| 2019-07-16 16:25:52 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | GAS COMMENTS: PREVIOUS COMMENTS |
| | |
| | 3) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE, |
| | TERMINATION POINT, HEIGHT ABOVE THE ROOF AND ANCHORING |
| | DETAILS OF THE GAS VENT(S) PER 2017 FBC-FUEL GAS SECS. |
| | 502 THRU 505 |
| | DETAIL PROVIDED IS INSUFFICIENT PLEASE PROVIDE THE |
| | FOLLOWING INFORMATION A) THE TYPE OF VENT OR EXHAUST |
| | PIPING. B) LOCATION OF TERMINATION POINT. C) LENGTH OF |
| | THE VENT OR EXHAUST.D) SIZE OF VENT OR EXHAUST PIPING. |
| | |
| | 4) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58. GAS |
| | APPLIANCES SHALL BE LISTED AND LABELED. INSTALLATION |
| | MANUAL SHALL CALL OUT THAT THE APPLIANCE IS ABLE TO RUN |
| | @ 15" W.C. |
| | CAN NOT BE DEFERRED SUBMITTAL |
| | |
| | 5) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS |
| | APPLIANCES. WHERE COMBUSTION AIR IS PROVIDED BY THE |
| | BUILDING'S MECHANICAL VENTILATION SYSTEM, THE SYSTEM |
| | SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN |
| | ADDITION TO THE REQUIRED VENTILATION AIR. 2017 FBC-FUEL |
| | GAS SEC.304.9.3 |
| | COULD NOT LOCATE COMBUSTION AIR CALCULATIONS RESPONSE |
| | LETTER STATE CALC ARE ON SHEET MO.1 NONE FOUND. |
| | |
| | 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION. 2014 FGC SEC.410.1 OR SHOW THAT EQUIPMENT |
| | IS ABLE TO RUN AT 15" W.C. |
| | CAN NOT BE DEFERRED SUBMITTAL |
| | |
| | NEW COMMENTS: |
| | |
| | 1. PLEASE SHOW METER ON RISER. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |
| | |
| | |