| Plan Review Notes For Permit 19021300 |
| Permit Number |
19021300 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-03-08 07:35:08 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE NEW DESIGN PRESSURE CALCULATIONS FROM KEITH | | | LEBLANC P.E. OF FEDERAL ENGINEERING AND TESTING ARE | | | REQUIRED TO HAVE THE ENGINEER'S SEAL AND HANDWRITTEN | | | SIGNATURE. DIGITAL SIGNATURES ARE ONLY ALLOWED ON | | | ELECTRONICALLY SUBMITTED DOCUMENTS. FS471 & FAC | | | 61G15-23.003 |
|