Plan Review Notes
Plan Review Notes For Permit 19030018
Permit Number 19030018
Review Stop B
Sequence Number 1
Notes
Date Text
2019-03-13 09:46:252017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19030018
 ADD: 550 OKEECHOBEE BLVD. SUITE: MPH22
 CONT: T-SQUARE CONSTRUCTION & SERVICES
 TEL: 561-482-4052
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. MARCH 13, 2019
 ACTION: DENIED
 1) SHEET A-2:
 1A) SHEET A-2 DOES INDICATE THE PLANS WERE DEVELOPED
 UNDER THE 2017 FBC-EXISTING BUILDING CODE LEVEL II
 ALTERATION. UNDER THE SECTION 806.1 FOR LEVEL II
 ALTERATIONS THE CODE TAKES YOU TO THE PROVISIONS OF THE
 2017 FBC-ACCESSIBILITY CODE, THE SECOND OR BACK HALF OF
 THE BOOK CONTAINS THE FAIR HOUSING GUIDELINE. THIS
 HIGHRISE WAS BUILT AFTER THE FAIR HOUSING GUIDELINES
 WENT IN AFFECT. THEY WENT INTO EFFECT MARCH 13, 1991.
 ALL HABITAL FLOORS HAVE ACCESS BY ELEVATORS AND ALL
 UNITS HAVE TO COMPLY WITH THE FAIR HOUSING ACT. NEITHER
 OF THE BATHROOMS SHOWN INDICATE IF THEY WERE DESIGNED
 TO SPECIFICATION A OR SPECIFICATION B.
 1B) THE PLANS DO INDICATE THE TWO BATHROOMS ARE TO BE
 REMODELED. THE GUIDELINE UNDER REQUIREMENT 7 GIVES
 DESIGN CHOICES:
 1) ALL BATHROOMS COMPLY WITH SPECIFICATION A
 OR
 2) ONE BATHROOM COMPLIES WITH SPECIFICATION B AND ALL
 OTHER BATHROOM(S) NOT REQUIRED TO MEET
 MANEUVERING AND CLEAR FLOOR SPACE REQUIREMENTS. TAKEN
 FROM THE TECHNICAL OVERVIEW/PARTICIPANT
 MANUAL.
 1C) SPECIFICATION A OR B CLEAR FLOOR SPACE- SHOWERS.
 SHOWER STALLS MAYBE OF ANY SIZE OR CONFIGURATION EXCEPT
 WHEN:
 1) THE SHOWER STALL IS THE ONLY BATHING FIXTURE IN THE
 DWELLING; OR
 2) WHEN THE SHOWER STALL IS DESIGNED THE ACCESSIBLE
 BATHING FIXTURE IN A SPECIFICATION B BATHROOM.
 IN BOTH OF THESE EXCEPTIONS, THE GUIDELINE SPECIFY THAT
 THE SHOWER STALL SHALL BE A MINIMUM OF 36
 INCHES X 36 INCHES.
 IT MUST HAVE A 30 X 48 INCH CLEAR FLOOR SPACE PARALLEL
 TO THE STALL AND FLUSH WITH THE CONTROL WALL. THE
 SHOWER WALL OPPOSITE THE CONTROLS MUST BE REINFORCED TO
 ALLOW FOR THE INSTALLATION OF A WALL-HUNG SEAT.
  
 2) SHEET A-2 INDICATES THE REMOVAL OF FLOOR FINISHES
 NEW FINISHES PER THE OWNERS SELECTION, PLEASE SHOW
 COMPLIANCE WITH:
  
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2017)
 FOR TILE, STONE, MARBLE, VINYL (LVT) OR (LVP) AND WOOD
 FLOORING ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT
 TESTED FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND
 MEET THE QUALIFICATIONS LISTED UNDER EACH OF THE
 STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ NO
 DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 2A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2B) FBC-B 2017 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  