| Date |
Text |
| 2019-03-01 10:56:57 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19021148 |
| | 3/1/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A1: REFER TO SECTION 301.1 FBC EX AND INDICATE |
| | ON THE PLAN WHICH METHOD OF COMPLIANCE WILL BE USED FOR |
| | THE PROPOSED PROJECT. |
| | |
| | 2) A3: PROVIDE THE TYPES AND SIZES OF NEW DUCTWORK |
| | SUPPLYING AIR TO THE STUDIOS AND DRESSING ROOMS- |
| | SECTION 603 FBC M. |
| | |
| | 3) A3: PROVIDE RETURN AIR FROM THE STUDIOS- SECTION |
| | 601.6 FBC M |
| | |
| | 4) A3: PROVIDE EXHAUST FOR THE DRESSING ROOMS AT A RATE |
| | OF .25 CFMS PER SF.- SEE TABLE 403.3.1.1 FBC M. |
| | |
| | 5) A3: A DUCT SMOKE DETECTOR IS REQUIRED IN THE SUPPLY |
| | AIR SYSTEM OF THE 5-TON AC SYSTEM PER SECTION 606.2.1. |
| | PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE |
| | MANUFACTURER'S SPECIFICATIONS INDICATE SYSTEMS ARE NOT |
| | CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |