| 2019-04-09 14:23:08 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19021070 |
| | 4/9/2019 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW |
| | RTU-1 SYSTEM- SECTION C403.2.1 FBC EC |
| | |
| | 2) SHEET M1.1.1: A DUCT SMOKE DETECTOR IS REQUIRED IN |
| | THE SUPPLY AIR SYSTEM OF THE 5-TON RTU PER SECTION |
| | 606.2.1. PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED |
| | IF THE MANUFACTURER'S SPECIFICATIONS INDICATE THE |
| | SYSTEM IS NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF |
| | SUPPLY AIR. |
| | |
| | 3) M1.1.1 & M1.1.2: PROVIDE AN AUTOMATICALLY CONTROLLED |
| | SHUTOFF DAMPER FOR THE RTU OUTDOOR AIR INTAKE- SECTION |
| | C403.2.4.3 FBC-EC. |
| | |
| | 4) M2.1.1: THE VENTILATION CALCULATIONS ARE NOT IN |
| | COMPLIANCE WITHTABLE 403.3.1.1 FBC M. THE RATE IS |
| | CALCULATED AT 100 PWRSONS PER 1000 SF. AT 7.5 CFMS PER |
| | PERSON + 0.18 CFMS PER SF. PLEASE CORRECT. |
| | |
| | 5) M1.1.2: STRUCTURAL ENGINEERING IS REQUIRED FOR THE |
| | NEW ROOF OPENING, AND INSTSALLATIONS OF THE NEW CURB |
| | AND RTU- SECTION 301.15 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |