Plan Review Notes
Plan Review Notes For Permit 19021265
Permit Number 19021265
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-03-01 11:50:11THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEETS A 1.0 & A 1.2 - THERE ARE DOORS INDICATED
 WITHIN THE FIRE WALL, 112 & 107B, THAT THE DOOR
 SCHEDULE DOES NOT INDICATE WITH A REQUIRED RATING.
  
 THE DOOR ARE REQUIRED TO HAVE A 1 HOUR FIRE RATING PER
 NFPA 101
  
 8.3.3 FIRE DOORS AND WINDOWS.
 8.3.3.1 OPENINGS REQUIRED TO HAVE A FIRE PROTECTION
 RATING BY TABLE
 8.3.4.2 SHALL BE PROTECTED BY APPROVED, LISTED, LABELED
 FIRE DOOR
 ASSEMBLIES AND FIRE WINDOW ASSEMBLIES AND THEIR
 ACCOMPANYING
 HARDWARE, INCLUDING ALL FRAMES, CLOSING DEVICES,
 ANCHORAGE, AND
 SILLS IN ACCORDANCE WITH THE REQUIREMENTS OF NFPA 80,
 STANDARD
 FOR FIRE DOORS AND OTHER OPENING PROTECTIVES, EXCEPT AS
 OTHERWISE SPECIFIED IN THIS CODE.
 8.3.3.1.1 FIRE RESISTANCE?RATED GLAZING TESTED IN
 ACCORDANCE WITH
 ASTM E 119, STANDARD TEST METHODS FOR FIRE TESTS OF
 BUILDING
 CONSTRUCTION AND MATERIALS, OR ANSI/UL 263, STANDARD
 FOR FIRE
 TESTS OF BUILDING CONSTRUCTION AND MATERIALS, SHALL BE
 PERMITTED
 IN FIRE DOOR ASSEMBLIES AND FIRE WINDOW ASSEMBLIES
 WHERE TESTED
 AND INSTALLED IN ACCORDANCE WITH THEIR LISTINGS.
 8.3.3.1.2 NEW FIRE RESISTANCE?RATED GLAZING SHALL BE
 MARKED IN
 ACCORDANCE WITH TABLE 8.3.3.12 AND TABLE 8.3.4.2. SUCH
 MARKING
 SHALL BE PERMANENTLY AFFIXED.
  
 PLEASE REVIEW AND PROVIDE FOR THE REQUIRED FIRE RATING
 AT EACH DOOR.
  
  
  
 2) SHEETS A 1.0 & A 1.2 - THERE IS AN INDICATION OF A
 ROLL-UP DOOR OVER DOUBLE DOOR 101B WITHIN THE FIRE
 WALL. THE DOOR SCHEDULE DOES NOT IDENTIFY A FIRE RATING
 FOR THIS DOUBLE DOOR NOR THE ROLL-UP DOOR.
  
 ONE OR THE OTHER IS REQUIRED TO HAVE THE REQUIRED
 RATING PER THE ABOVE CCODE REFERNECE.
  
 PLEASE REVIEW AND PROVIDE FOR THE REQUIRED FIRE RATING
 FOR ONE OR THE OTHER DOOR.
  
  
  
  
 3) SHEET E 1 - THERE IS NO INDICATION OF A FIRE ALARM
 WORK.
  
 ANY FIRE ALARM WORK, DEMO OR NEW INSTALL SHALL BE UNDER
 SEPARATE SHOP DRAWINGS BY A CERTIFIED FIRE ALARM
 CONTRACTOR.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE.
  
  
  
  
 4) SHEET A 0.0 & A0.1 - THE IS NO INDICATIONS REGARDING
 THE CONTINUE MAINTENANCE AND FUNCTION OF THE FIRE
 SPRINKLER SYSTEM AND FIRE ALARM SYSTEMS.
  
 THESE SYSTEMS SHALL BE MAINTAINED THROUGHOUT DEMO AND
 NEW CONSTRUCTION.
  
 PLEASE REVIEW AND PROVICE AN APPLICABLE NOTE.
  
  
  
 5) SHEET A 1.0 - THE IS AN INDICATION OF A NEW FIRE
 WALL. THIS WALL SHALL BE PROPERLY IDENTIFIED PER NFPA
 101
  
 8.3.2.4 EACH NEW FIRE WALL, FIRE BARRIER, FIRE
 PARTITION, SMOKE
 BARRIER, SMOKE PARTITION, OR ANY OTHER NEW WALL
 REQUIRED TO HAVE
 PROTECTED OPENINGS SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR
 STENCILING ABOVE ANY DECORATIVE CEILING AND IN
 CONCEALED SPACES
 WITH THE WORDING, ?FIRE AND SMOKE BARRIER ? PROTECT
 ALL OPENINGS,? OR SIMILAR LANGUAGE. SUCH SIGNS OR
 STENCILING
 SHALL BE IN 4 INCH HIGH LETTERS, ? INCH STROKE, AND NOT
 MORE THAN 15
 FEET ON-CENTER.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE.
  
  
  
 6) SHEET E 2 - THERE IS AN INDICATION OF AN EXIT SIGN
 OVER DOOR 101B. THIS DOOR IS INDICATED AS HAVING A
 ROLL-UP DOOR OVER IT ON A FUSIBLE LINK.
  
 SHOULD THIS LIND ACTIVATE, THE DOOR WOULD CLOSE AND NOT
 FUNCTION AS AN EXIT. THERE IS AN EXIT DOOR RIGHT NEXT
 TO THIS DOOR.
  
 THE EXIT SIGN OVER THE 101B NEEDS TO BE REMOVED AND
 THIS DOOR WILL REMIAN A CONVENIENCE DOOR.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES AND NARRATIVE.
  
  
  
  
 7) SHEET E 2 - THERE IS A DOOR ON THE SIDE OF THE
 WAREHOUSE THAT IS NOT MARKED AS AN EXIT. THERE ARE NO
 TRAVEL DISTANCES INDICATED WITHIN THE SPACE VERIFYING
 THAT ONLY ONE EXIT IS REQUIRED.
  
  
 PER NFPA 101
  
 42.2.4 NUMBER OF MEANS OF EGRESS. THE NUMBER OF MEANS
 OF
 EGRESS SHALL COMPLY WITH 42.2.4.1 THROUGH 42.2.4.3.
 (SEE ALSO
 SECTION 7.4.)
 42.2.4.1 THE NUMBER OF MEANS OF EGRESS SHALL COMPLY
 WITH ANY OF
 THE FOLLOWING:
 (1) IN LOW HAZARD STORAGE OCCUPANCIES, A SINGLE MEANS
 OF EGRESS
 SHALL BE PERMITTED FROM ANY STORY OR SECTION.
 (2) IN ORDINARY HAZARD STORAGE OCCUPANCIES, A SINGLE
 MEANS OF
 EGRESS SHALL BE PERMITTED FROM ANY STORY OR SECTION,
 PROVIDED
 THAT THE EXIT CAN BE REACHED WITHIN THE DISTANCE
 PERMITTED AS A
 COMMON PATH OF TRAVEL.
 (3) ALL BUILDINGS OR STRUCTURES NOT COMPLYING WITH
 42.2.4.1(1) OR
 42.2.4.1(2) AND USED FOR STORAGE, AND EVERY SECTION
 THEREOF
 CONSIDERED SEPARATELY, SHALL HAVE NOT LESS THAN TWO
 SEPARATE
 MEANS OF EGRESS AS REMOTELY LOCATED FROM EACH OTHER AS
 PRACTICABLE.
  
 42.2.5 ARRANGEMENT OF MEANS OF EGRESS. MEANS OF EGRESS,
 ARRANGED IN ACCORDANCE WITH SECTION 7.5, SHALL NOT
 EXCEED THAT
 PROVIDED BY TABLE 42.2.5.
 42.2.6* TRAVEL DISTANCE TO EXITS. TRAVEL DISTANCE,
 MEASURED IN
 ACCORDANCE WITH SECTION 7.6, SHALL NOT EXCEED THAT
 PROVIDED BY
 TABLE 42.2.6.
  
 PLEASE PROVICE TRAVEL DISTANCES TO THE SINGLE EXIT OF
 PROVIDE AN EXIT SIGN OVER THIS DOOR.
  
  
  
  
 8) SHEET A 1.1 - THERE ARE INDICATIONS OF RACKS WITHIN
 THE WAREHOUSE. THE INSTALLATION OF RACKS SHALL BE UNDER
 SEPARATE SHOP DRAWINGS THAT INCLUDE MANUFACTURES SPECS,
 HEIGHT, FASTENING, AND A FIRE SPRINKLER REVIEW OF THE
 STORAGE COMMODITY WRAPPING AND PALLET TYPE.
  
 PLEASE BE SURE A REVIEW IS PROVIDED REGARDING IN-RACK
 FIRE SPRINKLERS REQUIREMENTS.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE.
  
  
  
  
 9) SHEET E 2 - WITH THE INSTALLATION OF RACKS THE PATH
 TO THE EXIT(S) MAY NOT BE CLEAR, DIRECTED OR PROPERLY
 ILLUMINATED PER THE CODE.
  
 PER NFPA 101
  
 42.2.8 ILLUMINATION OF MEANS OF EGRESS.
 42.2.8.1 MEANS OF EGRESS SHALL BE ILLUMINATED IN
 ACCORDANCE WITH
 SECTION 7.8.
 42.2.8.2 IN STRUCTURES OCCUPIED ONLY DURING DAYLIGHT
 HOURS, MEANS
 OF EGRESS SHALL BE PERMITTED TO BE ILLUMINATED WITH
 WINDOWS
 ARRANGED TO PROVIDE THE REQUIRED LEVEL OF ILLUMINATION
 ON ALL
 PORTIONS OF THE MEANS OF EGRESS DURING SUCH HOURS, WHEN
 APPROVED
 BY THE AUTHORITY HAVING JURISDICTION.
 42.2.9 EMERGENCY LIGHTING. EMERGENCY LIGHTING SHALL BE
 PROVIDED IN NORMALLY OCCUPIED STORAGE OCCUPANCIES IN
 ACCORDANCE
 WITH SECTION 7.9, EXCEPT FOR SPACES OCCUPIED ONLY
 DURING DAYLIGHT
 HOURS WITH NATURAL ILLUMINATION IN ACCORDANCE WITH
 42.2.8.2.
 42.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL
 HAVE SIGNS IN ACCORDANCE WITH SECTION 7.10.
  
 PLEASE REVIEW AND MAKE CORRECTIONS AS APPLICABLE.
  
  
  
 10) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  