| Plan Review Notes For Permit 19021265 |
| Permit Number |
19021265 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-04-05 11:42:42 | PLUMBING 1ST REVIEW**DENIED** | | | | | | 1) PROVIDE OCCUPANCY LOAD. FBC 107.3.5 | | | | | | 2) MENS TOILET COMPARTMENT IS MISSING THE SINK WITH-IN. | | | FBC-A 604.8.1.6 | | | | | | 3) PROVIDE ALL REQUIRED CLEAR FLOOR SPACE AND TURNING | | | SPACE FOR EACH FIXTURE LESS THE MOP SINK. FBC-A | | | 603.2.1, 606.2, 305, 306 | | | | | | 4) PROVIDE MEASUREMENT SHOWING MIRROR WITH BE MAX 40" | | | TO THE REFLECTIVE SURFACE. | | | | | | 5) SHT.P1.0 CALLS OUT FOR THE TOILET 18" MIN FROM SIDE | | | WALL. THE TOILET SHALL BE 16"-18" FROM SIDE WALL. 18" | | | WOULD BE THE MAX ALLOWED. FBC-A 604.2 | | | | | | 6) SHT,P1.0 CALLS OUT FOR THE GRAB BARS TO BE MOUNTED | | | 33"-36" TO THE CENTER. FBC-A 609.4 CALLS FOR THE | | | MEASUREMENT TO BE TO THE TOP OF THE GRIPPING SURFACE. | | | | | | 7) PROVIDE MORE DETAIL ON THE DESIGN OF THE SHELF THE | | | WATER HEATER IS TO BE STORED ON. LIST MAX WEIGHT THIS | | | DESIGN IS CAPABLE OF HANDLING WITH THE HEATER BEING | | | FULL OF WATER. FBC 107.2.1 | | | | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | CITY OF WEST PALM BEACH | | | 561-248-2703 | | | [email protected] | | | [email protected] | | | |
|