Plan Review Notes For Permit 19021148
Permit Number 19021148
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-02-27 11:32:39THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET 1 OF 4 - THERE IS NO ADDRESS OF THE OCCUPANCY
 ON THIS SHEET.
  
 PLEASE PROVIDE THE OCCUPANCY ADDRESS ON THIS SHEET.
  
  
  
 2) SHEET 1 OF 4 - THERE IS AN INDICATION OF THIS SHEET,
 1 OF 4; HOWEVER, THERE ARE ONLY THREE SHEETS SUBMITTED
 AND ARE INDICATED AS 2 OF 3 AND 3 OF 3.
  
 PLEASE CORRECT TO THE APPLICABLE PAGE(S) SUBMITTED.
  
  
  
 3) THERE IS NO REFERNCE TO A FIRE CODE INDICATED ON ANY
 SHEET.
  
 PROPOSED PROJECTS SHALL MEET THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH
 INCLUDES THE 2015 EDITION OF NFPA 1 AND NFPA 101.
  
  
 PLEASE REIVE AND ENSURE COMPLIANCE AND PROVIDE AN
 APPLICABLE NOTE UNDER CODE INFORMATION.
  
  
  
 3) SHEET 1 OF 4 - THERE IS AN INDICATION OF THE
 OCCUPANCY CLASSIFICATION AS "B" (BUSINESS); HOWEVER,
 UNDER THE OCCUPANCY LOAD THERE IS AN INDICATION 1/80.
  
 PER THE FFPC, NFPA 101, CH 7, TABLE 7.3.1.2, A BUSINESS
 OCCUPANCY SHALL CALCULATE AT 1/100.
  
 ADDITIONALLY, A STORAGE/OFFICE IS INDICATED AND BASED
 ON THE INTENDED USE MAY CLACULATE AT 1/200.
  
 PLEASE REVIEW AMD CORRECT AS APPLICABLE.
  
  
  
 4) SHEET 2 OF 3 - THERE ARE NO EXITS SIGNS INDICATED
 BUT WILL BE VERIFIED ON INSPECTION IF THEY ARE
 EXISTING.
  
 PER NFPA 101, CH 7
  
 7.10 MARKING OF MEANS OF EGRESS.
 7.10.1 GENERAL.
 7.10.1.1 WHERE REQUIRED. MEANS OF EGRESS SHALL BE
 MARKED IN
 ACCORDANCE WITH SECTION 7.10 WHERE REQUIRED IN CHAPTERS
 11
 THROUGH 43.
  
 PLEASE ENSURE THAT EXITS ARE PROPERLY MARKED.
  
  
  
 5) SHEET 2 OF 3 - A REAR DOOR LEADING INTO A
 STORAGE/OFFICE SPACE WITH AN EXTERIOR DOOR LEADING OUT
 OF THE BUILDING IS INDICATED.
  
 PER NFPA 101 CH 7
  
 7.5.2 IMPEDIMENTS TO EGRESS. SEE ALSO 7.1.9 AND
 7.2.1.5.
 7.5.2.1* ACCESS TO AN EXIT SHALL NOT BE THROUGH
 KITCHENS,
 STOREROOMS OTHER THAN AS PROVIDED IN CHAPTERS 36 AND
 37,
 RESTROOMS, CLOSETS, BEDROOMS OR SIMILAR SPACES, OR
 OTHER ROOMS OR
 SPACES SUBJECT TO LOCKING, UNLESS PASSAGE THROUGH SUCH
 ROOMS OR
 SPACES IS PERMITTED FOR THE OCCUPANCY BY CHAPTER 18,
 19, 22, OR 23.
  
 AN EXIT SIGN OVER THIS STORAGE/OFFICE DOOR WOULD NOT BE
 APPLICABLE IF THE ROOM IS USED FOR GENERAL STORAGE.
  
 AN EXIT SIGN OVER THE EXTERIOR DOOR WOULD BE
 APPLICABLE.
  
  
  
 6) SHEET 1 OF 4 - THERE IS AN INDICATION LABELD "AREA"
 1050 S.F. A/C; HOWEVER, THERE IS A SQ 2248 INDICATED
 FOR OCCUPANCY.
  
 PLEASE REVIEW AND CORRECT OR JUSITFY WHAT THE SQ IS.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  