2019-02-28 07:55:11CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SCOPE OF WPRK NOT CLEAR ON PLAN. MARK WHAT IS
 EXISTING AND WHAT IS NEW. IF ANY LOAD IS BEING ADDED,
 PROVIDE LOAD CALCULATION TO CONFIRM SERVICE IS
 ADEQUATE. IF NO LOAD IS BEING ADDED, STATE THAT ON
 PLAN. NOTE 5 STATES ALL LIGHTS EXCEPT BATHROOMS TO BE
 SWITCHED FROM PANEL. IF THERE ARE LIGHTING CHANGES,
 AUTOMATIC CONTROL OF LIGHT FIXTURES IS REQUIRED PER
 ENERGY CODE. PROVIDE CLARIFICATION AND/OR CORRECTIONS
 AS NEEDED. WPB FBC 107.2.1; NEC 220; FBC EC C405.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  