2019-03-12 08:55:402017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19021354
 ADD: 831 VILLAGE BLVD. SUITE: 307
 CONT: SIZ CONSTRUCTION CORP.
 TEL: 305-303-8111
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MARCH 12/ 2019
 ACTION: DENIED
  
 1) THE SUBMITTED PLANS ARE NOT SIGNED AND SEALED BY A
 DESIGN PROFESSIONAL. UNDER THE PROJECT DIRECTORY IT
 STATES:
 ARCHITECT:
 ARCHIDEZIGNS, LLC / LICENSE FOR ARCHITECT BUSINESS
 AA26002029
 1585 NE 26TH ST.
 WILTON MANORS, FL 33305
 954-934-9076
 ARCHITECTS: FLORIDA ADMINISTRATIVE CODE 61G1-16.005.
 PROCEDURES FOR DIGITALLY SIGNING AND SEALING AND FOR
 ELECTRONICALLY TRANSMITTING PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
  
 MEP ENGINEERS
 B & K ENGINEERING GROUP CERTIFICATE OF AUTHORIZATION
 31989
 11731 NW 39TH PLACE
 SUNRISE, FL 33323
 561-716-7120
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 2) THE JOBSITE VALUE OF THIS PROJECT IS $93,000.00
 DOLLARS IN VALUE. PLEASE REVIEW WHERE UP TO $18,600.00
 DOLLARS IN VALUE (0.20% X $93,000.00= $18,600.00) WILL
 BE SPENT ON ACCESSIBLE UPGRADES OVER AND BEYOND THE
 COST OF THE JOB TO MAKE THIS TENANT SPACE FULLY
 ACCESSIBLE. PLEASE REVIEW IN ORDER OF HOW THE FUNDS ARE
 TO BE SPENT. 2017 FBC-ACCESS. CODE SECTION:
 202.4.1 DISPROPORTIONATE COST. ALTERATIONS MADE TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO THE ALTERED
 AREA WILL BE DEEMED DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20% OF THE COST OF THE
 ALTERATION TO THE PRIMARY FUNCTION AREA. COSTS THAT MAY
 BE COUNTED AS EXPENDITURES REQUIRED TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I) COSTS
 ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (II) COSTS
 ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS
 INSTALLING GRAB BARS, ENLARGING TOILET STALLS,
 INSULATING PIPES, OR INSTALLING ACCESSIBLE FAUCET
 CONTROLS; (III) COSTS ASSOCIATED WITH PROVIDING
 ACCESSIBLE TELEPHONES, SUCH AS RELOCATING THE TELEPHONE
 TO AN ACCESSIBLE HEIGHT, INSTALLING AMPLIFICATION
 DEVICES, OR INSTALLING A TEXT TELEPHONE (TTY); (IV)
 COSTS ASSOCIATED WITH RELOCATING AN INACCESSIBLE
 DRINKING FOUNTAIN.
 EITHER THE DESIGN PROFESSIONAL OR THE CONTRACTOR CAN
 CREATE ON THEIR LETTERHEAD A LETTER IN THE ORDER OF
 ALTERED AREAS HOW THE FUNDS WILL BE SPENT TO MAKE THIS
 PROJECT CODE COMPLIANT AS MUCH AS POSSIBLE WITHOUT
 GOING OVER THE DISPROPORTIONATE COST OF $18,600.00 IN
 VALUE FOR ACCESSIBILITY.
  
 3) SHEET 005-A-141 IS SHOWN AS THE LIFE SAFETY SHEET.
  
 3A) CAPACITY OF EXITS. THE PLAN STATES THE MINIMUM
 REQUIRED DOOR WIDTH IS 32 INCHES. PLEASE REVIEW THE
 2017 FBC-B:
 1010.1.1 SIZE OF DOORS. THE REQUIRED CAPACITY OF EACH
 DOOR OPENING SHALL BE SUFFICIENT FOR THE OCCUPANT LOAD
 THEREOF AND SHALL PROVIDE A MINIMUM CLEAR WIDTH OF 32
 INCHES. CLEAR OPENINGS OF DOORWAYS WITH SWINGING DOORS
 SHALL BE MEASURED BETWEEN THE FACE OF THE DOOR AND THE
 STOP, WITH THE DOOR OPEN 90 DEGREES).
 2017 FBC-ACCESSIBILITY CODE 404.2.3 CLEAR WIDTH. DOOR
 OPENINGS SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES
 MINIMUM. CLEAR OPENINGS OF DOORWAYS WITH SWINGING DOORS
 SHALL BE MEASURED BETWEEN THE FACE OF THE DOOR AND THE
 STOP, WITH THE DOOR OPEN 90 DEGREES.
  
 3B) THE LIFE SAFETY SHEET SHOWS 2 EXISTING RESTROOMS,
 BOTH SHOW A CIRCLE WITHIN BOTH, NOT DIMENSIONED, ON
 SHEET 002-A-101 THE DIMENSION PLAN DOES NOT SHOW
 DIMENSIONS TO THE EXISTING RESTROOMS. COMPLIANCE WITH
 THE 2017 FBC-ACCESSIBILITY CODE 213.2 NOR 603 CANNOT BE
 DETERMINED.
  
 3C) THIS SHEET SHOWS CUSTOMER SEATING AND TABLES BUT
 DOES NOT GIVE THE HEIGHT OF THE ACCESSIBLE TABLE? SHOW
 COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY CODE SECTION
 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND WORK
 SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 4A) SHEET 010-A-401 DETAIL 1 SHOWS ONE OF THE EXISTING
 RESTROOMS AND STATES FOR REFERENCE ONLY. THIS DETAIL
 DOES NOT INDICATE THAT THIS IS SUPPOSED TO BE AN
 ACCESSIBLE RESTROOM ALTHOUGH THERE IS A CIRCLE WITHIN
 THE RESTROOM POSSIBLY REPRESENTING 5 FOOT DIAMETER AND
 COMPLIANCE WITH ACCESS. CODE 304.3.1 THE CIRCLE NOR
 DOES THE ROOM SHOW ANY DIMENSIONS INDICATING CODE
 COMPLIANCE.
  
 4B) WITHIN THIS SAME RESTROOM THE PLAN DOES SHOW THE
 CLEAR FLOOR SPACE REQUIRED BY 604.3.1 BUT DOES NOT MEET
 THE OVERLAP REQUIREMENTS OF 604.3.2 OF THE ACCESS.
 CODE.
  
 4C) PLEASE SEE THE ELEVATIONS FOR THE GRAB BARS, DETAIL
 4 ELEVATIONS, THE GRAB BARS ARE DIMENSIONED FROM THE
 CENTERLINE OF THE GARB BAR, UNDER THE 2017
 FBC-ACCESSIBILITY CODE YOU WOULD MEASURE FROM THE TOP
 OF THE BAR.
  
 2017 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF
 GRAB BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
  
 4D) IN THE ELEVATION 4 DETAIL 1 ELEVATION THE BACK GRAB
 BAR WOULD APPEAR NOT TO MEET THE REQUIREMENTS OF
 604.5.2ACCESS. CODE FOR THE REAR WALL, COMPLIANCE
 CANNOT BE DETERMINED SINCE THERE ARE NO DIMENSIONS.
  
 5) SHEET 011-A-402: THE LOCATION OF GRAB BARS AGAIN IS
 TAKEN FROM THE CENTERLINE NOT THE TOP OF THE GRIPPING
 SURFACE. 2017 FBC-ACCESSIBILITY CODE SECTION 609.4
 POSITION OF GRAB BARS. GRAB BARS SHALL BE INSTALLED IN
 A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE, NOT CENTERLINE.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  