| 2019-02-28 07:55:11 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. SCOPE OF WPRK NOT CLEAR ON PLAN. MARK WHAT IS |
| | EXISTING AND WHAT IS NEW. IF ANY LOAD IS BEING ADDED, |
| | PROVIDE LOAD CALCULATION TO CONFIRM SERVICE IS |
| | ADEQUATE. IF NO LOAD IS BEING ADDED, STATE THAT ON |
| | PLAN. NOTE 5 STATES ALL LIGHTS EXCEPT BATHROOMS TO BE |
| | SWITCHED FROM PANEL. IF THERE ARE LIGHTING CHANGES, |
| | AUTOMATIC CONTROL OF LIGHT FIXTURES IS REQUIRED PER |
| | ENERGY CODE. PROVIDE CLARIFICATION AND/OR CORRECTIONS |
| | AS NEEDED. WPB FBC 107.2.1; NEC 220; FBC EC C405.2 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |