| Plan Review Notes For Permit 19021420 |
| Permit Number |
19021420 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-09-12 17:48:19 | PLUMBING 1ST REVIEW**DENIED** | | | | | | 1) PERMIT APPLICATION CALLS OUT TEMP SYSTEM. PLEASE | | | CLARIFY HOW LONG THIS TIME SYSTEM WILL BE IN PLACE AND | | | PROVIDE SECTIONS ON PLAN WHICH AREA WILL BE TEMP. FBC | | | 107.2.1 | | | 2) SHT. 2 CALL OUT A PVB BACKFLOW. PER THE CITY OF WPB | | | CROSS CONNECTION MANUAL ALL COMMERCIAL PROPERTIES | | | IRRIGATION SYSTEM BE PROTECTED BY AN RPZ BACKFLOW PIPED | | | FROM THE METER IN MIN TYPE (L) COPPER. INSTALLED OF THE | | | DEVICE IS ONLY TO BY DONE BY LICENSE PLUMBER (F.S 489 | | | AND CROSS CONNECTION MANUAL) AND REQUIRES SEPARATE | | | PERMIT. | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH (CGA SOLUTIONS) | | | [email protected] | | | 561-248-2703 | | | |
|