Plan Review Notes
Plan Review Notes For Permit 19021265
Permit Number 19021265
Review Stop P
Sequence Number 1
Notes
Date Text
2019-04-05 11:42:42PLUMBING 1ST REVIEW**DENIED**
  
 1) PROVIDE OCCUPANCY LOAD. FBC 107.3.5
  
 2) MENS TOILET COMPARTMENT IS MISSING THE SINK WITH-IN.
 FBC-A 604.8.1.6
  
 3) PROVIDE ALL REQUIRED CLEAR FLOOR SPACE AND TURNING
 SPACE FOR EACH FIXTURE LESS THE MOP SINK. FBC-A
 603.2.1, 606.2, 305, 306
  
 4) PROVIDE MEASUREMENT SHOWING MIRROR WITH BE MAX 40"
 TO THE REFLECTIVE SURFACE.
  
 5) SHT.P1.0 CALLS OUT FOR THE TOILET 18" MIN FROM SIDE
 WALL. THE TOILET SHALL BE 16"-18" FROM SIDE WALL. 18"
 WOULD BE THE MAX ALLOWED. FBC-A 604.2
  
 6) SHT,P1.0 CALLS OUT FOR THE GRAB BARS TO BE MOUNTED
 33"-36" TO THE CENTER. FBC-A 609.4 CALLS FOR THE
 MEASUREMENT TO BE TO THE TOP OF THE GRIPPING SURFACE.
  
 7) PROVIDE MORE DETAIL ON THE DESIGN OF THE SHELF THE
 WATER HEATER IS TO BE STORED ON. LIST MAX WEIGHT THIS
 DESIGN IS CAPABLE OF HANDLING WITH THE HEATER BEING
 FULL OF WATER. FBC 107.2.1
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  