Plan Review Notes
Plan Review Notes For Permit 19021420
Permit Number 19021420
Review Stop P
Sequence Number 2
Notes
Date Text
2020-06-30 11:15:262ND REVIEW FBC-2017 PLUMBING
 PERMIT 19021420
 6/30/2020
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A NEW LANDSCAPE PLAN WAS SUBMITTED HOWEVER THE 1ST
 REVIEW PLUMBING COMMENTS PRINTED BELOW ABOUT THE
 IRRIGATION SYSTEM WERE NOT ADDRESSED. PLEASE NOTE THAT
 A SEPARATE PERMIT IS REQUIRED FOR LANDSCAPING.
  
 PLUMBING 1ST REVIEW**DENIED**
  
 1) PERMIT APPLICATION CALLS OUT TEMP SYSTEM. PLEASE
 CLARIFY HOW LONG THIS TIME SYSTEM WILL BE IN PLACE AND
 PROVIDE SECTIONS ON PLAN WHICH AREA WILL BE TEMP. FBC
 107.2.1
 2) SHT. 2 CALL OUT A PVB BACKFLOW. PER THE CITY OF WPB
 CROSS CONNECTION MANUAL ALL COMMERCIAL PROPERTIES
 IRRIGATION SYSTEM BE PROTECTED BY AN RPZ BACKFLOW PIPED
 FROM THE METER IN MIN TYPE (L) COPPER. INSTALLED OF THE
 DEVICE IS ONLY TO BY DONE BY LICENSE PLUMBER (F.S 489
 AND CROSS CONNECTION MANUAL) AND REQUIRES SEPARATE
 PERMIT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  
  
 PLUMBING 1ST REVIEW**DENIED**
  
 1) PERMIT APPLICATION CALLS OUT TEMP SYSTEM. PLEASE
 CLARIFY HOW LONG THIS TIME SYSTEM WILL BE IN PLACE AND
 PROVIDE SECTIONS ON PLAN WHICH AREA WILL BE TEMP. FBC
 107.2.1
 2) SHT. 2 CALL OUT A PVB BACKFLOW. PER THE CITY OF WPB
 CROSS CONNECTION MANUAL ALL COMMERCIAL PROPERTIES
 IRRIGATION SYSTEM BE PROTECTED BY AN RPZ BACKFLOW PIPED
 FROM THE METER IN MIN TYPE (L) COPPER. INSTALLED OF THE
 DEVICE IS ONLY TO BY DONE BY LICENSE PLUMBER (F.S 489
 AND CROSS CONNECTION MANUAL) AND REQUIRES SEPARATE
 PERMIT.
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH (CGA SOLUTIONS)
 [email protected]
 561-248-2703
  