| 2019-02-27 11:32:39 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) SHEET 1 OF 4 - THERE IS NO ADDRESS OF THE OCCUPANCY |
| | ON THIS SHEET. |
| | |
| | PLEASE PROVIDE THE OCCUPANCY ADDRESS ON THIS SHEET. |
| | |
| | |
| | |
| | 2) SHEET 1 OF 4 - THERE IS AN INDICATION OF THIS SHEET, |
| | 1 OF 4; HOWEVER, THERE ARE ONLY THREE SHEETS SUBMITTED |
| | AND ARE INDICATED AS 2 OF 3 AND 3 OF 3. |
| | |
| | PLEASE CORRECT TO THE APPLICABLE PAGE(S) SUBMITTED. |
| | |
| | |
| | |
| | 3) THERE IS NO REFERNCE TO A FIRE CODE INDICATED ON ANY |
| | SHEET. |
| | |
| | PROPOSED PROJECTS SHALL MEET THE REQUIREMENTS OF THE |
| | 6TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH |
| | INCLUDES THE 2015 EDITION OF NFPA 1 AND NFPA 101. |
| | |
| | |
| | PLEASE REIVE AND ENSURE COMPLIANCE AND PROVIDE AN |
| | APPLICABLE NOTE UNDER CODE INFORMATION. |
| | |
| | |
| | |
| | 3) SHEET 1 OF 4 - THERE IS AN INDICATION OF THE |
| | OCCUPANCY CLASSIFICATION AS "B" (BUSINESS); HOWEVER, |
| | UNDER THE OCCUPANCY LOAD THERE IS AN INDICATION 1/80. |
| | |
| | PER THE FFPC, NFPA 101, CH 7, TABLE 7.3.1.2, A BUSINESS |
| | OCCUPANCY SHALL CALCULATE AT 1/100. |
| | |
| | ADDITIONALLY, A STORAGE/OFFICE IS INDICATED AND BASED |
| | ON THE INTENDED USE MAY CLACULATE AT 1/200. |
| | |
| | PLEASE REVIEW AMD CORRECT AS APPLICABLE. |
| | |
| | |
| | |
| | 4) SHEET 2 OF 3 - THERE ARE NO EXITS SIGNS INDICATED |
| | BUT WILL BE VERIFIED ON INSPECTION IF THEY ARE |
| | EXISTING. |
| | |
| | PER NFPA 101, CH 7 |
| | |
| | 7.10 MARKING OF MEANS OF EGRESS. |
| | 7.10.1 GENERAL. |
| | 7.10.1.1 WHERE REQUIRED. MEANS OF EGRESS SHALL BE |
| | MARKED IN |
| | ACCORDANCE WITH SECTION 7.10 WHERE REQUIRED IN CHAPTERS |
| | 11 |
| | THROUGH 43. |
| | |
| | PLEASE ENSURE THAT EXITS ARE PROPERLY MARKED. |
| | |
| | |
| | |
| | 5) SHEET 2 OF 3 - A REAR DOOR LEADING INTO A |
| | STORAGE/OFFICE SPACE WITH AN EXTERIOR DOOR LEADING OUT |
| | OF THE BUILDING IS INDICATED. |
| | |
| | PER NFPA 101 CH 7 |
| | |
| | 7.5.2 IMPEDIMENTS TO EGRESS. SEE ALSO 7.1.9 AND |
| | 7.2.1.5. |
| | 7.5.2.1* ACCESS TO AN EXIT SHALL NOT BE THROUGH |
| | KITCHENS, |
| | STOREROOMS OTHER THAN AS PROVIDED IN CHAPTERS 36 AND |
| | 37, |
| | RESTROOMS, CLOSETS, BEDROOMS OR SIMILAR SPACES, OR |
| | OTHER ROOMS OR |
| | SPACES SUBJECT TO LOCKING, UNLESS PASSAGE THROUGH SUCH |
| | ROOMS OR |
| | SPACES IS PERMITTED FOR THE OCCUPANCY BY CHAPTER 18, |
| | 19, 22, OR 23. |
| | |
| | AN EXIT SIGN OVER THIS STORAGE/OFFICE DOOR WOULD NOT BE |
| | APPLICABLE IF THE ROOM IS USED FOR GENERAL STORAGE. |
| | |
| | AN EXIT SIGN OVER THE EXTERIOR DOOR WOULD BE |
| | APPLICABLE. |
| | |
| | |
| | |
| | 6) SHEET 1 OF 4 - THERE IS AN INDICATION LABELD "AREA" |
| | 1050 S.F. A/C; HOWEVER, THERE IS A SQ 2248 INDICATED |
| | FOR OCCUPANCY. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSITFY WHAT THE SQ IS. |
| | |
| | |
| | |
| | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |