2019-02-27 16:51:33****CORRECTIONS****
 W.P.B. PERMIT: 19021148
 REVIEWED: FEBRUARY 27, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 1. 61G1-16.004 FLORIDA ADMINISTRATIVE CODE. TITLE
 BLOCK. A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL
 OR INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS THAT ARE REQUIRED TO BE SIGNED
 AND SEALED. THE TITLE BLOCK MUST, AT A MINIMUM, CONTAIN
 THE FOLLOWING INFORMATION:
 PLEASE RE-PRINT THE COVER PAGE TO INCLUDE THE TITLE
 BLOCK.
  
 2. 501 FBC[EXISTING] STATE THE LEVEL OF ALTERATION FOR
 WORK BEING PERFORMED.
  
 3. 501 FBC[EXISTING] PROVIDE EXISTING OCCUPANCY.
 IF NO CHANGE IN OCCUPANCY, PLEASE STATE OCCUPANCY AS NO
 CHANGE FROM PREVIOUS. THIS WILL SATISFY THE IMPACT STOP
 THAT WAS INCLUDED WITH THIS PERMIT REVIEW.
  
 4. 107.5.3 FBC[AMENDED] SHEET A-1 IN CODE INFORMATION
 THAT IT IS USING 2017 FBC 5TH EDITION. PLEASE CHANGE TO
 6TH EDITION. PLEASE ADD LEVEL OF ALTERATION TO DESIGN
 DATA.
  
 5. 107.5.3 FBC[AMENDED] IS THE BUILDING SPRINKLERED OR
 NON SPRINKLERED?
  
 6. 107.3.5 FBC[B] REMOVE NOTE #4 IN SCOPE OF ON SHEET
 A-1 THAT STATES NO CHANGE IN A/C CONFIGURATION.
  
 7. 1005.1 FBC[B] GENERAL. ALL PORTIONS OF THE MEANS OF
 EGRESS SYSTEM SHALL BE SIZED IN ACCORDANCE WITH THIS
 SECTION.
  
 8. 1004.1 FBC[B] SHEET A-1 SHOWS 2248 SF @ 1/80 = 74.8
 PERSONS. PLEASE REVIEW THIS AS THE OCCUPANT LOAD
 DOESN'T MATCH WHAT IS PROVIDED IN TABLE 1004.1.2 OR IN
 NFPA 101.
  
 9. 1004.1 FBC[B] SHEET A-1 IN AREA STATES 1050 SQ. FT
 AND OCCUPANT LOAD STATES 2248 SQ. FT. PLEASE CLARIFY
 THE SQ. FOOTAGE AND IF 1050 IS THE AREA OF WORK STATE
 AS SUCH WITH THE LEVEL OF ALTERATION.
  
 10. 1004.1 FBC[B] PROVIDE LIFE SAFETY TO SHOW NUMBER OF
 EXITS AND COMMON PATH OF TRAVEL.
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -COMMENTS ARE A BRIEF OVERVIEW OF CODE SECTIONS.
 FURTHER REVIEW OF THE REFERENCED CODE SECTIONS WILL BE
 REQUIRED.
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  