| 2019-05-10 09:04:22 | RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | |
| | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR FLAT ROOF |
| | AND CLEARLY MARK WHICH APPROVED ASSEMBLY IS GOING TO BE |
| | INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. NOTE: IF THE |
| | SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR |
| | ALL ROOF ZONES, THEN SIGNED AND SEALED RAS 117 |
| | CALCULATIONS ARE REQUIRED. |
| | FAC 61G20-3.001. |
| | |
| | RESPONSE: |
| | - FLAT ROOF NOA 18-0919.07 SUBMITTED: CLEARLY MARK |
| | WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO |
| | VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. |
| | R301.1 FBC-RESIDENTIAL. NOTE: IF THE SELECTED ASSEMBLY |
| | DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, |
| | THEN SIGNED AND SEALED RAS 117 CALCULATIONS ARE |
| | REQUIRED. SEE GENERAL LIMITATION #7 ON LAST PAGE OF |
| | NOA. |
| | NOTE: ASSEMBLIES THAT ARE LIMITED BY GENERAL LIMITATION |
| | #9 MAY NOT BE USED IF THE MAXIMUM DESIGN PRESSURES |
| | DON'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES. |
| | GENERAL LIMITATION #9 DOESN'T ALLOW NAIL ENHANCEMENT. |
| | SEE GENERAL LIMITATION #9 ON LAST PAGE OF NOA. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |