| 2019-03-20 09:47:05 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE, |
| | INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF |
| | SERVICE IS ADEQUATE. THE WATER HEATER IS NOT INCLUDED |
| | IN PANEL SCHEDULE/LOAD CALC. THE RANGE SHOULD BE |
| | CALCULATED AT A MINIMUM OF 8 KW. FOR THE AC/AHU LOAD, |
| | IT SHOULD BE 100% OF AC, OR 65% OF AHU. LOAD CALC |
| | PROVIDED SHOWS 60%. PROVIDE CORRECTIONS. NEC 215.2, |
| | 220, TABLE 220.55, 408.30; FBC RE E3602.2 |
| | 2. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE |
| | OUTLETS IN GARAGE, INCLUDING GARAGE DOOR OPENER. |
| | PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.2 |
| | 3. CONDUIT FROM 200 AMP SERVICE DISCONNECT TO INTERIOR |
| | PANEL IS REQUIRED TO HAVE AN EQUIPMENT GROUNDING |
| | CONDUCTOR. PROVIDE CORRECTION. NEC 250.122; FBC RE |
| | E3704.6, 3607.3.1. |
| | 4. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A |
| | TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST |
| | ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND |
| | NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE |
| | INSTALLED AT THE FRONT AND BACK OF THE DWELLING. |
| | PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE E3901.7 |
| | 5. THERE IS A CONFLICT ON THE PLAN IN REFERENCE TO AFCI |
| | PROTECTION. A BIG BLOCK NOTE CORRECTLY STATES THE CODE. |
| | HOWEVER, A SMALLER NOTE ON LEFT OF PLAN UNDER THE TITLE |
| | "FOR NEW ELECTRIC ONLY" INCORRECTLY STATES THE CODE |
| | REQUIREMENT, STATING THAT KITCHENS DO NOT REQUIRE AFCI. |
| | PROVIDE CORRECTION. WPB FBC 107.2.1; NEC 210.12; FBC RE |
| | E3902 |
| | 6. A NOTE ON LEFT OF PLAN UNDER THE TITLE "FOR NEW |
| | ELECTRIC ONLY" STATES THAT RECEPTACLES SHALL BE TAMPER |
| | RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT |
| | APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE |
| | CORRECTION. NEC 406.12; FBC RE E4002.14 |
| | 7. RISER DIAGRAM STATES THAT THE METER AND SERVICE |
| | DISCONNECT ARE EXISTING, BUT THE PLAN SHOW THESE AS |
| | NEW. PROVIDE CLARIFICATION AND/OR CORRECTION. IF NEW OR |
| | BEING REPLACED, PROVIDE AVAILABLE SHORT CIRCUIT |
| | CALCULATION FOR SERVICE INCLUDING INFORMATION FROM THE |
| | POWER COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT |
| | CURRENT IS FOR THE SERVICE TO CONFIRM THE STATED AIC |
| | RATING OF THE SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, |
| | 110.10; FBC RE E3606.3; WPB FBC 107.2.1 |
| | 8. PROVIDE LOCATION OF CONDENSING UNITS ON PLAN. |
| | PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR SERVICING |
| | OF A/C EQUIPMENT WITHIN 25 FEET OF THE EQUIPMENT PER |
| | CODE. NEC 210.63; FBC RE E3901.12; WPB FBC 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |