Plan Review Notes
Plan Review Notes For Permit 19021196
Permit Number 19021196
Review Stop G
Sequence Number 2
Notes
Date Text
2019-07-16 16:25:521ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 GAS COMMENTS: PREVIOUS COMMENTS
  
 3) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE,
 TERMINATION POINT, HEIGHT ABOVE THE ROOF AND ANCHORING
 DETAILS OF THE GAS VENT(S) PER 2017 FBC-FUEL GAS SECS.
 502 THRU 505
 DETAIL PROVIDED IS INSUFFICIENT PLEASE PROVIDE THE
 FOLLOWING INFORMATION A) THE TYPE OF VENT OR EXHAUST
 PIPING. B) LOCATION OF TERMINATION POINT. C) LENGTH OF
 THE VENT OR EXHAUST.D) SIZE OF VENT OR EXHAUST PIPING.
  
 4) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58. GAS
 APPLIANCES SHALL BE LISTED AND LABELED. INSTALLATION
 MANUAL SHALL CALL OUT THAT THE APPLIANCE IS ABLE TO RUN
 @ 15" W.C.
 CAN NOT BE DEFERRED SUBMITTAL
  
 5) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS
 APPLIANCES. WHERE COMBUSTION AIR IS PROVIDED BY THE
 BUILDING'S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR. 2017 FBC-FUEL
 GAS SEC.304.9.3
 COULD NOT LOCATE COMBUSTION AIR CALCULATIONS RESPONSE
 LETTER STATE CALC ARE ON SHEET MO.1 NONE FOUND.
  
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1 OR SHOW THAT EQUIPMENT
 IS ABLE TO RUN AT 15" W.C.
 CAN NOT BE DEFERRED SUBMITTAL
  
 NEW COMMENTS:
  
 1. PLEASE SHOW METER ON RISER. PER WPB AMEND TO FBC
 107.2.1
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  
  