| 2019-04-11 15:43:52 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. SHEET E2.3 AND E2.4, NOTE 2 STATES THAT WATER |
| | FOUNTAIN GFCI RECEPTACLES SHOULD BE INSTALLED WITHIN |
| | THE ENCLOSURE OF THE WATER FOUNTAIN. GFCI RECEPTACLES |
| | FOR WATER FOUNTAINS ARE REQUIRED TO BE READILY |
| | ACCESSIBLE. PROVIDE CORRECTION. NEC 422.5, 422.52 |
| | 2. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| | DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| | SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND |
| | SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN |
| | THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE |
| | INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN |
| | SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC |
| | 105.1, 107.2.1 |
| | 3. ATS-MAIN DOES NOT APPEAR TO HAVE THE CLEARANCE IN |
| | THE FRONT AS REQUIRED PER NEC 110.26. PROVIDE |
| | CLARIFICATION AND/OR CORRECTION. NEC 110.26 |
| | 4. PROVIDE CLARIFICATION FOR DESIGN THAT INCLUDES TWO |
| | TRANSFER SWITCHES. ATS-MAIN IS FED FROM THE GENERATOR |
| | AND FPL, AND THEN FEEDS MSB. ATS-LS IS FED FROM MSB AND |
| | THE GENERATOR. SO, IN LOSS OF POWER, THE GENERATOR |
| | WOULD ENERGIZE MSB, THEREBY FEEDING ATS_LS AGAIN AS IT |
| | WOULD UNDER NORMAL POWER. THIS WOULD MAKE THE TRANSFER |
| | SWITCH THINK NORMAL POWER HAS RETURNED AND POSSIBLY NOT |
| | TRANSFER? OR TRANSFER ONCE THE GENERATOR ALLOWS ONLY TO |
| | IMMEDIATELY TRANSFER BACK? WHAT IS THE POINT OF THIS |
| | TRANSFER SWITCH IF ALL LOADS ARE ALREADY CAPABLE OF |
| | BEING FED BY THE GENERATOR? PROVIDE CLARIFICATION |
| | AND/OR CORRECTIONS AS NEEDED. WPB FBC 107.2.1; NEC |
| | 110.3 |
| | 5. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| | 6. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES |
| | EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN |
| | RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR |
| | LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |