEL DISTANCE TO AN EXIT DOOR
 SHALL BE NOT GREATER THAN 200 FEET (60 960 MM) MEASURED
 ALONG THE LINE OF TRAVEL IN NONSPRINKLERED BUILDINGS.
 TRAVEL DISTANCE SHALL BE NOT MORE THAN 250 FEET (76 200
 MM) IN SPRINKLERED BUILDINGS. WHERE AISLES ARE PROVIDED
 FOR SEATING, THE DISTANCE SHALL BE MEASURED ALONG THE
 AISLES AND AISLE ACCESSWAYS WITHOUT TRAVEL OVER OR ON
 THE SEATS.
  
 1029.8 FBC[B] COMMON PATH OF EGRESS TRAVEL. THE COMMON
 PATH OF EGRESS TRAVEL SHALL NOT EXCEED 30 FEET FROM ANY
 SEAT TO A POINT WHERE AN OCCUPANT HAS A CHOICE OF TWO
 PATHS OF EGRESS TRAVEL TO TWO EXITS. EXCEPTIONS:
 -FOR AREAS SERVING LESS THAN 50 OCCUPANTS, THE COMMON
 PATH OF EGRESS TRAVEL SHALL NOT EXCEED 75 FEET.
 -FOR SMOKE-PROTECTED ASSEMBLY SEATING, THE COMMON PATH
 OF EGRESS TRAVEL SHALL NOT EXCEED 50 FEET.
  
 A. STATE THE MAXIMUM COMMON PATH OF TRAVEL ON ONE OR
 ALL LIFE SAFETY SHEETS.
 B. STATE THE MAXIMUM EXIT ACCESS TRAVEL DISTANCE.
 C. SHOW THE MAXIMUM COMMON PATH OF TRAVEL AND MAXIMUM
 EXIT ACCESS TRAVEL DISTANCE ON THE PLANS FOR EACH
 AUDITORIUM BEING OCCUPIED.
 D. SHEET LEGEND ON ALL EGRESS PLANS SHOWS R=3
 REPRESENTS REQUIRED EGRESS UNITS AND P=3 FOR PROVIDED
 EGRESS UNITS. ARE THESE UNITS SUPPOSED TO BE THE NUMBER
 OF EXITS REQUIRED AND PROVIDED?
 WHERE USED ON THE PLANS THE R AND P BECOME EGRESS
 WIDTH. IT APPEARS THAT THE EGRESS WIDTH SHOULD BE IN
 THE TABLE WHERE THE COLUMN STATES EGRESS WIDTH AND THE
 R= AND P= SHOULD BE THE NUMBER OF EXITS AT EACH
 AUDITORIUM.
  
 4) 1013.1 FBC[B] EXIT SIGNS.
  -MARK EXIT SIGNS ON LIFE SAFETY SHEETS.
  
 5) 1004.3 FBC[B] POSTING OF OCCUPANT LOAD. EVERY ROOM
 OR SPACE THAT IS AN ASSEMBLY OCCUPANCY SHALL HAVE THE
 OCCUPANT LOAD OF THE ROOM OR SPACE POSTED IN A
 CONSPICUOUS PLACE, NEAR THE MAIN EXIT OR EXIT ACCESS
 DOORWAY FROM THE ROOM OR SPACE. POSTED SIGNS SHALL BE
 OF AN APPROVED LEGIBLE PERMANENT DESIGN AND SHALL BE
 MAINTAINED BY THE OWNER OR THE OWNER?S AUTHORIZED
 AGENT.
  -PLEASE ADD NOTE TO PLANS, OR TELL ME WHERE THE NOTE
 IS LOCATED.
  
 6) 1008.3.1 FBC[B] GENERAL. IN THE EVENT OF POWER
 SUPPLY FAILURE IN ROOMS AND SPACES THAT REQUIRE TWO OR
 MORE MEANS OF EGRESS, AN EMERGENCY ELECTRICAL SYSTEM
 SHALL AUTOMATICALLY ILLUMINATE ALL OF THE FOLLOWING
 AREAS:
 -AISLES.
 -CORRIDORS.
 -EXIT ACCESS STAIRWAYS AND RAMPS.
  
 1008.3.2 FBC[B] BUILDINGS. IN THE EVENT OF POWER SUPPLY
 FAILURE IN BUILDINGS THAT REQUIRE TWO OR MORE MEANS OF
 EGRESS, AN EMERGENCY ELECTRICAL SYSTEM SHALL
 AUTOMATICALLY ILLUMINATE ALL OF THE FOLLOWING AREAS:
 -INTERIOR EXIT ACCESS STAIRWAYS AND RAMPS.
 -INTERIOR AND EXTERIOR EXIT STAIRWAYS AND RAMPS.
 -EXIT PASSAGEWAYS.
 -VESTIBULES AND AREAS ON THE LEVEL OF DISCHARGE USED
 FOR EXIT DISCHARGE IN ACCORDANCE WITH SECTION 1028.1.
 -EXTERIOR LANDINGS AS REQUIRED BY SECTION 1010.1.6 FOR
 EXIT DOORWAYS THAT LEAD DIRECTLY TO THE EXIT DISCHARGE.
  
 1008.3.3 FBC[B] ROOMS AND SPACES. IN THE EVENT OF POWER
 SUPPLY FAILURE, AN EMERGENCY ELECTRICAL SYSTEM SHALL
 AUTOMATICALLY ILLUMINATE ALL OF THE FOLLOWING AREAS:
 -ELECTRICAL EQUIPMENT ROOMS.
 -FIRE COMMAND CENTERS.
 -FIRE PUMP ROOMS.
 -GENERATOR ROOMS.
 -PUBLIC RESTROOMS WITH AN AREA GREATER THAN 300 SQUARE
 FEET
  
 A) I SEE GENERATOR FEEDING PANELS, BUT NOT SURE WHAT
 THOSE PANELS COVER. CAN YOU PLEASE PROVIDE PANEL
 SCHEDULES AND EMERGENCY LIGHTING PLAN TO SHOW
 COMPLIANCE WITH 1008.3.1 ? 1008.3.3.?
 B) WHAT HAPPENS TO MOTORIZED CHAIRS IN POWER FAILURE?
  
 5) THE FOLLOWING ITEMS WILL BE DEFERRED SUBMITTALS (NO
 RESPONSE REQD)
 A. GUARDS/RAILS
 B. INTERIOR FINISH FOR DRAPES/CURTAINS
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  