| Plan Review Notes For Permit 19021372 |
| Permit Number |
19021372 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-03-07 09:16:06 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | JOSEAN A. DUPREY E.I., BN, PX | | | BUILDING PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6716 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PLEASE PROVIDE THE LICENSURE DATE FOR THE GENERAL | | | CONTRACTOR. PER SECTION 489.113, FLORIDA STATUTES, | | | ROOFING WORK MUST BE SUBCONTRACTED TO A | | | CERTIFIED/REGISTERED ROOFING CONTRACTOR, BUT THERE ARE | | | SOME EXCEPTIONS TO WHEN A GENERAL, BUILDING, OR | | | RESIDENTIAL CONTRACTOR MAY PERFORM ROOFING WORK. THE | | | CONTRACTOR IS NOT REQUIRED TO SUBCONTRACT THE | | | INSTALLATION, OR REPAIR MADE UNDER WARRANTY OF WOOD | | | SHINGLES, WOOD SHAKES, OR ASPHALT OR FIBERGLASS SHINGLE | | | ROOFING MATERIALS ON A NEW BUILDING OF HIS OR HER OWN | | | CONSTRUCTION. A CGC CANNOT DO ROOF REPAIRS AND CANNOT | | | DO A ROOF TIE IN AN ADDITION TO AN EXISTING STRUCTURE. | | | THAT IS THE SCOPE OF A CERTIFIED ROOFER. HOWEVER IF THE | | | CGC LICENSE WAS ISSUE ON OR BEFORE 1973 THE 489.113 DO | | | NOT APPLY. | | | | | | 2. PLEASE BE MORE SPECIFIC WITH THE STUCCO SCOPE OF | | | WORK. DO THIS IS FOR THE ENTIRE HOUSE OR SOME AREAS? | | | FBC 107 |
|