| 2019-03-16 08:51:30 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. SCOPE OF WPRK NOT CLEAR ON PLAN. MARK WHAT IS |
| | EXISTING AND WHAT IS NEW. IF ANY LOAD IS BEING ADDED, |
| | PROVIDE LOAD CALCULATION TO CONFIRM SERVICE IS |
| | ADEQUATE. IF NO LOAD IS BEING ADDED, STATE THAT ON |
| | PLAN. NOTE 5 STATES ALL LIGHTS EXCEPT BATHROOMS TO BE |
| | SWITCHED FROM PANEL. IF THERE ARE LIGHTING CHANGES, |
| | AUTOMATIC CONTROL OF LIGHT FIXTURES IS REQUIRED PER |
| | ENERGY CODE. PROVIDE CLARIFICATION AND/OR CORRECTIONS |
| | AS NEEDED. WPB FBC 107.2.1; NEC 220; FBC EC C405.2 |
| | (CONFLICT EXIST BETWEEN LETTER PROVIDED AND PLAN. |
| | LETTER STATES THAT THE CHANDELIERS ARE BEING ADDED, BUT |
| | THE PLAN SHOWS THEM AS EXISTING. PROVIDE CLARIFICATION |
| | AND/OR CORRECTION. SHOW LOCATION OF ALL EXISTING ITEMS |
| | AS WELL AS NEW ITEMS.) |
| | |
| | NEW COMMENTS: |
| | |
| | 2. LOAD CALCULATION PROVIDED IS NOT ACCURATE. THE LOAD |
| | CALCULATION SHOULD INCLUDE EXISTING AND NEW LOADS TO |
| | CONFIRM CAPACITY OF SERVICE IS ADEQUATE. PLAN STATES AC |
| | IS EXISTING, BUT NO LOAD IS SHOWN FOR THAT. INCLUDE ALL |
| | LOADS. NEC 215.2, 220, 408.30 |
| | 3. SWITCHIHNG OF LIGHT FIXTURES NOT SHOWN. PROVIDE |
| | CORRECTION. WPB FBC 107.2.1 |
| | 4. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND |
| | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS |
| | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC |
| | 109.3 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |