2019-05-06 07:11:18PLUMBING 2ND REVIEW**DENIED**
  
 1) ANSWERED**
  
 2) NOT ADDRESSED**MENS TOILET COMPARTMENT IS MISSING
 THE SINK WITH-IN. SHT'S. A1-1, A2, A3.0 ALL SHOW A
 TOILET COMPARTMENT WITH IN THE TOILET ROOM. ALL TOILET
 COMPARTMENTS SHALL HAVE AN ACCESSIBLE TOILET WITH IN IT
 FBC-A 604.8.1.6
  
 3) NOT ADDRESSED** PROVIDE ALL REQUIRED CLEAR FLOOR
 SPACE AND TURNING SPACE FOR EACH FIXTURE LESS THE MOP
 SINK. BOTH THE DRINKING FOUNTAIN AND BREAK SINK SHALL
 HAVE THE CLEAR FLOOR SPACE PROVIDED.FBC-A 603.2.1,
 606.2, 305, 306
  
 4) ANSWERED**
  
 5) ANSWERED**
  
 7) ANSWERED**
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR