Plan Review Notes
Plan Review Notes For Permit 19021354
Permit Number 19021354
Review Stop P
Sequence Number 1
Notes
Date Text
2019-03-20 13:53:10PLUMBING 1ST REVIEW**DENIED**
  
 1) PROVIDE MANUFACTURES INSTALLATION MANUAL FOR THE NEW
 GREASE INTERCEPTOR. ALSO NOTE ON PLANS A SEPERATE
 PERMIT FOR THE INTERCEPTOR IS REQUIRED. FBC 107.2.1
  
 2) PLEASE RESUBMIT SHT.A-402 AS MOST ALL PRINT IS NOT
 READABLE. FBC 107.3.5
  
 3) THE GRAB BAR ON SHT. A-402 IS SHOWING 33"-36" TO THE
 CENTER. FBC-A 604.5.2 STATES THE 33"-36" IS TO THE
 GRIPPING SURFACE OR TOP/
  
 4) ALL PAGES OF THE PLANS ARE SUBBMITTED ELECTRONICALLY
 ARE REQUIRED TO BE DIGITAL SIGNED BY DESIGNER OF
 RECORED. F.A.C 61G15-23.003. NON EOF THE PLUMBING PAGES
 ARE SIGNED AT ALL.
  
 5) YOUR EXISTING RESTROOMS SHOW CLEAR FLOOR SPACE'S BUT
 THE SINK ENCROACHES INTO THE TOILETS CLEAR FLOOR SPACE
 WHICH IS NOT PERMITTED. FBC-A604.3.2. IS IT YOUR INTENT
 TO MAKE ALL FIXTURES MEET ADA/ FLORIDA ACCESSIBILITY?
  
 6) THE USAGE OF THIS SPACE BEFORE WAS A RESTAURANT
 WHICH IS EXEMPT FROM THE REQUIRED OF HAVE A HI-LOW
 DRINKING FOUNTAIN UNDER FBC-P 410.4. PLEASE PROVIDE A
 HI-LOW DRINKING FOUNTAIN TO COMPLY WITH FBC-P 410.3
  
 7) PROVIDE INSTALLATION MANUAL FOR THE NEW WATER
 HEATER. FBC 107.2.1.
  
 8) WHAT IS THE TOTAL DEVELOPED LENGHT OF HOT WATER
 PIPING FROM THE WATER HEATER TO THE LAST FIXTURE? IT
 OVER 50' A HOT WATER RETURN SYSTEM WOULD BE REQUIRED.
 FBC-P 607.2
  
  
 TIM HUNT
 PLUMBING INSPECTOR/PLUMBING PLAN EXAMINER
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 561-248-2703