| Notes |
| Date |
Text |
| 2019-03-07 11:39:01 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | | | | 1- TARCO UNDERLAYMENT NOA 11-0912.04 SUBMITTED EXPIRED | | | ON 01/25/17. NEED TO PROVIDE 2 COPIES OF CURRENT | | | PRODUCT APPROVAL AND CLEARLY MARK WHICH UNDERLAYMENT IS | | | GOING TO BE INSTALLED. | | | FAC 61G20-3.001. | | | | | | 2- SPECIFY SQUARE FOOTAGE OF METAL ROOFING TO BE | | | REPLACED AS REQUIRED BY CITY POLICY FOR ALL ROOFING | | | PERMITS. | | | | | | 3- VALUATION DECLARED IN THE PERMIT APPLICATION SEEMS | | | TO BE LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, | | | CONTRACTOR'S OVERHEAD AND PROFIT AS REQUIRED BY SEC. | | | 109.3 CITY AMENDMENTS. UPDATE VALUATION OR PROVIDE COPY | | | OF SIGNED CONTRACTS INCLUDING DESIGN PROFESSIONAL FEES. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|