| Plan Review Notes For Permit 19021240 |
| Permit Number |
19021240 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-03-11 10:09:29 | PLUMBING 1ST REVIEW**DENIED** | | | | | | 1) THE FOLLOWING SHHETS MUST BE SIGNED AND SEALED. ADA | | | 1.0, 1.1, 1.2 PER. F.A.C 61G1-16 | | | | | | 2) PROVIDE OVERALL DISTANCE FROM WATER HEATER TO NEW | | | SINKS. IF THE TOTAL DEVELOPED LENGTH IS OVER 50' A | | | RECIRCUATION LINE MUST BE ADDED . INSULATION OF BOTH | | | THE RETURN LINE AND HOT WATER LINE IN 1" WOULD BE | | | REQUIRED AS CALLED OUT ON SHT.P-0 NOTE #10 | | | | | | 3) SHT.ADA 1.2 SHOW'STOILET ROOMS AND ACCESSIBLE | | | ACCESSORIES. SHOW ON PLAN WHICH OF THE EXISTING ROOMS | | | THIS WILL APPLY TOO. FBC 107.3.5 | | | | | | 4) SHOW ON PLAN THE APPROCH AND CLEAR FLOOR SPACE FOR | | | THE 3 NEW SINKS AND ANY AND ALL PLUMBING ELEMENTS THAT | | | WILL COMPLY WITH FLORIDA ACCESSIBILITY 107.3.5 | | | | | | TIM HUNT | | | PLUMBING INSPECTOR/ PLANS EXAMINER | | | | | | 561-805-6711 SAMANTHA HILL*CHIEF PLANS EXAMINER | | | | | | 561-805-6724 GEORGE JOHNSON* PLUMBING PLANS EXAMINER | | | |
|