Plan Review Notes
Plan Review Notes For Permit 19021148
Permit Number 19021148
Review Stop E
Sequence Number 2
Notes
Date Text
2019-03-16 08:51:30CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. SCOPE OF WPRK NOT CLEAR ON PLAN. MARK WHAT IS
 EXISTING AND WHAT IS NEW. IF ANY LOAD IS BEING ADDED,
 PROVIDE LOAD CALCULATION TO CONFIRM SERVICE IS
 ADEQUATE. IF NO LOAD IS BEING ADDED, STATE THAT ON
 PLAN. NOTE 5 STATES ALL LIGHTS EXCEPT BATHROOMS TO BE
 SWITCHED FROM PANEL. IF THERE ARE LIGHTING CHANGES,
 AUTOMATIC CONTROL OF LIGHT FIXTURES IS REQUIRED PER
 ENERGY CODE. PROVIDE CLARIFICATION AND/OR CORRECTIONS
 AS NEEDED. WPB FBC 107.2.1; NEC 220; FBC EC C405.2
 (CONFLICT EXIST BETWEEN LETTER PROVIDED AND PLAN.
 LETTER STATES THAT THE CHANDELIERS ARE BEING ADDED, BUT
 THE PLAN SHOWS THEM AS EXISTING. PROVIDE CLARIFICATION
 AND/OR CORRECTION. SHOW LOCATION OF ALL EXISTING ITEMS
 AS WELL AS NEW ITEMS.)
  
 NEW COMMENTS:
  
 2. LOAD CALCULATION PROVIDED IS NOT ACCURATE. THE LOAD
 CALCULATION SHOULD INCLUDE EXISTING AND NEW LOADS TO
 CONFIRM CAPACITY OF SERVICE IS ADEQUATE. PLAN STATES AC
 IS EXISTING, BUT NO LOAD IS SHOWN FOR THAT. INCLUDE ALL
 LOADS. NEC 215.2, 220, 408.30
 3. SWITCHIHNG OF LIGHT FIXTURES NOT SHOWN. PROVIDE
 CORRECTION. WPB FBC 107.2.1
 4. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved