Plan Review Notes
Plan Review Notes For Permit 19021354
Permit Number 19021354
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-03-05 13:29:42THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET A 001 - UNDER GENERAL NOTES # 1 THERE IS AN
 INDICATION TO THE CITY OF OKEECHOBEE. THIS PROJECT
 APPEARS TO BE IN WEST PALM BEACH.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 2) SHEET A 001 - AT THE TOP OF THE PAGE UNDET TENANT
 IMPROVEMENT IS OKEECHOBEE FL.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 3) SHEET A 001 - THERE IS A CONFLICT INDICATED UNDER
 APPLICABLE CODES: FLORIDA FIRE PREVENTION CODE 2018 VS
 FFPC 2012.
  
 THE CORRECT EDITION WAS APPROVED ON DEC. 31, 2018,
 WHICH INCLUDES NFPA 1, 2015 ED & NFPA 101, 2015 ED,
 WITH FL AMENDMENTS.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 4) SHEET E 1.1 - THERE ARE NO INDICATIONS OF FIRE ALARM
 DEVICES OR EQUIPMENT.
  
 THERE SHOULD BE A FIRE ALARM NOTIFICATION DEVICE IN
 THIS SUITE FOR FIRE SPRINKLER ACTIVATION NOTIFICATION.
  
 PLEASE REVIEW AND ENSURE ANY FIRE ALARM WORK IS UNDER
 SEPARATE SHOP DRAWINGS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  