Plan Review Notes
Plan Review Notes For Permit 19021148
Permit Number 19021148
Review Stop M
Sequence Number 1
Notes
Date Text
2019-03-01 10:56:571ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19021148
 3/1/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A1: REFER TO SECTION 301.1 FBC EX AND INDICATE
 ON THE PLAN WHICH METHOD OF COMPLIANCE WILL BE USED FOR
 THE PROPOSED PROJECT.
  
 2) A3: PROVIDE THE TYPES AND SIZES OF NEW DUCTWORK
 SUPPLYING AIR TO THE STUDIOS AND DRESSING ROOMS-
 SECTION 603 FBC M.
  
 3) A3: PROVIDE RETURN AIR FROM THE STUDIOS- SECTION
 601.6 FBC M
  
 4) A3: PROVIDE EXHAUST FOR THE DRESSING ROOMS AT A RATE
 OF .25 CFMS PER SF.- SEE TABLE 403.3.1.1 FBC M.
  
 5) A3: A DUCT SMOKE DETECTOR IS REQUIRED IN THE SUPPLY
 AIR SYSTEM OF THE 5-TON AC SYSTEM PER SECTION 606.2.1.
 PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE
 MANUFACTURER'S SPECIFICATIONS INDICATE SYSTEMS ARE NOT
 CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  